AEPH do Brasil ONIX Modbus register map

Weighing indicator: displayed weight with status (gross or net, stable, negative, overload), tare and remote tare, zero and print commands

  • Official
  • 12 registers
  • Modbus RTU
  • Revision 1 · 2026-11-08

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8N2 · 19200 baud, 8 data bits, none parity, 2 stop bits
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
12 holding registers
Groups
3
Translation tables
1
Revision
1 · 2026-11-08
Added
()
File
maps/aeph/onix.mbmap.json · 4 KB · history
SHA-256
4fea80a7a4fb767e8cb8d97f321c9bbe9ba89879d03466c6a56c305c1de15028
Manufacturer
aephdobrasil.com.br

Sources and notes

  • Manual ONIX · version 2.0, 2018-07-10
    chapter 20; linked in issue #148

Source: AEPH do Brasil ONIX manual, chapter 20 (Modbus RTU protocol)

  • Modbus RTU (slave); set PR = rtU on the indicator. FC03 reads and FC06 writes holding registers. Addresses are 0-based, as sent on the wire.
  • The manual asks for 19200 bit/s, 8 data bits, no parity, 2 stop bits. The address (END) is 1 to 99.
  • Weight and tare are 17-bit values split over two registers: the high byte of the first register holds the status (or the decimal places), its lowest bit is bit 16 of the value, and the second register holds bits 0-15. They are given here as separate registers because the format has no type for this layout.
  • The manual's register list gives the weight and tare registers as 0x0010 and 0x0012, but its example frames read them at 10 (0x000A) and 12 (0x000C); this map follows the frames.
  • The command values follow the manual's example frames (1 = tare, 2 = zero, 3 = clear tare, 4 = print); the text next to the frames disagrees in places.
  • Written from the manual; this map has not been tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 11 uint16 R Bits 0-15 of the displayed weight; bit 16 is in register 10. Weight = bit 16 x 65536 + this value, with the decimal point and sign given by the status
HR 10 bool bit 0 R
HR 10 uint16 bits 8–10 R
HR 10 bool bit 11 R
HR 10 bool bit 12 R
HR 10 bool bit 13 R
HR 10 bool bit 14 R
HR 10 bool bit 15 R
HR 13 uint16 R Bits 0-15 of the tare; bit 16 is in register 12
HR 12 bool bit 0 R
HR 12 uint16 bits 8–10 R
HR 2 uint16 W