Lovato Electric DMG210 Modbus register map

Digital multimeter

  • Verified
  • 67 registers
  • Modbus RTU
  • Revision 3 · 2026-11-10

Verified: Tested on a real device.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
67 holding registers
Groups
5
Revision
3 · 2026-11-10
Added
()
File
maps/lovato-electric/dmg210.mbmap.json · 13 KB · history
SHA-256
bae415deadc7e9e3c078b4f52837ec8b0e39302dda0cf4d20f274f0afe56e974
Manufacturer
lovatoelectric.com

Sources and notes

Source: Lovato Electric, DMG series Modbus communication protocol, I317 I GB 02_22

  • Addresses are those of the manual; the address sent in the request is one less (address_base 1).
  • Function 03 and 04 both read the measurements. 32- and 64-bit values are sent high word first.
  • The model is reported by function 17 (Report Slave ID): type code 0x79.
  • Max (HI), min (LO), average and max demand values, harmonics, I/O and setup parameters (tables 4-8 of the manual) are not listed here.
  • Tested on a DMG210 read over a Modbus TCP gateway, November 2026: all 65 registers read without errors. Checked: voltages, currents, power, power factor, THD, neutral current, asymmetry, the 32-bit and 64-bit energy counters (same values), hour meters, phase sequence and the word order (big). Frequency read 5003, so its scale is 0.01 (50.03 Hz), not 0.001 as this map had before.
AreaAddressNameTypeAccessUnitScaleDescription
HR 2 uint32 ABCD R V ×0.01
HR 4 uint32 ABCD R V ×0.01
HR 6 uint32 ABCD R V ×0.01
HR 8 uint32 ABCD R A ×0.0001
HR 10 uint32 ABCD R A ×0.0001
HR 12 uint32 ABCD R A ×0.0001
HR 14 uint32 ABCD R V ×0.01
HR 16 uint32 ABCD R V ×0.01
HR 18 uint32 ABCD R V ×0.01
HR 20 int32 ABCD R W ×0.01
HR 22 int32 ABCD R W ×0.01
HR 24 int32 ABCD R W ×0.01
HR 26 int32 ABCD R var ×0.01
HR 28 int32 ABCD R var ×0.01
HR 30 int32 ABCD R var ×0.01
HR 32 uint32 ABCD R VA ×0.01
HR 34 uint32 ABCD R VA ×0.01
HR 36 uint32 ABCD R VA ×0.01
HR 38 int32 ABCD R ×0.0001
HR 40 int32 ABCD R ×0.0001
HR 42 int32 ABCD R ×0.0001
HR 50 uint32 ABCD R Hz ×0.01
HR 52 uint32 ABCD R V ×0.01
HR 54 uint32 ABCD R V ×0.01
HR 56 uint32 ABCD R A ×0.0001
HR 58 int32 ABCD R W ×0.01
HR 60 int32 ABCD R var ×0.01
HR 62 uint32 ABCD R VA ×0.01
HR 64 int32 ABCD R ×0.0001
HR 66 uint32 ABCD R % ×0.01
HR 68 uint32 ABCD R % ×0.01
HR 70 uint32 ABCD R % ×0.01
HR 72 uint32 ABCD R A ×0.0001
HR 84 uint32 ABCD R % ×0.01
HR 86 uint32 ABCD R % ×0.01
HR 88 uint32 ABCD R % ×0.01
HR 90 uint32 ABCD R % ×0.01
HR 92 uint32 ABCD R % ×0.01
HR 94 uint32 ABCD R % ×0.01
HR 96 uint32 ABCD R % ×0.01
HR 98 uint32 ABCD R % ×0.01
HR 100 uint32 ABCD R % ×0.01
HR 6688 uint32 ABCD R kWh ×0.01 Rolls over after 19 999 999.99
HR 6690 uint32 ABCD R kWh ×0.01 Rolls over after 19 999 999.99
HR 6692 uint32 ABCD R kvarh ×0.01 Rolls over after 19 999 999.99
HR 6694 uint32 ABCD R kvarh ×0.01 Rolls over after 19 999 999.99
HR 6696 uint32 ABCD R kVAh ×0.01 Rolls over after 19 999 999.99
HR 6698 uint32 ABCD R kWh ×0.01 Rolls over after 19 999 999.99
HR 6700 uint32 ABCD R kWh ×0.01 Rolls over after 19 999 999.99
HR 6702 uint32 ABCD R kvarh ×0.01 Rolls over after 19 999 999.99
HR 6704 uint32 ABCD R kvarh ×0.01 Rolls over after 19 999 999.99
HR 6706 uint32 ABCD R kVAh ×0.01 Rolls over after 19 999 999.99
HR 6944 uint64 ABCD R kWh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6948 uint64 ABCD R kWh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6952 uint64 ABCD R kvarh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6956 uint64 ABCD R kvarh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6960 uint64 ABCD R kVAh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6964 uint64 ABCD R kWh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6968 uint64 ABCD R kWh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6972 uint64 ABCD R kvarh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6976 uint64 ABCD R kvarh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 6980 uint64 ABCD R kVAh ×0.01 64-bit counter from software revision 07; older revisions roll over like the 32-bit counters
HR 7680 uint32 ABCD R s
HR 7682 uint32 ABCD R s
HR 8308 uint16 R
HR 12033 uint16 W Write 1
HR 12272 uint16 W Write with function 06; send a reboot after the parameter commands (13-15)