Schneider Electric Altivar 12 (ATV12) Modbus register map

Compact variable speed drive with Modbus RTU on its RJ45 port

  • Official
  • 43 registers
  • Modbus RTU
  • Revision 1 · 2026-11-11

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
43 holding registers
Groups
4
Revision
1 · 2026-11-11
Added
()
File
maps/schneider-electric/atv12.mbmap.json · 12 KB · history
SHA-256
2bd80adb9763cf13271c930e249224c359be88bec1b48217e33e88ee2c5d0879
Manufacturer
se.com

Sources and notes

  • Altivar 12 Modbus Communication Manual · version BBV28590 06/2012
    Communication parameters, drive state machine, command and status words and the I/O scanner

Source: Schneider Electric, ATV12 Modbus Communication Manual BBV28590, 06/2012

  • Partial map: the manual gives the communication settings, the control and status words, the communication scanner and a few examples. The full list of drive parameters is in a separate Excel file that came with the manual and is not mapped here.
  • Registers are addressed as the W numbers of the manual (W3201 is address 3201; the examples send 16#0C81 for 3201 and 16#2329 for 9001), so address_base is 0. Functions: 0x03 read, 0x06 write one, 0x10 write several, 0x17 read/write (four words each way), 0x2B/0x0E device identification.
  • Control: write the command word (CMD, 8501) with 6, 7 and then 15 to run and read the status word (ETA, 3201); the state machine follows IEC 61800-7. A masked ETA (ETA and 16#006F) gives the state: 16#0050 switch on disabled, 16#0031 ready, 16#0033 switched on, 16#0037 operation enabled, 16#0017 quick stop active.
  • Units are given only by the manual's examples (HSP 50 Hz = 500, tFr 60 Hz = 600, SFr 4 kHz = 40, so 0.1 Hz and 0.1 kHz); no scale is set because the manual does not state it in a table.
  • Serial settings: 4.8, 9.6, 19.2 or 38.4 kbps (default 19.2 kbps on the ATV12), 8E1 by default, address 1 to 247. The factory address is off until set. Address 0 is broadcast and is not answered.
  • This map covers the ATV12 only; the ATV212 uses a different manual.
AreaAddressNameTypeAccessUnitScaleDescription
HR 3201 uint16 R Drive state word; 16#0637 stopped or forward at speed, 16#0237 forward accelerating or decelerating, 16#8237 reverse accelerating or decelerating
HR 3201 bool bit 0 R
HR 3201 bool bit 1 R
HR 3201 bool bit 2 R
HR 3201 bool bit 3 R
HR 3201 bool bit 4 R
HR 3201 bool bit 5 R
HR 3201 bool bit 6 R
HR 3201 bool bit 9 R
HR 3201 bool bit 10 R
HR 3201 bool bit 11 R
HR 3201 bool bit 14 R
HR 3201 bool bit 15 R
HR 3206 uint16 R
HR 8501 uint16 RW Drive state commands: 6 shutdown, 7 switch on, 15 enable operation, 0 disable voltage, 2 quick stop, 128 fault reset (rising edge). Bit 11 reverse direction, bit 8 stop
HR 8504 uint16 RW
HR 8602 uint16 RW Speed reference written over Modbus
HR 8604 uint16 R
HR 3102 uint16 RW Example value 40 for 4 kHz
HR 3103 uint16 RW Example value 600 for 60 Hz (0.1 Hz)
HR 3104 uint16 RW Example value 500 for 50 Hz (0.1 Hz)
HR 3105 uint16 RW 0.1 Hz
HR 9001 uint16 RW The manual's example writes 13 for 13 s
HR 6001 uint16 RW 0 = off (broadcast only), 1 to 247
HR 6003 uint16 RW 4.8, 9.6, 19.2 or 38.4 kbps
HR 6004 uint16 RW 8O1, 8E1, 8N1 or 8N2
HR 6005 uint16 RW 0.1 to 30 s, default 10 s
HR 12701 uint16 RW Address of the parameter read as input word 1
HR 12702 uint16 RW Address of the parameter read as input word 2
HR 12703 uint16 RW Address of the parameter read as input word 3
HR 12704 uint16 RW Address of the parameter read as input word 4
HR 12721 uint16 RW Address of the parameter written as output word 1
HR 12722 uint16 RW Address of the parameter written as output word 2
HR 12723 uint16 RW Address of the parameter written as output word 3
HR 12724 uint16 RW Address of the parameter written as output word 4
HR 12741 uint16 R
HR 12742 uint16 R
HR 12743 uint16 R
HR 12744 uint16 R
HR 12761 uint16 RW
HR 12762 uint16 RW
HR 12763 uint16 RW
HR 12764 uint16 RW