  3. Acti9 iEM3000 (iEM3150 / iEM3155 / iEM3250 / iEM3255 / iEM3350 / iEM3355)

Schneider Electric Acti9 iEM3000 (iEM3150 / iEM3155 / iEM3250 / iEM3255 / iEM3350 / iEM3355) Modbus register map

DIN rail three-phase energy meters with Modbus RS-485: iEM3150/3155 (63 A direct), iEM3250/3255 (CT), iEM3350/3355 (125 A direct)

  • Verified
  • 81 registers
  • Modbus RTU
  • Revision 2
  • Identity: model, serial number

Verified: Tested on a real device.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
81 holding registers
Groups
12
Translation tables
3
Revision
2
Added
()
File
maps/schneider-electric/iem3000.mbmap.json · 16 KB · history
SHA-256
ee8fe1b83ed3b2a4bfa7650561e67527a108eb301e570f9ed254a112af7c1f0c
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter model holding 50 string[20]
Serial number Serial number holding 130 uint32 ABCD

Sources and notes

Source: Schneider Electric, "iEM3100 / iEM3200 / iEM3300 series User Manual", DOCA0005EN-16; https://www.productinfo.schneider-electric.com/iem3100_iem3200_iem3300/

  • Schneider Electric Acti9 iEM3000 energy meters with Modbus RS-485 (iEM3150/3155, iEM3250/3255, iEM3350/3355).
  • Addresses are the manual's register numbers (address on the wire = register - 1).
  • The meter only supports FC03 (read) and FC16 (write). Settings marked WC in the manual are changed through the command interface (registers 5250+), so they are listed here as read-only.
  • Rows marked "not on iEM3x50" only exist on the iEM3155 / iEM3255 / iEM3355.
  • Tested on an iEM3250 and an iEM3155, both hardware revision 1.0.0 and firmware 14002, read over a Modbus TCP gateway, November 2026: all 81 registers read without errors on each. Checked: identification (name, model, manufacturer, serial number), setup, communication, currents, voltages, frequency, power, power factor, the 64-bit energy counters and their float copies (iEM3155: 127432214 Wh = 127432.21875 kWh), and the phase energies. On the iEM3155, L1 + L2 + L3 active power (2.5512 kW) equals the total, and active / apparent power (2.5512 / 4.0854) gives the power factor 0.6245 that the meter reports.
  • On the iEM3250 the rows marked "not on iEM3x50" read NaN (floats) or 0xFFC00000; on the iEM3155 they read values (reactive and apparent power, energy export, the reactive phase energies, the four rates, which were 0 because multi-tariff is disabled). Both meters answer FC17 with illegal function.
  • Not verified: the meaning of diagnostic codes 204 and 205 (code 205 was active on both meters, and 204 also on the iEM3250), and Digital input status (8906), which read 0x00008000 on the iEM3155 and 0xFFC00000 on the iEM3250: the 32-bit value does not fit the description of bit 1 given for it, and the state of the input was not known.
AreaAddressNameTypeAccessUnitScaleDescription
HR 30 string[20] R
HR 50 string[20] R
HR 70 string[20] R
HR 130 uint32 ABCD R
HR 136 string[5] R
HR 1637 uint16 R DLF format X.Y.ZTT
HR 45000 bool bit 0 R
HR 45000 bool bit 1 R
HR 45000 bool bit 2 R
HR 45000 bool bit 3 R
HR 45000 bool bit 4 R
HR 45000 bool bit 5 R
HR 45000 bool bit 6 R
HR 45000 bool bit 7 R
HR 45000 bool bit 8 R
HR 2014 uint16 R
HR 2015 uint16 R
HR 2016 uint16 R Set with the command interface
HR 2017 uint16 R Hz Set with the command interface
HR 2030 uint16 R A iEM3250/3255 only
HR 2031 uint16 R A iEM3250/3255 only
HR 6501 uint16 R Set with the command interface
HR 6502 uint16 R Set with the command interface
HR 6503 uint16 R One stop bit
HR 3000 float32 ABCD R A
HR 3002 float32 ABCD R A
HR 3004 float32 ABCD R A
HR 3010 float32 ABCD R A
HR 3020 float32 ABCD R V
HR 3022 float32 ABCD R V
HR 3024 float32 ABCD R V
HR 3026 float32 ABCD R V
HR 3028 float32 ABCD R V
HR 3030 float32 ABCD R V
HR 3032 float32 ABCD R V
HR 3036 float32 ABCD R V
HR 3054 float32 ABCD R kW
HR 3056 float32 ABCD R kW
HR 3058 float32 ABCD R kW
HR 3060 float32 ABCD R kW
HR 3068 float32 ABCD R kvar Not on iEM3x50
HR 3076 float32 ABCD R kVA Not on iEM3x50
HR 3084 float32 ABCD R Four-quadrant encoding: 0..1 Q1, 1..2 Q4, -1..0 Q2, -2..-1 Q3
HR 3192 float32 ABCD R Plain -1..+1 value; recent firmware of iEM3x55 only
HR 3194 float32 ABCD R Recent firmware of iEM3x55 only
HR 3110 float32 ABCD R Hz
HR 4191 uint16 R Not on iEM3x50
HR 3204 int64 ABCD R Wh Cannot be reset
HR 3208 int64 ABCD R Wh Not on iEM3x50
HR 3220 int64 ABCD R varh Not on iEM3x50
HR 3224 int64 ABCD R varh Not on iEM3x50
HR 3256 int64 ABCD R Wh
HR 3272 int64 ABCD R varh Not on iEM3x50
HR 3518 int64 ABCD R Wh
HR 3522 int64 ABCD R Wh
HR 3526 int64 ABCD R Wh
HR 3558 int64 ABCD R Not on iEM3x50
HR 4196 int64 ABCD R Wh Not on iEM3x50
HR 4200 int64 ABCD R Wh Not on iEM3x50
HR 4204 int64 ABCD R Wh Not on iEM3x50
HR 4208 int64 ABCD R Wh Not on iEM3x50
HR 45100 float32 ABCD R kWh Same counter as 3204
HR 45102 float32 ABCD R kWh Not on iEM3x50
HR 45104 float32 ABCD R kvarh Not on iEM3x50
HR 45106 float32 ABCD R kvarh Not on iEM3x50
HR 45108 float32 ABCD R kWh
HR 45110 float32 ABCD R kvarh Not on iEM3x50
HR 45112 float32 ABCD R kWh
HR 45114 float32 ABCD R kWh
HR 45116 float32 ABCD R kWh
HR 45118 float32 ABCD R Not on iEM3x50
HR 45120 float32 ABCD R kWh Not on iEM3x50
HR 45122 float32 ABCD R kWh Not on iEM3x50
HR 45124 float32 ABCD R kWh Not on iEM3x50
HR 45126 float32 ABCD R kWh Not on iEM3x50
HR 45128 float32 ABCD R kvarh iEM3x55 with 1PH4W multi L-N firmware
HR 45130 float32 ABCD R kvarh iEM3x55 with 1PH4W multi L-N firmware
HR 45132 float32 ABCD R kvarh iEM3x55 with 1PH4W multi L-N firmware
HR 8906 uint32 ABCD R Bit 1: 0 = open, 1 = closed. iEM3x55 only
HR 45005 uint16 R iEM3x55 only
HR 45011 float32 ABCD R kW iEM3x55 only