XY XY-MD02 Modbus register map

RS485 temperature and humidity transmitter with an SHT20 sensor, Modbus RTU

  • Verified
  • 6 registers
  • Modbus RTU
  • Revision 2 · 2026-11-08

Verified: Tested on a real device.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first default
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
4 holding registers, 2 input registers
Groups
2
Revision
2 · 2026-11-08
Added
()
File
maps/xy/xy-md02.mbmap.json · 4 KB · history
SHA-256
740fbc5a2b323a72bf92d164bc7325963316de36b6ba6647dbd4ed383dc0311f

Sources and notes

  • XY-MD02 Modbus RTU RS485 SHT20 Temperature Humidity Transmitter manual
    Modbus protocol tables and examples
  • Test report on an XY-MD02 · 2026-11-08
    baud rate encoding, correction scale and stop bits

Source: XY-MD02 Modbus RTU RS485 SHT20 Temperature Humidity Transmitter manual

  • Function codes 0x03, 0x04, 0x06 and 0x10. Temperature and humidity are input registers (FC04); the settings are holding registers (FC03 read, FC06 or FC10 write).
  • Addresses are the ones in the manual's frames: temperature is read from address 0x0001 (frame 01 04 00 01 00 01).
  • The baud rate register holds the rate itself in bit/s (9600 reads 9600), as in the manual's write example; the 0/1/2 codes in the manual's register table are wrong.
  • The temperature correction is in tenths of a degree: writing 10 raised the reading by about 1 °C. The humidity correction was not tested and is taken to work the same way. The manual's range of -10 to 10 is therefore -100 to 100 on the wire.
  • Factory defaults: 9600 bit/s, 8N1, address 1. The device uses 1 stop bit, but it also answers a master set to 2.
  • A new address or baud rate applies only after the device is powered off and on again.
  • Tested on an XY-MD02, firmware not shown, November 2026: temperature (including -1.8 °C, read as 0xFFEE), humidity, the address and baud rate registers, the serial settings and the temperature correction. The humidity correction was not tested.
AreaAddressNameTypeAccessUnitScaleDescription
IR 1 int16 R °C ×0.1 Signed value in tenths of a degree (0x0131 is 30.5 °C, 0xFF33 is -20.5 °C)
IR 2 uint16 R %RH ×0.1 Relative humidity in tenths of a percent (0x0222 is 54.6 %RH)
HR 257 uint16 RW Modbus slave address, default 1. Applies after a power cycle
HR 258 uint16 RW bit/s The rate itself, for example 9600 or 19200. Applies after a power cycle
HR 259 int16 RW °C ×0.1 Added to the measured temperature, in steps of 0.1 °C
HR 260 int16 RW %RH ×0.1 Added to the measured humidity, in steps of 0.1 %RH