WEG CFW500 Modbus register map

Compact frequency inverter with Modbus RTU: monitoring, ramps and references, regulation, configuration, I/O, protections, motor, PID, SoftPLC and network control parameters

  • Official
  • 367 registers
  • Modbus RTU
  • Revision 3 · 2026-10-20
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
367 holding registers
Groups
17
Translation tables
34
Revision
3 · 2026-10-20
Added
()
File
maps/weg/cfw500.mbmap.json · 81 KB · history
SHA-256
8f31ce9f3a5884ad1b20aaabebe401db91f657a8245485070b0224ea8f3d6e34
Manufacturer
weg.net

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Main software version holding 23 uint16

Sources and notes

Source: WEG CFW500 programming manual V2.2X and Modbus RTU manual

  • Every parameter Pxxxx is the holding register of the same number (P0003 is register 3); the Modicon address is 40001 + the number.
  • Values travel as integers: a parameter shown as 1.5 A is sent as 15. Scales in this map follow the decimal places of the programming manual.
  • Read from the programming manual V2.2X: 327 parameters with documented ranges. Parameters of the CAN, Ethernet and other network modules (P0700 and up, except P0680 to P0698) are not included; they are described in the module manuals.
  • P0001 and P0002 use the scale and unit chosen in P0208 to P0210, so they are shown raw.
  • P0682 and P0683 are written only through the serial interface, and the drive must be set to use serial as command and reference source (P0105 and P0220 to P0228).
  • P0312 = 2 selects Modbus RTU on the standard RS485 interface (default); a remote HMI uses the same port with P0312 = 0.
  • Parity and stop bits: P0311, default 1 = 8 data bits, even parity, 1 stop bit.
  • Parameters marked 'can be changed only with the motor stopped' are the manual's cfg parameters; the drive refuses a write while the motor runs.
  • A drive answers with an exception when a block of registers contains a parameter its firmware does not have, and the whole block fails. Parameters differ between firmware versions (V2.2X here); if a block fails, switch off the registers that the drive does not have (in Modbench: right-click, stop reading it).
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 RW P0000
HR 1 uint16 R P0001; scale set by P0208 to P0210
HR 2 uint16 R P0002; scale set by P0208 to P0210
HR 3 uint16 R A ×0.1 P0003
HR 4 uint16 R V P0004
HR 5 uint16 R Hz ×0.1 P0005
HR 6 uint16 R P0006
HR 7 uint16 R V P0007
HR 9 int16 R % ×0.1 P0009
HR 10 uint16 R kW ×0.1 P0010
HR 11 int16 R ×0.01 P0011
HR 12 bool bit 0 R P0012
HR 12 bool bit 1 R P0012
HR 12 bool bit 2 R P0012
HR 12 bool bit 3 R P0012
HR 12 bool bit 4 R P0012
HR 12 bool bit 5 R P0012
HR 12 bool bit 6 R P0012
HR 12 bool bit 7 R P0012
HR 13 bool bit 0 R P0013
HR 13 bool bit 1 R P0013
HR 13 bool bit 2 R P0013
HR 13 bool bit 3 R P0013
HR 13 bool bit 4 R P0013
HR 14 uint16 R % ×0.1 P0014
HR 15 uint16 R % ×0.1 P0015
HR 16 uint16 R % ×0.1 P0016
HR 17 uint16 R Hz P0017
HR 18 int16 R % ×0.1 P0018
HR 19 int16 R % ×0.1 P0019
HR 20 int16 R % ×0.1 P0020
HR 21 int16 R % ×0.1 P0021
HR 22 uint16 R Hz P0022
HR 23 uint16 R ×0.01 P0023
HR 24 uint16 R ×0.01 P0024
HR 27 uint16 R P0027
HR 30 int16 R °C P0030
HR 37 uint16 R % P0037
HR 38 uint16 R rpm P0038
HR 39 uint16 R P0039
HR 40 uint16 R ×0.1 P0040
HR 41 uint16 R ×0.1 P0041
HR 47 uint16 R P0047
HR 48 uint16 R P0048; alarm number
HR 49 uint16 R P0049; fault number
HR 50 uint16 R P0050
HR 51 uint16 R A ×0.1 P0051
HR 52 uint16 R V P0052
HR 53 uint16 R Hz ×0.1 P0053
HR 54 int16 R °C P0054
HR 55 uint16 R P0055; bit field, see the manual
HR 60 uint16 R P0060
HR 61 uint16 R A ×0.1 P0061
HR 62 uint16 R V P0062
HR 63 uint16 R Hz ×0.1 P0063
HR 64 int16 R °C P0064
HR 65 uint16 R P0065; bit field, see the manual
HR 70 uint16 R P0070
HR 71 uint16 R A ×0.1 P0071
HR 72 uint16 R V P0072
HR 73 uint16 R Hz ×0.1 P0073
HR 74 int16 R °C P0074
HR 75 uint16 R P0075; bit field, see the manual
HR 100 uint16 RW s ×0.1 P0100
HR 101 uint16 RW s ×0.1 P0101
HR 102 uint16 RW s ×0.1 P0102
HR 103 uint16 RW s ×0.1 P0103
HR 104 uint16 RW P0104; can be changed only with the motor stopped
HR 105 uint16 RW P0105
HR 106 uint16 RW s ×0.1 P0106
HR 120 uint16 RW P0120
HR 121 uint16 RW Hz ×0.1 P0121
HR 124 int16 RW Hz ×0.1 P0124
HR 125 int16 RW Hz ×0.1 P0125
HR 126 int16 RW Hz ×0.1 P0126
HR 127 int16 RW Hz ×0.1 P0127
HR 128 int16 RW Hz ×0.1 P0128
HR 129 int16 RW Hz ×0.1 P0129
HR 130 int16 RW Hz ×0.1 P0130
HR 131 int16 RW Hz ×0.1 P0131
HR 132 uint16 RW % P0132; can be changed only with the motor stopped
HR 133 uint16 RW Hz ×0.1 P0133
HR 134 uint16 RW Hz ×0.1 P0134
HR 135 uint16 RW A ×0.1 P0135
HR 136 uint16 RW % ×0.1 P0136
HR 137 uint16 RW % ×0.1 P0137
HR 138 int16 RW % ×0.1 P0138
HR 139 uint16 RW ms P0139
HR 140 uint16 RW ms P0140
HR 142 uint16 RW % ×0.1 P0142; can be changed only with the motor stopped
HR 143 uint16 RW % ×0.1 P0143; can be changed only with the motor stopped
HR 144 uint16 RW % ×0.1 P0144; can be changed only with the motor stopped
HR 145 uint16 RW Hz ×0.1 P0145; can be changed only with the motor stopped
HR 146 uint16 RW Hz ×0.1 P0146; can be changed only with the motor stopped
HR 147 uint16 RW Hz ×0.1 P0147; can be changed only with the motor stopped
HR 150 uint16 RW P0150; can be changed only with the motor stopped; see the manual for the values
HR 151 uint16 RW V P0151
HR 152 uint16 RW ×0.01 P0152
HR 153 uint16 RW V P0153
HR 156 uint16 RW A ×0.1 P0156