Lovato Electric DCRG8 Modbus register map

Digital power factor controller (DCRG8 series). Values marked single/three phase depend on how the controller is wired and programmed

  • Verified
  • 548 registers
  • Modbus TCP and RTU
  • Revision 4 · 2026-10-29

Verified: Tested on a real device.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
1001
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1
Max read
80 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
548 holding registers
Groups
13
Translation tables
3
Revision
4 · 2026-10-29
Added
()
File
maps/lovato-electric/dcrg8.mbmap.json · 86 KB · history
SHA-256
b69346fd4814db96199acdfdf573c18673774944171c63b88714c7e40d38a2d8
Manufacturer
lovatoelectric.com

Sources and notes

Source: Lovato Electric, "DCRG8 Series Modbus Communication Protocol", doc. I432IGB05_20 (2020-05-20), tables 2-9; from firmware revision 4

  • Lovato Electric DCRG8 digital power factor controller.
  • Addresses are as in the protocol tables; the wire address is one less.
  • FC06 and FC16 work only on addresses above 1000H.
  • Tested on a DCRG8, October 2026, over an RS-485 to RTU-over-TCP gateway (firmware not recorded).
  • A second DCRG8 was read in November 2026 over RS-485 at 9600 baud, 8N1, with the controller under load (about 387 A, 416 V line to line, single current input): 538 of 541 registers read. Checked: both measure sets (the single-phase set and the per-phase set read as zero for the unused phases, as table 2 says), power, energies, the average weekly power factor, temperatures, the counters, the limits, inputs and outputs, the alarm word with its bits (the step failure bit was set and matched the outputs), the event pointer, the clock, the harmonics and the step data. The three parameter value registers at 5004H were refused, as expected before a menu and parameter are selected. FC17 answered with the build date and time of the firmware (Feb 15 2018, 09:31:31) after 8 bytes the protocol document does not describe, and FC43 was refused (illegal function), so the map has no identify block.
  • Total cos phi (0000H, signed long, value/1000) is not in this map: its wire address is FFFFH, which a map cannot hold. Read it with FC04 from address 65535, 2 registers. A read of wire address 0 alone is refused (illegal data address).
  • Table 2: with one voltage and one current wired, the controller returns the first measure (0000H-0010H); with three voltages and three currents, the second (0040H-0062H, 1500H-150EH). The other one reads ND.
  • Writing a parameter, as in the manual's example (P02.01 CT primary = 200): FC06 value 2 at 5000H (menu), FC06 value 1 at 5002H (parameter), FC16 value 200 at 5004H, FC06 value 1 at 2F03H (save EEPROM), then FC06 value 4 at 2F03H (reboot). The controller does not answer the last two. To read a parameter, select the menu and parameter the same way, then read 5004H with FC04.
  • Cos phi setpoint (3004H) is not in the protocol document. It comes from Node-RED flows that have run for years on several DCRG8 controllers (FC04 read, FC06 write, value x 100, read back after the write). Which setpoint it changes and whether the change survives a power cycle without an EEPROM save (2F03H = 1) are not known. The documented way is the parameter access above with P02.13 (Setpoint cosphi 1, 0.50 IND to 0.50 CAP, instruction manual I340GB06_24).
AreaAddressNameTypeAccessUnitScaleDescription
HR 2 int32 ABCD R ×0.001
HR 4 int32 ABCD R ×0.001
HR 6 int32 ABCD R V ×0.1
HR 8 int32 ABCD R A ×0.001
HR 10 int32 ABCD R var
HR 12 int32 ABCD R var Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 14 int32 ABCD R var Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 16 int32 ABCD R var Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 18 int32 ABCD R var
HR 22 uint32 ABCD R kWh ×0.1
HR 24 uint32 ABCD R kvarh ×0.1
HR 26 uint32 ABCD R kVAh ×0.1
HR 28 uint32 ABCD R kWh ×0.1
HR 30 uint32 ABCD R kvarh ×0.1
HR 64 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 66 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 68 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 70 int32 ABCD R A ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 72 int32 ABCD R A ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 74 int32 ABCD R A ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 76 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 78 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 80 int32 ABCD R V ×0.1 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 82 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 84 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 86 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 88 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 90 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 92 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 94 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 96 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 98 int32 ABCD R ×0.001 Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5376 uint32 ABCD R W
HR 5378 uint32 ABCD R W Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5380 uint32 ABCD R W Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5382 uint32 ABCD R W Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5384 uint32 ABCD R VA
HR 5386 uint32 ABCD R VA Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5388 uint32 ABCD R VA Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 5390 uint32 ABCD R VA Not available (ND) when the controller is wired for single phase; the equivalent values at 0000H-0010H apply
HR 4864 uint32 ABCD R kvar ×0.01
HR 4866 uint32 ABCD R kvar ×0.01
HR 4868 uint32 ABCD R kvar ×0.01
HR 4870 uint32 ABCD R kvar ×0.01
HR 4872 uint32 ABCD R kvar ×0.01
HR 4874 uint32 ABCD R kvar ×0.01
HR 4876 uint32 ABCD R kvar ×0.01
HR 4878 uint32 ABCD R kvar ×0.01
HR 4880 uint32 ABCD R kvar ×0.01
HR 4882 uint32 ABCD R kvar ×0.01
HR 4884 uint32 ABCD R kvar ×0.01
HR 4886 uint32 ABCD R kvar ×0.01
HR 4888 uint32 ABCD R kvar ×0.01
HR 4890 uint32 ABCD R kvar ×0.01
HR 4892 uint32 ABCD R kvar ×0.01
HR 4894 uint32 ABCD R kvar ×0.01
HR 4896 uint32 ABCD R kvar ×0.01
HR 4898 uint32 ABCD R kvar ×0.01
HR 4900 uint32 ABCD R kvar ×0.01
HR 4902 uint32 ABCD R kvar ×0.01
HR 4904 uint32 ABCD R kvar ×0.01
HR 4906 uint32 ABCD R kvar ×0.01
HR 4908 uint32 ABCD R kvar ×0.01
HR 4910 uint32 ABCD R kvar ×0.01
HR 4912 uint32 ABCD R kvar ×0.01
HR 4914 uint32 ABCD R kvar ×0.01
HR 4916 uint32 ABCD R kvar ×0.01
HR 4918 uint32 ABCD R kvar ×0.01
HR 4920 uint32 ABCD R kvar ×0.01
HR 4922 uint32 ABCD R kvar ×0.01
HR 4924 uint32 ABCD R kvar ×0.01
HR 4926 uint32 ABCD R kvar ×0.01
HR 4608 uint32 ABCD R s
HR 4610 uint32 ABCD R s
HR 4612 uint32 ABCD R s
HR 4614 uint32 ABCD R s
HR 4616 uint32 ABCD R s
HR 4618 uint32 ABCD R s
HR 4620 uint32 ABCD R s
HR 4622 uint32 ABCD R s
HR 4624 uint32 ABCD R s
HR 4626 uint32 ABCD R s
HR 4628 uint32 ABCD R s
HR 4630 uint32 ABCD R s
HR 4632 uint32 ABCD R s
HR 4634 uint32 ABCD R s
HR 4636 uint32 ABCD R s
HR 4638 uint32 ABCD R s
HR 4640 uint32 ABCD R s
HR 4642 uint32 ABCD R s
HR 4644 uint32 ABCD R s
HR 4646 uint32 ABCD R s
HR 4648 uint32 ABCD R s
HR 4650 uint32 ABCD R s
HR 4652 uint32 ABCD R s
HR 4654 uint32 ABCD R s
HR 4656 uint32 ABCD R s
HR 4658 uint32 ABCD R s
HR 4660 uint32 ABCD R s
HR 4662 uint32 ABCD R s