- Manufacturers
- Continental Control Systems
Continental Control Systems
3 device maps · 411 registers · ctlsys.com
- Verified 0
- Official 0
- Unofficial 3
Devices
| Model | Description | Status | Protocol | Registers |
|---|---|---|---|---|
| Wattnode | Unofficial | 50 | ||
| WattNode WNC | 3-phase energy meter, Modbus RTU/TCP. FC03/04 read, FC06/16 write. Basic FP (f32): energy kWh at 1000-1006, power W at 1008-1014, voltage V at 1016-1030, freq at 1032. Advanced FP: per-phase energy+reactive+apparent at 1100-1136, PF at 1138-1144, reactive/apparent power at 1146-1160, current A at 1162-1166, demand at 1168-1180. Integer equivalents (s32 energy, s16 power/volt/current) at 1200-1220 (basic) and 1300-1361 (advanced). Config at 1600-1622. Comms at 1650-1655. Diagnostics at 1700-1722. | Unofficial | 159 | |
| WattNode WND-WR-MB | Wide-range 3-phase energy meter, Modbus RTU/TCP. FC03/04 read, FC06/16 write. Basic FP (f32): energy kWh at 1000-1006, power W at 1008-1014, voltage V at 1016-1030, freq at 1032. PowerFast (10 Hz, f32 only) at 1034-1042. Advanced FP: per-element energy net/pos/neg at 1100-1120, reactive energy net/pos/neg at 1122-1196, apparent at 1130-1136, PF at 1138-1144, reactive/apparent power at 1146-1160, current at 1162-1166, demand at 1168-1180. Integer equivalents at 1200-1220 (basic) and 1300-1377 (advanced). Config at 1600-1685. Comms at 1650-1658. Diagnostics at 1700-1761. | Unofficial | 202 |
Missing a Continental Control Systems device? Request it or add a map.