WEG CFW11 Modbus register map

Frequency inverter with Modbus RTU through the RS485-01 or RS232-01 accessory: monitoring, fault history, ramps and references, command sources, serial interface, motor data and serial control

  • Official
  • 175 registers
  • Modbus RTU
  • Revision 1 · 2026-10-29
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N2 · 9600 baud, 8 data bits, none parity, 2 stop bits
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
29 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
175 holding registers
Groups
11
Translation tables
11
Revision
1 · 2026-10-29
Added
()
File
maps/weg/cfw11.mbmap.json · 41 KB · history
SHA-256
e8344952b97ac54a7c09f937748f087f40114854a5386daf00592b5c2c95a3ff
Manufacturer
weg.net

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Software version holding 23 uint16

Sources and notes

Source: WEG CFW-11 programming manual V2.0X (0899.5664/04) and CFW-11 serial communication manual (0899.5741)

  • Modbus RTU needs an RS485-01 or RS232-01 accessory (or CAN/RS485-01) and P0312 = 2 (Modbus RTU, default).
  • Every parameter Pxxxx is the holding register of the same number (P0003 is register 3); the Modicon address is 40001 + the number.
  • Values travel as integers: a parameter shown as 3.5 A is sent as 35. Scales in this map follow the decimal places of the programming manual.
  • Functions 03, 06, 16 and 43 (device identification). A telegram cannot exceed 64 bytes, so a read returns at most 29 registers.
  • Serial defaults: address 1 (P0308), 9600 bit/s (P0310 = 0). The programming manual V2.0X gives P0311 = 3 (8 data bits, no parity, 2 stop bits) as the default; the serial communication manual gives P0311 = 0 (8N1). Check P0311 on the drive.
  • To control the drive over Modbus, set the command and reference sources to Serial/USB (P0105, P0220 to P0228). P0682 (control word) and P0683 (speed reference, 8192 = synchronous speed) can be written only through the serial interface or USB.
  • Parameters marked 'can be changed only with the motor stopped' are the manual's CFG parameters; the drive refuses a write while the motor runs.
  • Only the parameters used to monitor and run the drive are listed; every other parameter is the register of its number, with the range given in the programming manual. The fault history dates and times (P0051 to P0089, except the fault numbers) are left out because the manual does not give their encoding.
  • Written from the manufacturer's manuals; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 RW P0000
HR 1 uint16 R rpm P0001
HR 2 uint16 R rpm P0002
HR 3 uint16 R A ×0.1 P0003
HR 4 uint16 R V P0004
HR 5 uint16 R Hz ×0.1 P0005
HR 6 uint16 R P0006
HR 7 uint16 R V P0007
HR 9 int16 R % ×0.1 P0009
HR 10 uint16 R kW ×0.1 P0010
HR 12 bool bit 0 R P0012
HR 12 bool bit 1 R P0012
HR 12 bool bit 2 R P0012
HR 12 bool bit 3 R P0012
HR 12 bool bit 4 R P0012
HR 12 bool bit 5 R P0012
HR 12 bool bit 6 R P0012
HR 12 bool bit 7 R P0012
HR 13 bool bit 0 R P0013
HR 13 bool bit 1 R P0013
HR 13 bool bit 2 R P0013
HR 13 bool bit 3 R P0013
HR 13 bool bit 4 R P0013
HR 14 uint16 R % ×0.01 P0014
HR 15 uint16 R % ×0.01 P0015
HR 16 int16 R % ×0.01 P0016
HR 17 int16 R % ×0.01 P0017
HR 18 int16 R % ×0.01 P0018
HR 19 int16 R % ×0.01 P0019
HR 20 int16 R % ×0.01 P0020
HR 21 int16 R % ×0.01 P0021
HR 23 uint16 R ×0.01 P0023
HR 25 bool bit 0 R IOC-01/IOC-02 module (bit 0 of P0025)
HR 25 bool bit 1 R IOC-01/IOC-02 module (bit 1 of P0025)
HR 25 bool bit 2 R IOC-01/IOC-02 module (bit 2 of P0025)
HR 25 bool bit 3 R IOC-01/IOC-02 module (bit 3 of P0025)
HR 25 bool bit 4 R IOC-01/IOC-02 module (bit 4 of P0025)
HR 25 bool bit 5 R IOC-01/IOC-02 module (bit 5 of P0025)
HR 25 bool bit 6 R IOC-01/IOC-02 module (bit 6 of P0025)
HR 25 bool bit 7 R IOC-01/IOC-02 module (bit 7 of P0025)
HR 26 bool bit 0 R IOC-01/IOC-02 module (bit 0 of P0026)
HR 26 bool bit 1 R IOC-01/IOC-02 module (bit 1 of P0026)
HR 26 bool bit 2 R IOC-01/IOC-02 module (bit 2 of P0026)
HR 26 bool bit 3 R IOC-01/IOC-02 module (bit 3 of P0026)
HR 26 bool bit 4 R IOC-01/IOC-02 module (bit 4 of P0026)
HR 26 bool bit 5 R IOC-01/IOC-02 module (bit 5 of P0026)
HR 26 bool bit 6 R IOC-01/IOC-02 module (bit 6 of P0026)
HR 26 bool bit 7 R IOC-01/IOC-02 module (bit 7 of P0026)
HR 27 uint16 R P0027; accessory identification code (hex)
HR 28 uint16 R P0028; accessory identification code (hex)
HR 29 uint16 R P0029; bits 0-5 rated current, 6-7 rated voltage, 8 EMC filter, 9 safety relay, 10-11 supply type, 12 braking IGBT
HR 30 int16 R °C ×0.1 P0030
HR 31 int16 R °C ×0.1 P0031
HR 32 int16 R °C ×0.1 P0032
HR 33 int16 R °C ×0.1 P0033
HR 34 int16 R °C ×0.1 P0034
HR 36 uint16 R rpm P0036
HR 37 uint16 R % P0037
HR 38 uint16 R rpm P0038
HR 39 uint16 R P0039
HR 40 uint16 R % ×0.1 P0040
HR 41 uint16 R % ×0.1 P0041
HR 42 uint16 R h P0042
HR 43 uint16 R h ×0.1 P0043
HR 44 uint16 R kWh P0044
HR 45 uint16 R h P0045
HR 48 uint16 R P0048; alarm number (Axxx)
HR 49 uint16 R P0049; fault number (Fxxx)
HR 50 uint16 R P0050; fault number (Fxxx)
HR 54 uint16 R P0054; fault number (Fxxx)
HR 58 uint16 R P0058; fault number (Fxxx)
HR 62 uint16 R P0062; fault number (Fxxx)
HR 66 uint16 R P0066; fault number (Fxxx)
HR 70 uint16 R P0070; fault number (Fxxx)
HR 74 uint16 R P0074; fault number (Fxxx)
HR 78 uint16 R P0078; fault number (Fxxx)
HR 82 uint16 R P0082; fault number (Fxxx)
HR 86 uint16 R P0086; fault number (Fxxx)
HR 90 uint16 R A ×0.1 P0090
HR 91 uint16 R V P0091
HR 92 uint16 R rpm P0092
HR 93 uint16 R rpm P0093
HR 94 uint16 R Hz ×0.1 P0094
HR 95 uint16 R V P0095
HR 96 uint16 R P0096; bit 0 = DI1 ... bit 7 = DI8
HR 97 uint16 R P0097; bit 0 = DO1 ... bit 4 = DO5
HR 100 uint16 RW s ×0.1 P0100
HR 101 uint16 RW s ×0.1 P0101
HR 102 uint16 RW s ×0.1 P0102
HR 103 uint16 RW s ×0.1 P0103
HR 104 uint16 RW P0104
HR 105 uint16 RW P0105; can be changed only with the motor stopped
HR 120 uint16 RW P0120
HR 121 uint16 RW rpm P0121
HR 122 uint16 RW rpm P0122
HR 123 uint16 RW rpm P0123; PM and vector control
HR 124 uint16 RW rpm P0124
HR 125 uint16 RW rpm P0125
HR 126 uint16 RW rpm P0126
HR 127 uint16 RW rpm P0127