MBMap Registry
  1. Devices
  2. Kael
  3. VARkombi 12 PC

Kael VARkombi 12 PC Modbus register map

Also covers VARkombi-12-PC

Kael VARkombi-12-PC three-phase reactive power controller with RS-485 (Modbus RTU)

  • Official
  • 185 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
185 holding registers
Groups
6
Revision
2 · 2026-10-17
Added
()
File
maps/kael/varkombi-12-pc.mbmap.json · 37 KB · history
SHA-256
d73677a22026d49a1e036a1363ee01f1701739c925efea9485570720ca817740
Manufacturer
kael.com.tr

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Program version holding 5 uint16

Sources and notes

Source: Kael Elektronik, "VARkombi-12-PC" user manual (Turkish), register table on pages 15-20, program version 0x0300

  • All registers are 16-bit holding registers. The manual gives 9600 baud, no parity and addresses 1-255.
  • ATRF is the current transformer ratio (register 0x1000, e.g. 20 for 100/5 A). Per-phase currents and powers must be multiplied by ATRF as noted in each description; the scale is the table's multiplier.
  • Energies are 48-bit counters in watt-seconds or var-seconds, split over three registers (bits 47-32, 31-16 and 15-0).
  • Command registers take 0x55AA.
  • Names and descriptions are translated from the Turkish manual.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 R 869
HR 1 uint16 R 7436
HR 2 uint32 ABCD R 88100 (0x00015824)
HR 4 uint16 R
HR 5 uint16 R 0x0300
HR 6 uint32 ABCD RW
HR 4096 uint16 RW For 100/5 A write 20
HR 4097 uint16 R Bits 0-2: L1-L3 reactive power is capacitive (1) or inductive (0); bit 3: total reactive power capacitive; bit 4: mode 1 (capacitors not all learned yet); bit 5: mode 2 (fully automatic); bit 6: manual mode
HR 4098 uint16 R V ×0.1
HR 4099 uint16 R V ×0.1
HR 4100 uint16 R V ×0.1
HR 4101 uint16 R A ×0.001 Multiply by ATRF
HR 4102 uint16 R A ×0.001 Multiply by ATRF
HR 4103 uint16 R A ×0.001 Multiply by ATRF
HR 4104 uint16 R W Multiply by ATRF
HR 4105 uint16 R W Multiply by ATRF
HR 4106 uint16 R W Multiply by ATRF
HR 4107 uint16 R var Multiply by ATRF
HR 4108 uint16 R var Multiply by ATRF
HR 4109 uint16 R var Multiply by ATRF
HR 4110 uint16 R VA Multiply by ATRF
HR 4111 uint16 R VA Multiply by ATRF
HR 4112 uint16 R VA Multiply by ATRF
HR 4113 int16 R ×0.01
HR 4114 int16 R ×0.01
HR 4115 int16 R ×0.01
HR 4116 int16 R ×0.01
HR 4117 int16 R % ×0.01
HR 4118 int16 R % ×0.01
HR 4119 int16 R % ×0.01
HR 4120 int16 R % ×0.01
HR 4121 uint16 R W P1 + P2 + P3
HR 4122 uint16 R var Sum of the inductive phases
HR 4123 uint16 R var Sum of the capacitive phases
HR 4124 int16 R var
HR 4125 uint16 R VA
HR 4126 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4127 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4128 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4129 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4130 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4131 uint16 R % ×0.01 Ratio of the accumulated energies
HR 4132 uint16 R % ×0.01
HR 4133 uint16 R % ×0.01
HR 4134 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4135 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4136 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4137 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4138 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4139 uint16 R % ×0.01 Dynamic limit for single-phase capacitors
HR 4140 uint16 R % ×0.01 Dynamic limit for three-phase capacitors
HR 4141 uint16 R % ×0.01 Dynamic limit for three-phase capacitors
HR 4142 uint16 R 1 = alarm active: bit 0 AL01 overvoltage, bit 1 AL02 undervoltage, bit 2 AL03 overcurrent, bit 3 AL04 overcompensation, bit 4 AL05 undercompensation, bit 5 AL06 system error, bit 6 AL08 phase missing, bit 7 AL09 overtemperature
HR 4143 uint16 R Hz ×0.1
HR 4144 uint16 R °C
HR 4145 uint16 R Bits 0-2: CT of L1-L3 reversed; bits 3-5: CT direction of L1-L3 learned
HR 4146 uint16 R Bits 0-11: steps 1-12 switched on; bit 14: alarm relay on; bit 15: fan relay on
HR 4147 uint16 R Bits 0-11: power of steps 1-12 learned; bit 15: all steps learned
HR 4148 uint16 R s For single-phase capacitors on this phase
HR 4149 uint16 R s For single-phase capacitors on this phase
HR 4150 uint16 R s For single-phase capacitors on this phase
HR 4151 uint16 R s For single-phase capacitors on this phase
HR 4152 uint16 R s For single-phase capacitors on this phase
HR 4153 uint16 R s For single-phase capacitors on this phase
HR 4154 uint16 R s
HR 4155 uint16 R s
HR 8192 uint32 ABCD R s Used to check that energy accumulated without gaps
HR 8194 uint16 R Part of a 48-bit counter in watt-seconds
HR 8195 uint16 R Part of a 48-bit counter in watt-seconds
HR 8196 uint16 R Part of a 48-bit counter in watt-seconds
HR 8197 uint16 R Part of a 48-bit counter in var-seconds
HR 8198 uint16 R Part of a 48-bit counter in var-seconds
HR 8199 uint16 R Part of a 48-bit counter in var-seconds
HR 8200 uint16 R Part of a 48-bit counter in var-seconds
HR 8201 uint16 R Part of a 48-bit counter in var-seconds
HR 8202 uint16 R Part of a 48-bit counter in var-seconds
HR 8203 uint16 R Part of a 48-bit counter in watt-seconds
HR 8204 uint16 R Part of a 48-bit counter in watt-seconds
HR 8205 uint16 R Part of a 48-bit counter in watt-seconds
HR 8206 uint16 R Part of a 48-bit counter in watt-seconds
HR 8207 uint16 R Part of a 48-bit counter in watt-seconds
HR 8208 uint16 R Part of a 48-bit counter in watt-seconds
HR 8209 uint16 R Part of a 48-bit counter in watt-seconds
HR 8210 uint16 R Part of a 48-bit counter in watt-seconds
HR 8211 uint16 R Part of a 48-bit counter in watt-seconds
HR 8212 uint16 R Part of a 48-bit counter in var-seconds
HR 8213 uint16 R Part of a 48-bit counter in var-seconds
HR 8214 uint16 R Part of a 48-bit counter in var-seconds
HR 8215 uint16 R Part of a 48-bit counter in var-seconds
HR 8216 uint16 R Part of a 48-bit counter in var-seconds
HR 8217 uint16 R Part of a 48-bit counter in var-seconds
HR 8218 uint16 R Part of a 48-bit counter in var-seconds
HR 8219 uint16 R Part of a 48-bit counter in var-seconds
HR 8220 uint16 R Part of a 48-bit counter in var-seconds
HR 8221 uint16 R Part of a 48-bit counter in var-seconds
HR 8222 uint16 R Part of a 48-bit counter in var-seconds
HR 8223 uint16 R Part of a 48-bit counter in var-seconds
HR 8224 uint16 R Part of a 48-bit counter in var-seconds
HR 8225 uint16 R Part of a 48-bit counter in var-seconds
HR 8226 uint16 R Part of a 48-bit counter in var-seconds

Help improve this map