Schneider Electric Altivar 320 Modbus register map

Altivar 320 variable speed drive: every parameter, by its Modbus (logic) address

  • Official
  • 1,071 registers
  • Modbus TCP and RTU
  • Revision 2 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502default
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
1071 holding registers
Groups
17
Revision
2 · 2026-10-18
Added
()
File
maps/schneider-electric/altivar-320.mbmap.json · 237 KB · history
SHA-256
9df6a08ed4511da3aacd453a6149b1e6dcf4836fdd149fcde2cffcb2f152bc69
Manufacturer
se.com

Sources and notes

Source: Schneider Electric, Altivar 320 communication parameters (NVE41316 V3.5)

  • The address of each parameter is its logic address, which is also its Modbus register address.
  • Each name ends with the parameter code used in the drive menus and manuals.
  • Parameters marked 'writable only when the motor is stopped' are refused while the drive runs.
  • Many enumerations are shared lists in the source file; only the parameter-specific ones are included here.
AreaAddressNameTypeAccessUnitScaleDescription
HR 3011 uint16 R Factory setting [Unknown rating] NO
HR 3012 uint16 R Factory setting [Unknown drive rate volt.] NO
HR 3015 uint16 RW Writable only when the motor is stopped; Factory setting [50Hz Motor frequency] 50Hz
HR 3017 uint16 R A ×0.1 Range 0.0 A ... 6553.5 A; Factory setting Refer to programming manual
HR 3022 uint16 RW Writable only when the motor is stopped; Factory setting BIT1
HR 3052 uint16 RW Writable only when the motor is stopped; Factory setting [Standard Start/Stop] STS
HR 3053 uint16 R
HR 3101 uint16 RW Writable only when the motor is stopped; Factory setting [Switch.frequency type 1] HF1
HR 3102 uint16 RW kHz ×0.1 Range 2.0 kHz ... 16.0 kHz; Factory setting 4.0 kHz
HR 3103 uint16 RW Hz ×0.1 Writable only when the motor is stopped; Range 10.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3104 uint16 RW Hz ×0.1 Range 0.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3105 uint16 RW Hz ×0.1 Range 0.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3106 uint16 RW Factory setting [Standard ref template] BSD
HR 3107 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3108 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3110 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3112 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3120 uint16 RW Factory setting [No] NO
HR 3130 uint16 RW Factory setting Refer to programming manual
HR 3201 uint16 R
HR 3202 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3203 int16 R Hz ×0.1 Range -599.0 Hz ... 599.0 Hz
HR 3204 uint16 R A ×0.1 Range 0.0 A ... 6553.5 A
HR 3205 int16 R % ×0.1 Range -3276.7 % ... 3276.7 %
HR 3206 uint16 R
HR 3207 uint16 R V ×0.1 Range 0.0 V ... 6553.5 V
HR 3208 uint16 R V Range 0 V ... 65535 V
HR 3209 uint16 R % Range 0 % ... 200 %
HR 3211 int16 R % Range -32767 % ... 32767 %
HR 3219 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3222 int16 R Range -32767 ... 32767
HR 3224 uint16 R A ×0.1 Range 0.0 A ... 6553.5 A
HR 3225 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3226 int16 R Range -32767 ... 32767
HR 3229 uint16 R V ×0.1 Range 0.0 V ... 6553.5 V
HR 3230 uint16 R Unit: Refer to programming manual; Range 0 ... 65535
HR 3231 uint16 R Unit: Refer to programming manual; Range 0 ... 65535
HR 3233 uint16 R Unit: Refer to programming manual; Range 0 ... 65535
HR 3234 uint16 R
HR 3235 uint16 R s Range 0 s ... 65535 s
HR 3240 uint16 R
HR 3241 uint16 R Range 0 ... 65535
HR 3242 uint16 R s Range 0 s ... 65535 s
HR 3250 uint16 R
HR 3251 uint16 R
HR 3252 uint16 R
HR 3253 uint16 R
HR 3254 uint16 R
HR 3255 uint16 R
HR 3256 uint16 R
HR 3257 uint16 R
HR 3281 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3290 int16 R % Range -32767 % ... 32767 %
HR 3302 uint16 R Range 0 ... 65535
HR 3340 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3341 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3342 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3343 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3344 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3345 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3346 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3347 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3561 uint16 R Factory setting [Not configured] NO
HR 3699 uint16 RW Range 0 ... 65535
HR 4001 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4002 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4003 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4004 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4005 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4006 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4021 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4022 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 0 ms
HR 4201 uint16 RW Writable only when the motor is stopped; Factory setting [1] POS
HR 4202 uint16 RW Writable only when the motor is stopped; Factory setting [1] POS
HR 4209 uint16 RW Writable only when the motor is stopped; Factory setting [1] POS
HR 4221 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 9999 ms; Factory setting 0 ms
HR 4222 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 9999 ms; Factory setting 0 ms
HR 4229 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 9999 ms; Factory setting 0 ms
HR 4241 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4242 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4249 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4261 uint16 RW Writable only when the motor is stopped; Factory setting [1] POS
HR 4271 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 9999 ms; Factory setting 0 ms
HR 4281 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4290 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 4291 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 4292 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 4293 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 4402 uint16 RW Writable only when the motor is stopped; Factory setting [AI in voltage selected] 10U
HR 4403 uint16 RW Writable only when the motor is stopped; Factory setting [AI bipolar volts selected] N10U
HR 4404 uint16 RW Writable only when the motor is stopped; Factory setting [AI in current selected] 0A
HR 4412 uint16 RW V ×0.1 Writable only when the motor is stopped; Range 0.0 V ... 10.0 V; Factory setting 0.0 V
HR 4413 uint16 RW V ×0.1 Writable only when the motor is stopped; Range 0.0 V ... 10.0 V; Factory setting 0.0 V
HR 4422 uint16 RW V ×0.1 Writable only when the motor is stopped; Range 0.0 V ... 10.0 V; Factory setting 10.0 V
HR 4423 uint16 RW V ×0.1 Writable only when the motor is stopped; Range 0.0 V ... 10.0 V; Factory setting 10.0 V
HR 4434 uint16 RW mA ×0.1 Writable only when the motor is stopped; Range 0.0 mA ... 20.0 mA; Factory setting 0.0 mA
HR 4444 uint16 RW mA ×0.1 Writable only when the motor is stopped; Range 0.0 mA ... 20.0 mA; Factory setting 20.0 mA
HR 4452 uint16 RW s ×0.01 Writable only when the motor is stopped; Range 0.00 s ... 10.00 s; Factory setting 0.00 s
HR 4453 uint16 RW s ×0.01 Writable only when the motor is stopped; Range 0.00 s ... 10.00 s; Factory setting 0.00 s
HR 4454 uint16 RW s ×0.01 Writable only when the motor is stopped; Range 0.00 s ... 10.00 s; Factory setting 0.00 s