MBMap Registry
  1. Devices
  2. Schneider Electric
  3. InRow RC3xx (ACRC30x)

Schneider Electric InRow RC3xx (ACRC30x) Modbus register map

InRow ACRC30x chilled water row cooler: group and unit status, set points and alarms

  • Official
  • 147 registers
  • Revision 1 · 2026-10-18
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
147 holding registers
Groups
3
Translation tables
17
Revision
1 · 2026-10-18
Added
()
File
maps/schneider-electric/inrow-acrc30x.mbmap.json · 22 KB · history
SHA-256
62cf0f848dff184f835e9f8028e78b94aeef71c373f80fb013c9085d78c5bbb4
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Model number holding 172 string[10]
Serial number Serial number holding 182 string[10]
Firmware Firmware rev holding 192 string[4]

Sources and notes

  • Modbus Register Map: InRow ACRC30x · version 990-4742A
    KKRZ-99YNMA_R1; all four pages

Source: Schneider Electric, Modbus Register Map: InRow ACRC30x, part number 990-4742A

  • Register numbers are the absolute decimal addresses of the manual (Modicon 40001 is address 0).
  • Reads use function code 3 or 4 and writes function code 16, or 6 for one-register values. Serial RTU and Modbus TCP are supported.
  • Temperatures are in °F; INT32 values have the most significant word first.
  • Reading a block that starts at a valid register returns zeros for reserved ones; reading a reserved register alone returns an error.
  • A reply can take 2 s or more for large blocks: read fewer registers or raise the timeout.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 R
HR 1 int32 ABCD R kW ×0.1
HR 3 int32 ABCD R kW ×0.1
HR 5 int32 ABCD RW °F ×0.1
HR 7 int32 ABCD RW °F ×0.1
HR 9 int32 ABCD R CFM
HR 11 int32 ABCD R °F ×0.1
HR 13 int32 ABCD R °F ×0.1
HR 15 uint16 RW
HR 16 int32 ABCD RW
HR 18 uint16 R
HR 19 int32 ABCD R ×0.01
HR 21 int32 ABCD R ×0.01
HR 23 int32 ABCD R ×0.01
HR 25 int32 ABCD R %
HR 27 int32 ABCD RW %
HR 30 int32 ABCD RW Feet
HR 32 int32 ABCD RW
HR 34 uint16 R
HR 35 uint16 R
HR 36 uint16 RW
HR 37 uint16 RW
HR 128 string[21] RW
HR 149 string[21] RW
HR 172 string[10] R
HR 182 string[10] R
HR 192 string[4] R
HR 196 string[4] R
HR 200 string[6] R Date as mm/dd/yyyy
HR 206 uint16 R
HR 207 int32 ABCD R kW ×0.1
HR 209 int32 ABCD R kW ×0.1
HR 211 int32 ABCD R °F ×0.1
HR 213 int32 ABCD R °F ×0.1
HR 215 int32 ABCD R °F ×0.1
HR 217 int32 ABCD R CFM
HR 219 int32 ABCD R % ×0.1
HR 221 uint16 R
HR 222 int32 ABCD R inWC ×0.01
HR 226 int32 ABCD R %
HR 228 int32 ABCD R GPM ×0.1
HR 230 int32 ABCD R °F ×0.1
HR 232 int32 ABCD R °F ×0.1
HR 234 int32 ABCD R Hours
HR 236 int32 ABCD R Hours
HR 238 int32 ABCD R Hours
HR 240 int32 ABCD R Hours
HR 242 int32 ABCD R Hours
HR 244 int32 ABCD R Hours
HR 246 int32 ABCD R Hours
HR 248 int32 ABCD R Hours
HR 250 int32 ABCD R Hours
HR 252 int32 ABCD R Hours
HR 254 int32 ABCD R Hours
HR 256 int32 ABCD R Hours
HR 258 int32 ABCD RW Weeks
HR 260 uint16 RW
HR 261 int32 ABCD RW °F ×0.1
HR 263 int32 ABCD RW °F ×0.1
HR 265 int32 ABCD RW °F ×0.1
HR 267 int32 ABCD RW °F ×0.1
HR 269 int32 ABCD RW sec
HR 271 uint16 R
HR 272 uint16 RW
HR 273 uint16 RW
HR 274 uint16 R
HR 276 uint16 R
HR 278 uint16 RW
HR 279 uint16 RW
HR 280 uint16 R
HR 281 uint16 R
HR 282 uint16 R
HR 283 uint16 R
HR 289 int32 ABCD R GPM ×0.1
HR 291 uint16 RW
HR 292 int32 ABCD R Weeks
HR 294 uint16 R
HR 295 int32 ABCD R °F ×0.1
HR 297 int32 ABCD R °F ×0.1
HR 299 int32 ABCD R kW ×0.1
HR 301 int32 ABCD R kWh ×0.1
HR 303 int32 ABCD R Hours
HR 305 int32 ABCD R Hours
HR 307 int32 ABCD RW
HR 309 int32 ABCD RW
HR 311 uint16 RW
HR 384 uint16 R
HR 386 uint16 R
HR 387 uint16 R
HR 388 uint16 R
HR 389 uint16 R
HR 390 uint16 R
HR 391 uint16 R
HR 392 uint16 R
HR 393 uint16 R
HR 394 uint16 R
HR 395 uint16 R
HR 396 uint16 R
HR 397 uint16 R
HR 398 uint16 R

Help improve this map