LC Technology LC-Modbus-8R-D7 Modbus register map

8-CH Modbus RTU relay + optocoupler input module, RS485/5V TTL, 4800/9600/19200 baud. FC05/FC01: relay ch1-8 at coil addr 0-7 (0xFF00=on/0x0000=off). FC02: optocoupler input ch1-8 at discrete input addr 0-7. FC03 addr 0: device address R (1-255). FC03 addr 1000: baud rate status (2=4800,3=9600,4=19200). FC10 addr 1001: set baud rate. FC10 relay N flash mode: base addr=3+(N-1)*5, 2 regs (word1: 0x0004=flash-OFF, 0x0002=flash-ON; word2=delay×0.1s).

  • Unofficial
  • 19 registers
  • Revision 2

Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
19 holding registers
Revision
2
Added
()
File
maps/lc-technology/lc-modbus-8r-d7.mbmap.json · 5 KB · history
SHA-256
3eec75c839239b28c7f68512b15f68ea5e67329c0bdc7adbb35ad7dc3339fc64
Manufacturer
www.chinalctech.com

Sources and notes

Source: Omni Console device library (OmniCoreST), modbus-library/lctech-8ch-relay.toml; Source: lctech-modbus-rtu-relay-8ch-register-table.html (chinalctech.com product page). Not verified against the manufacturer's documentation

  • LC Technology LC-Modbus-8R-D7.
  • Converted automatically from the Omni Console device library (OmniCoreST).
  • Not verified against the manufacturer's documentation.
  • Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
  • | LC Technology LC-Modbus-8R-D7 8-Channel Modbus RTU Relay Module
  • |
  • | Source: lctech-modbus-rtu-relay-8ch-register-table.html (chinalctech.com product page)
  • | Protocol: Modbus RTU; RS485 or 5V TTL UART; 4800/9600/19200 baud, default 9600
  • | Device address: 1-255, default 255 (0xFF); address 0x00 = broadcast
  • |
  • | FC05 (Write Single Coil): relay 1-8 at coil addresses 0x0000-0x0007 (0xFF00=ON, 0x0000=OFF)
  • | FC0F (Write Multiple Coils): addr 0x0000, count 8; data byte bit0-7 = relay 1-8
  • | FC01 (Read Coils): addr 0x0000, count 8; returns relay 1-8 state (bit0=relay1)
  • | FC02 (Read Discrete Inputs): addr 0x0000, count 8; optocoupler 1-8 state (bit0=ch1)
  • | FC03 (Read Holding Registers): device address (addr 0), baud rate status (addr 1000)
  • | FC10 (Write Multiple Registers): device address (addr 0), baud rate (addr 1001),
  • | relay flash/delay mode (addr 3/8/13/18/23/28/33/38, 2 regs each)
  • |
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 R
HR 3 uint16 R
HR 4 uint16 R
HR 8 uint16 R
HR 9 uint16 R
HR 13 uint16 R
HR 14 uint16 R
HR 18 uint16 R
HR 19 uint16 R
HR 23 uint16 R
HR 24 uint16 R
HR 28 uint16 R
HR 29 uint16 R
HR 33 uint16 R
HR 34 uint16 R
HR 38 uint16 R
HR 39 uint16 R
HR 1000 uint16 R
HR 1001 uint16 R

Help improve this map