LC Technology

1 device map · 19 registers · www.chinalctech.com

  • Verified 0
  • Official 0
  • Unofficial 1

Devices

ModelDescriptionStatusProtocolRegisters
LC-Modbus-8R-D78-CH Modbus RTU relay + optocoupler input module, RS485/5V TTL, 4800/9600/19200 baud. FC05/FC01: relay ch1-8 at coil addr 0-7 (0xFF00=on/0x0000=off). FC02: optocoupler input ch1-8 at discrete input addr 0-7. FC03 addr 0: device address R (1-255). FC03 addr 1000: baud rate status (2=4800,3=9600,4=19200). FC10 addr 1001: set baud rate. FC10 relay N flash mode: base addr=3+(N-1)*5, 2 regs (word1: 0x0004=flash-OFF, 0x0002=flash-ON; word2=delay×0.1s).Unofficial19