Electron do Brasil GRIDSCAN 6000 Modbus register map
Multi-sensor transformer monitor for dissolved hydrogen, moisture, pressure and temperature with Modbus RTU
- Official
- 74 registers
- Modbus RTU
- Revision 1 · 2026-11-10
- Identity: serial number
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1
- Serial
- 19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 64 holding registers, 10 input registers
- Groups
- 8
- Translation tables
- 8
- Revision
- 1 · 2026-11-10
- Added
- ()
- File
- maps/electron/gdscan-6000.mbmap.json · 17 KB · history
- SHA-256
- 908217ff6223ac70d6a0fe7cc891533b43fd22c11a937b9a820b2f0e4d969eeb
- Manufacturer
- electron.com.br
Device identity
What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.
| Role | Register | Address | Type | Values |
|---|---|---|---|---|
| Serial number | Product serial number | holding 41 | string[10] |
Sources and notes
- Mapa de Registradores MODBUS, GRIDSCAN 6000 · version 1.0 linked in issue #132
Source: Electron do Brasil, Mapa de Registradores MODBUS, GRIDSCAN 6000, v1.0
- Addresses are the register numbers of the document, which starts at 0 (hydrogen at registers 0 and 1), so address_base is 0. The document lists them as holding registers (function 03).
- Default connection from the document: 19200 baud, 8 data bits, no parity, 1 stop bit (the framing register also allows 2 stop bits, even and odd parity), RS-485 two-wire, unit ID 1. Set the master timeout to 10 seconds or more.
- 32-bit values (hydrogen, rates, calibration values) are read with the high word first. The document asks to read the high word before the low word: read both registers in one request.
- Strings are ASCII, two characters per register, up to 19 characters, null-terminated. Dates are packed as month and day in one register (high and low byte) and the year in the next.
- The issue asked for the GRIDSCAN 6200. The linked document is the Modbus map of the GRIDSCAN 6000 and does not mention the 6200, so this file is named after the 6000.
- The document also describes discrete inputs (function 02, addresses 0 to 74) that repeat the status bits and mark which values are valid; they are not mapped here.
- The input registers (function 04) are taken from the table at the end of the document, which lists 32-bit and floating-point values. The rate-of-change input registers are not mapped because the document does not say how they are encoded there.
- Written from the manufacturer's document; not tested on a device.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 0 | uint32 ABCD | R | ppm | Dissolved hydrogen in ppm H2, unscaled. Read the high word (register 0) first; the value is 0 until the ready bit of the unit status is set | ||
| HR | 7 | uint16 | R | °C | ×0.01 −100 | Internal temperature of the electronics; above 105 °C can damage the device | |
| HR | 8 | uint16 | R | °C | ×0.01 −100 | 0 until the first measurement; the sensor is calibrated up to 105 °C | |
| HR | 13 | uint32 ABCD | R | ppm/day | −20000000 | Raw value is stored with an offset of 20,000,000; negative means falling hydrogen. Trends reset to zero after a power cycle | |
| HR | 15 | uint32 ABCD | R | ppm/week | −20000000 | Raw value is stored with an offset of 20,000,000; negative means falling hydrogen. Trends reset to zero after a power cycle | |
| HR | 17 | uint32 ABCD | R | ppm/month | −20000000 | Raw value is stored with an offset of 20,000,000; negative means falling hydrogen. Trends reset to zero after a power cycle | |
| HR | 22 | uint16 | R | %RH | ×0.1 | ||
| HR | 23 | uint16 | R | atm | ×0.001 | ||
| HR | 24 | uint16 | R | ppm | |||
| HR | 25 | uint16 | R | ×0.01 | Gauge pressure in the unit chosen in register 153; the document lists it as PSI | ||
| HR | 31 | string[10] | R | ||||
| HR | 41 | string[10] | R | ||||
| HR | 51 | string[10] | R | ||||
| HR | 61 | string[10] | R | ||||
| HR | 81 | uint16 bits 8–15 | R | ||||
| HR | 81 | uint16 bits 0–7 | R | ||||
| HR | 82 | uint16 | R | ||||
| HR | 83 | uint16 bits 8–15 | R | ||||
| HR | 83 | uint16 bits 0–7 | R | ||||
| HR | 84 | uint16 | R | ||||
| HR | 87 | uint16 bits 8–15 | R | ||||
| HR | 87 | uint16 bits 0–7 | R | ||||
| HR | 88 | uint16 | R | ||||
| HR | 89 | string[10] | R | Text in the form x:y:z (major, minor, product designator), for example 3:7:A | |||
| HR | 111 | bool bit 15 | R | Hydrogen readings are valid | |||
| HR | 111 | bool bit 14 | R | Cleared by reading the register | |||
| HR | 111 | bool bit 12 | R | An unrecoverable error occurred; see registers 112 and 113 | |||
| HR | 111 | uint16 bits 3–5 | R | ||||
| HR | 112 | bool bit 15 | R | ||||
| HR | 112 | bool bit 14 | R | ||||
| HR | 112 | bool bit 13 | R | ||||
| HR | 113 | bool bit 8 | R | Cleared by setting the clock or cycling the power | |||
| HR | 113 | bool bit 4 | R | ||||
| HR | 113 | bool bit 1 | R | ||||
| HR | 113 | bool bit 0 | R | ||||
| HR | 121 | uint16 | RW | First step of the DGA adjustment: write when an oil sample is taken. Not within 24 hours of installation or of the last DC command. The document gives no value to write | |||
| HR | 122 | uint16 | RW | Second step: write after registers 126 to 129 are set. Needs a prior DA and takes up to 10 seconds to answer. The document gives no value to write | |||
| HR | 125 | uint16 | RW | Clears the DGA adjustment. The document gives no value to write | |||
| HR | 126 | uint32 ABCD | RW | ppm | Laboratory hydrogen result, written before command DB | ||
| HR | 128 | uint16 bits 8–15 | RW | The date must match the internal clock for command DB to be accepted | |||
| HR | 128 | uint16 bits 0–7 | RW | ||||
| HR | 129 | uint16 | RW | ||||
| HR | 136 | string[8] | RW | Up to 15 characters, null-terminated | |||
| HR | 144 | uint32 ABCD | RW | ×0.000001 −0.001 | Stored as m x 1,000,000 + 1,000 (default 1093 for synthetic ester). A wrong value disables hydrogen measurement | ||
| HR | 146 | uint32 ABCD | RW | ×0.000001 −0.001 | Stored as b x 1,000,000 + 1,000 (default 40739 for synthetic ester). A wrong value disables hydrogen measurement | ||
| HR | 148 | uint16 | RW | Write 1 to open the user-defined type for editing, then 2 to save or 3 to abort | |||
| HR | 150 | uint16 | RW | Writing to unit 0 reaches every connected device. The new ID applies without a power cycle | |||
| HR | 151 | uint16 | RW | Laboratory mode runs the self-calibration every 4 hours instead of every 12 | |||
| HR | 152 | uint16 | RW | ||||
| HR | 153 | uint16 | RW | ||||
| HR | 158 | uint16 | RW | 0 disables, any other value enables | |||
| HR | 159 | uint16 | RW | Applies when the baud rate register is written | |||
| HR | 160 | uint16 | RW | ||||
| HR | 164 | uint16 | RW | ×0.01 −100 | Stored as (offset + 100) x 100, in the selected pressure unit | ||
| HR | 175 | uint16 bits 8–15 | RW | Read register 175 first; write 175 to 178 in order, the clock is saved when 178 is written | |||
| HR | 175 | uint16 bits 0–7 | RW | +2000 | Year minus 2000 in the register | ||
| HR | 176 | uint16 bits 8–15 | RW | ||||
| HR | 176 | uint16 bits 0–7 | RW | ||||
| HR | 177 | uint16 bits 8–15 | RW | ||||
| HR | 177 | uint16 bits 0–7 | RW | ||||
| HR | 178 | uint16 | RW | Write 0 | |||
| HR | 201 | string[10] | RW | Up to 19 characters; read from the lowest address, write all registers to save | |||
| HR | 211 | string[10] | RW | ||||
| HR | 221 | string[10] | RW | ||||
| IR | 0 | uint16 | R | Same bit layout as holding register 111 | |||
| IR | 1 | uint32 ABCD | R | Same bit layout as holding registers 112 and 113 | |||
| IR | 3 | uint32 ABCD | R | ppm | |||
| IR | 11 | float32 ABCD | R | °C | Floating point; the unit is not stated in the document and degrees Celsius is assumed | ||
| IR | 13 | float32 ABCD | R | °C | Floating point; the unit is not stated in the document and degrees Celsius is assumed | ||
| IR | 17 | float32 ABCD | R | %RH | Floating point; the unit is assumed from the holding register | ||
| IR | 19 | float32 ABCD | R | Floating point, in the selected pressure unit | |||
| IR | 21 | float32 ABCD | R | ppm | Floating point; the unit is assumed from the holding register | ||
| IR | 45 | uint16 | R | ||||
| IR | 46 | float32 ABCD | R |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).