 "$schema": "https://raw.githubusercontent.com/nobrega8/mbmap-library/main/schema/mbmap-2.schema.json",
 "mbmap": 2,
 "vendor": "ISE",
 "model": "smart connect Modbus Vaillant (geoTHERM/3 heat pump)",
 "vendor_website": "ise.de",
 "description": "Vaillant geoTHERM/3 heat pump through the ise Modbus TCP gateway",
 "revision": 1,
 "revised": "2026-11-11",
 "source": "ISE Individuelle Software und Elektronik, ise smart connect Modbus Vaillant, Product Manual (order no. S-0002-007), section 4.5",
 "sources": [
  {
   "title": "ise smart connect Modbus Vaillant, Product Manual",
   "version": "S-0002-007",
   "note": "Section 4.5 Modbus registers and 4.6 data types"
  }
 ],
 "notes": [
  "The gateway (ise smart connect Modbus Vaillant with the ise eBUS adapter) answers Modbus TCP and reads the Vaillant device over eBUS; this map is for unit ID 1, the geoTHERM/3 heat pump (the manual's Modbus unit ID). The manual covers the Vaillant geoTHERM/3 VWS 220/3 to 460/3 ground-source heat pump only; other Vaillant heat pumps such as the aroTHERM are not covered.",
  "Modbus TCP, port 502 by default (configurable from 2000 to 4000). Functions 0x03, 0x04, 0x06 and 0x10. Addresses are one-based: register 1 is address 1 with address_base 1.",
  "32-bit values (uint32 and IEEE 754 floats) take two registers and the first register holds the least significant word (little word order); they can only be written together with function 0x10.",
  "The gateway polls the heat pump over eBUS every 2 to 60 minutes depending on the value (2 minutes for most sensors, 15 for error history and outside temperature, 60 for counters), so reads show the last polled value. A request to a unit ID whose device is not present gets exception 0x0B."
 ],
 "protocol": "tcp",
 "port": 502,
 "unit_id": 1,
 "byte_order": "big",
 "word_order": "little",
 "address_base": 1,
 "x_status": "official",
 "enums": {
  "dtc": {
   "514": "Error comp inlet sensor",
   "515": "Error evaporator sensor",
   "516": "Error heat source outlet sensor",
   "517": "Error comp outlet sensor",
   "518": "Error heat source inlet sensor",
   "519": "Error HP return sensor",
   "520": "Error HP flow sensor",
   "521": "Error AF sensor",
   "522": "Error SP sensor",
   "523": "Error VF1 sensor",
   "524": "Error RF1 sensor",
   "525": "Error VF2 sensor",
   "526": "Sensor fault: TCoilLiquidOpen",
   "527": "Error heat source outlet sensor",
   "528": "Error condenser sensor",
   "529": "Heat source anti freezing protection: delta T6-T7",
   "530": "Heat source anti freezing protection: T5<4 °C",
   "531": "Heat source anti freezing protection: T6<-10 °C",
   "532": "No water flow",
   "533": "Abnormal cooling of the CH circuit",
   "534": "Building circuit: floor protection active",
   "535": "CH flow temperature too high for floor heating",
   "536": "Compressor outlet overheat",
   "537": "Refrigerant pressure too high",
   "538": "Refrigerant pressure too high, check CH pump",
   "539": "Refrigerant pressure too low",
   "540": "CH pressure too low",
   "541": "Brine pressure too low",
   "542": "CH return temperature too high",
   "543": "Fan overheat thermostat open",
   "544": "One or two phases missing",
   "545": "Wrong phase order",
   "546": "Refrigerant pressure sensors fault",
   "547": "Operation interlock: heat source anti freezing delta T6-T7",
   "548": "Operation interlock: heat source anti freezing T5<4 °C",
   "549": "Operation interlock: heat source anti freezing T6<-10 °C",
   "550": "Operation interlock: no water flow",
   "551": "Operation interlock: CH circuit anti freezing protection",
   "552": "Operation interlock: CH flow temperature too high",
   "553": "Operation interlock: compressor outlet overheat",
   "554": "Refrigerant pressure out of range",
   "555": "CH circuit pressure sensor error",
   "556": "Brine circuit pressure sensor error",
   "557": "Hydraulic scheme and external sensors do not match",
   "558": "Appliance code and internal sensors do not match",
   "561": "No power for compressor",
   "577": "Operation interlock: refrigerant pressure too high",
   "578": "Operation interlock: refrigerant pressure too low",
   "579": "Operation interlock: pressostats opened",
   "580": "Brine pressure low (below 0.6 bar for more than a minute)",
   "1471": "Exchanger temperature sensor error",
   "1472": "Air inlet temperature sensor error",
   "1478": "Too low evaporation temperature, retrying",
   "1480": "Too high evaporation temperature, retrying",
   "1495": "Fluid flow reversed (warning)",
   "1496": "Air flow blocked (warning)",
   "1497": "Fan blocked or defective or air flow fully blocked",
   "1498": "Lost communication with outdoor unit",
   "1499": "De-icing was incomplete (warning)",
   "1500": "STB ODU is open (error)",
   "1501": "CH pump failure",
   "1502": "Brine pump failure",
   "65535": "No fault existing"
  },
  "ebus_error": {
   "0": "No error",
   "1": "geoTHERM/3, VR60 or VR90 not found",
   "2": "No compatible geoTHERM/3, VR60 or VR90 found",
   "3": "Error in communication with the ise eBUS adapter",
   "4": "eBUS cable not connected",
   "5": "No answer from eBUS",
   "7": "Value not permitted"
  },
  "ebus_state": {
   "0": "No error / device found",
   "1": "Error during eBUS communication / device not found"
  },
  "hp_status": {
   "0": "Standby",
   "1": "Cooling",
   "2": "De-icing",
   "3": "CH: compressor only",
   "4": "CH: compressor and auxiliary",
   "5": "CH: auxiliary only",
   "6": "CH: compressor and auxiliary off",
   "7": "DHW: compressor and auxiliary off",
   "8": "DHW: compressor only",
   "9": "DHW: auxiliary only",
   "10": "Peak rate: hot water",
   "11": "Peak rate: standby",
   "12": "Acceleration mode",
   "13": "Frost protection heating",
   "14": "Frost protection cylinder",
   "15": "Legionella protection",
   "16": "Automatic pump spin",
   "17": "Floor drying",
   "18": "Venting mode",
   "19": "Fault shutdown: heating",
   "20": "Error shutdown: heating",
   "21": "Fault shutdown: DHW",
   "22": "Error shutdown: DHW",
   "23": "Malfunction",
   "24": "Blocking error",
   "25": "Operation interlock",
   "26": "CH compressor overrun",
   "27": "DHW compressor overrun",
   "28": "Cooling and DHW",
   "29": "CH return too high"
  },
  "mixer": {
   "0": "Stationary",
   "1": "Opening",
   "2": "Closing"
  },
  "op_hc": {
   "1": "On",
   "2": "Off",
   "3": "Auto",
   "4": "Eco",
   "5": "Low"
  },
  "sensor": {
   "0": "No fault",
   "85": "Short-circuit",
   "170": "Interrupt"
  },
  "status": {
   "0": "Off",
   "1": "On"
  }
 },
 "registers": [
  {
   "name": "eBUS error",
   "group": "Input registers",
   "area": "input",
   "address": 1,
   "type": "uint16",
   "access": "R",
   "enum": "ebus_state"
  },
  {
   "name": "eBUS last error",
   "group": "Input registers",
   "area": "input",
   "address": 2,
   "type": "uint16",
   "access": "R",
   "enum": "ebus_error"
  },
  {
   "name": "Air brine outlet temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 3,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Air brine outlet temperature",
   "group": "Input registers",
   "area": "input",
   "address": 4,
   "type": "float32",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Brine inlet temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 6,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Brine inlet temperature",
   "group": "Input registers",
   "area": "input",
   "address": 7,
   "type": "float32",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Environment circuit pressure sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 9,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Environment circuit pressure",
   "group": "Input registers",
   "area": "input",
   "address": 10,
   "type": "float32",
   "access": "R",
   "unit": "bar"
  },
  {
   "name": "Fan / brine pump status",
   "group": "Input registers",
   "area": "input",
   "address": 12,
   "type": "uint16",
   "access": "R",
   "enum": "status"
  },
  {
   "name": "Compressor starts",
   "group": "Input registers",
   "area": "input",
   "address": 13,
   "type": "uint32",
   "access": "R"
  },
  {
   "name": "Compressor operating hours",
   "group": "Input registers",
   "area": "input",
   "address": 15,
   "type": "uint32",
   "access": "R",
   "unit": "h"
  },
  {
   "name": "Compressor running",
   "group": "Input registers",
   "area": "input",
   "address": 17,
   "type": "uint16",
   "access": "R",
   "enum": "status"
  },
  {
   "name": "Compressor high pressure sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 18,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Compressor high pressure",
   "group": "Input registers",
   "area": "input",
   "address": 19,
   "type": "float32",
   "access": "R",
   "unit": "bar"
  },
  {
   "name": "Compressor low pressure sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 21,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Compressor low pressure",
   "group": "Input registers",
   "area": "input",
   "address": 22,
   "type": "float32",
   "access": "R",
   "unit": "bar"
  },
  {
   "name": "Compressor outlet temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 24,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Compressor outlet temperature",
   "group": "Input registers",
   "area": "input",
   "address": 25,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "External top cylinder temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 26,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "External top cylinder temperature",
   "group": "Input registers",
   "area": "input",
   "address": 27,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "External bottom cylinder temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 28,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "External bottom cylinder temperature",
   "group": "Input registers",
   "area": "input",
   "address": 29,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Error history 1",
   "group": "Input registers",
   "area": "input",
   "address": 30,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 2",
   "group": "Input registers",
   "area": "input",
   "address": 31,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 3",
   "group": "Input registers",
   "area": "input",
   "address": 32,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 4",
   "group": "Input registers",
   "area": "input",
   "address": 33,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 5",
   "group": "Input registers",
   "area": "input",
   "address": 34,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 6",
   "group": "Input registers",
   "area": "input",
   "address": 35,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 7",
   "group": "Input registers",
   "area": "input",
   "address": 36,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 8",
   "group": "Input registers",
   "area": "input",
   "address": 37,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 9",
   "group": "Input registers",
   "area": "input",
   "address": 38,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Error history 10",
   "group": "Input registers",
   "area": "input",
   "address": 39,
   "type": "uint16",
   "access": "R",
   "enum": "dtc"
  },
  {
   "name": "Heat pump status",
   "group": "Input registers",
   "area": "input",
   "address": 40,
   "type": "uint16",
   "access": "R",
   "enum": "hp_status"
  },
  {
   "name": "Earned environment energy",
   "group": "Input registers",
   "area": "input",
   "address": 41,
   "type": "uint32",
   "access": "R",
   "unit": "kWh"
  },
  {
   "name": "Outside temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 43,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Outside temperature",
   "group": "Input registers",
   "area": "input",
   "address": 44,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Flow temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 45,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Flow temperature",
   "group": "Input registers",
   "area": "input",
   "address": 46,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Return temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 47,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Return temperature",
   "group": "Input registers",
   "area": "input",
   "address": 48,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Heating circuit pressure sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 49,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "Heating circuit pressure",
   "group": "Input registers",
   "area": "input",
   "address": 50,
   "type": "float32",
   "access": "R",
   "unit": "bar"
  },
  {
   "name": "Energy integral value",
   "group": "Input registers",
   "area": "input",
   "address": 52,
   "type": "int16",
   "access": "R",
   "unit": "°min"
  },
  {
   "name": "VF2 flow temperature sensor state",
   "group": "Input registers",
   "area": "input",
   "address": 53,
   "type": "uint16",
   "access": "R",
   "enum": "sensor"
  },
  {
   "name": "VF2 flow temperature",
   "group": "Input registers",
   "area": "input",
   "address": 54,
   "type": "int16",
   "access": "R",
   "unit": "°C"
  },
  {
   "name": "Mixer activation",
   "group": "Input registers",
   "area": "input",
   "address": 55,
   "type": "uint16",
   "access": "R",
   "enum": "mixer"
  },
  {
   "name": "Heating circuit pump status",
   "group": "Input registers",
   "area": "input",
   "address": 56,
   "type": "uint16",
   "access": "R",
   "enum": "status"
  },
  {
   "name": "Brine pump speed control",
   "group": "Holding registers",
   "area": "holding",
   "address": 57,
   "type": "uint16",
   "access": "RW",
   "unit": "%"
  },
  {
   "name": "Compressor hysteresis",
   "group": "Holding registers",
   "area": "holding",
   "address": 58,
   "type": "uint16",
   "access": "RW",
   "unit": "K"
  },
  {
   "name": "Energy integral since compressor started",
   "group": "Holding registers",
   "area": "holding",
   "address": 59,
   "type": "int16",
   "access": "RW",
   "unit": "°min"
  },
  {
   "name": "CH pump speed control",
   "group": "Holding registers",
   "area": "holding",
   "address": 60,
   "type": "uint16",
   "access": "RW",
   "unit": "%"
  },
  {
   "name": "Heating circuit operating mode",
   "group": "Holding registers",
   "area": "holding",
   "address": 61,
   "type": "uint16",
   "access": "RW",
   "enum": "op_hc"
  },
  {
   "name": "Day target room temperature",
   "group": "Holding registers",
   "area": "holding",
   "address": 62,
   "type": "uint16",
   "access": "RW",
   "unit": "°C"
  },
  {
   "name": "Set-back temperature",
   "group": "Holding registers",
   "area": "holding",
   "address": 63,
   "type": "uint16",
   "access": "RW",
   "unit": "°C"
  },
  {
   "name": "Heating curve",
   "group": "Holding registers",
   "area": "holding",
   "address": 64,
   "type": "float32",
   "access": "RW"
  },
  {
   "name": "Maximum target flow temperature",
   "group": "Holding registers",
   "area": "holding",
   "address": 66,
   "type": "uint16",
   "access": "RW",
   "unit": "°C"
  },
  {
   "name": "Minimum target flow temperature",
   "group": "Holding registers",
   "area": "holding",
   "address": 67,
   "type": "uint16",
   "access": "RW",
   "unit": "°C"
  },
  {
   "name": "Outside temperature switch-off threshold",
   "group": "Holding registers",
   "area": "holding",
   "address": 68,
   "type": "uint16",
   "access": "RW",
   "unit": "°C"
  }
 ]
}