{
  "$schema": "https://raw.githubusercontent.com/nobrega8/mbmap-library/main/schema/mbmap-2.schema.json",
  "mbmap": 2,
  "vendor": "Socomec",
  "model": "Netys PR Netys RT Itys",
  "models": ["Netys PR", "Netys RT", "Itys"],
  "vendor_website": "socomec.com",
  "revision": 2,
  "source": "Modbus Database (Jibril Sharafi, MIT licence), table socomec/netys-pr-netys-rt-itys; https://www.aggsoft.com/serial-data-logger/tutorials/modbus-data-logging/socomec-netys-pr-netys-rt-itys.htm. Not verified against the manufacturer's documentation",
  "notes": [
    "Socomec Netys PR Netys RT Itys.",
    "Converted automatically from the Modbus Database (MIT licence, Jibril Sharafi).",
    "Not verified against the manufacturer's documentation. The byte order is a guess: the source does not give one.",
    "Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual."
  ],
  "byte_order": "big",
  "word_order": "big",
  "address_base": 0,
  "x_status": "unofficial",
  "x_origin": "modbus-database",
  "registers": [
    {"name": "Broadcast, load phase 1 (M00)", "area": "holding", "address": 96, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Broadcast, total load (M03)", "area": "holding", "address": 99, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Broadcast, battery capacity (M04)", "area": "holding", "address": 100, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Broadcast, auxiliary mains star voltage v1 (M06)", "area": "holding", "address": 102, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Broadcast, output star voltage v1 (M09)", "area": "holding", "address": 105, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Broadcast, output current phase l1 (M15)", "area": "holding", "address": 111, "type": "uint16", "unit": "A", "access": "R"},
    {"name": "Broadcast, auxiliary frequency (M18)", "area": "holding", "address": 114, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Broadcast, output frequency (M19)", "area": "holding", "address": 115, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Broadcast, positive battery voltage (M20)", "area": "holding", "address": 116, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Broadcast, internal UPS temperature (M22)", "area": "holding", "address": 118, "type": "uint16", "unit": "DC", "access": "R"},
    {"name": "Broadcast, remaining back up time (M23)", "area": "holding", "address": 119, "type": "uint16", "unit": "min", "access": "R"},
    {"name": "Broadcast, input mains star voltage v1 (M33)", "area": "holding", "address": 129, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Concentrator, load phase 1 (M00)", "area": "holding", "address": 4192, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Concentrator, total load (M03)", "area": "holding", "address": 4195, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Concentrator, battery capacity (M04)", "area": "holding", "address": 4196, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Concentrator, auxiliary mains star voltage v1 (M06)", "area": "holding", "address": 4198, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Concentrator, output star voltage v1 (M09)", "area": "holding", "address": 4201, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Concentrator, output current phase l1 (M15)", "area": "holding", "address": 4207, "type": "uint16", "unit": "A", "access": "R"},
    {"name": "Concentrator, auxiliary frequency (M18)", "area": "holding", "address": 4210, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Concentrator, output frequency (M19)", "area": "holding", "address": 4211, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Concentrator, positive battery voltage (M20)", "area": "holding", "address": 4212, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Concentrator, internal UPS temperature (M22)", "area": "holding", "address": 4214, "type": "uint16", "unit": "DC", "access": "R"},
    {"name": "Concentrator, remaining back up time (M23)", "area": "holding", "address": 4215, "type": "uint16", "unit": "min", "access": "R"},
    {"name": "Concentrator, input mains star voltage v1 (M33)", "area": "holding", "address": 4225, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 1, load phase 1 (M00)", "area": "holding", "address": 8288, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 1, total load (M03)", "area": "holding", "address": 8291, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 1, battery capacity (M04)", "area": "holding", "address": 8292, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 1, auxiliary mains star voltage v1 (M06)", "area": "holding", "address": 8294, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 1, output star voltage v1 (M09)", "area": "holding", "address": 8297, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 1, output current phase l1 (M15)", "area": "holding", "address": 8303, "type": "uint16", "unit": "A", "access": "R"},
    {"name": "Module 1, auxiliary frequency (M18)", "area": "holding", "address": 8306, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Module 1, output frequency (M19)", "area": "holding", "address": 8307, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Module 1, positive battery voltage (M20)", "area": "holding", "address": 8308, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 1, internal UPS temperature (M22)", "area": "holding", "address": 8310, "type": "uint16", "unit": "DC", "access": "R"},
    {"name": "Module 1, remaining back up time (M23)", "area": "holding", "address": 8311, "type": "uint16", "unit": "min", "access": "R"},
    {"name": "Module 1, input mains star voltage v1 (M33)", "area": "holding", "address": 8321, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 2, load phase 1 (M00)", "area": "holding", "address": 12384, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 2, total load (M03)", "area": "holding", "address": 12387, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 2, battery capacity (M04)", "area": "holding", "address": 12388, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 2, auxiliary mains star voltage v1 (M06)", "area": "holding", "address": 12390, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 2, output star voltage v1 (M09)", "area": "holding", "address": 12393, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 2, output current phase l1 (M15)", "area": "holding", "address": 12399, "type": "uint16", "unit": "A", "access": "R"},
    {"name": "Module 2, auxiliary frequency (M18)", "area": "holding", "address": 12402, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Module 2, output frequency (M19)", "area": "holding", "address": 12403, "type": "uint16", "unit": "Hz", "access": "R"},
    {"name": "Module 2, positive battery voltage (M20)", "area": "holding", "address": 12404, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 2, internal UPS temperature (M22)", "area": "holding", "address": 12406, "type": "uint16", "unit": "DC", "access": "R"},
    {"name": "Module 2, remaining back up time (M23)", "area": "holding", "address": 12407, "type": "uint16", "unit": "min", "access": "R"},
    {"name": "Module 2, input mains star voltage v1 (M33)", "area": "holding", "address": 12417, "type": "uint16", "unit": "V", "access": "R"},
    {"name": "Module 3, load phase 1 (M00)", "area": "holding", "address": 16480, "type": "uint16", "unit": "%", "access": "R"},
    {"name": "Module 3, total load (M03)", "area": "holding", "address": 16483, "type": "uint16", "unit": "%", "access": "R"}
  ]
}
