Schneider Electric PM1000 / PM1200 Modbus register map

PowerLogic PM1000 series panel power meters; the PM1200 has the RS-485 Modbus RTU port

  • Official
  • 57 registers
  • Modbus RTU
  • Revision 3 · 2026-10-24

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
57 holding registers
Groups
7
Revision
3 · 2026-10-24
Added
()
File
maps/schneider-electric/pm1000-pm1200.mbmap.json · 9 KB · history
SHA-256
2625305ba5745a60a1292867512df637e7ed31652490cfb0189261589b7e81c2
Manufacturer
se.com

Sources and notes

Source: PowerLogic PM1000 Series Power Meters User manual, PLSED309039EN, 08/2010, chapter 6

  • Only the PM1200 communicates: the PM1000 has no RS-485 port.
  • Function 03 only. Registers are numbered as in the manual (3901 is holding register 43901), 1-based, so 3901 is sent as 3900.
  • Values are 32-bit floats, low word first ('little endian float' in the manual), in base units (V, A, W, VA, Wh); the run counters are 32-bit integers.
  • This map uses the individual parameter addresses (3861-3999), which can be read one value at a time. The manual's block addresses (3001-3199, 3721-3775) hold the same data but must be read as whole blocks of 20 registers (FAQ FA212915), so they are left out.
  • Factory settings: address 1, 9600 bps, even parity, 8 data bits, 1 stop bit. Poll about once a second at 9600 bps.
  • Written from the manufacturer's manual; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 3861 float32 CDAB R % THD option only
HR 3863 float32 CDAB R % THD option only
HR 3865 float32 CDAB R % THD option only
HR 3867 float32 CDAB R % THD option only; -999.0 when the secondary current is out of range or f > 65 Hz
HR 3869 float32 CDAB R % THD option only
HR 3871 float32 CDAB R % THD option only
HR 3881 float32 CDAB R %
HR 3883 float32 CDAB R %
HR 3885 float32 CDAB R %
HR 3887 float32 CDAB R %
HR 3889 float32 CDAB R %
HR 3891 float32 CDAB R %
HR 3901 float32 CDAB R VA
HR 3903 float32 CDAB R W
HR 3905 float32 CDAB R var
HR 3907 float32 CDAB R
HR 3909 float32 CDAB R V
HR 3911 float32 CDAB R V
HR 3913 float32 CDAB R A
HR 3915 float32 CDAB R Hz
HR 3917 float32 CDAB R VA
HR 3919 float32 CDAB R W
HR 3921 float32 CDAB R var
HR 3923 float32 CDAB R
HR 3925 float32 CDAB R V
HR 3927 float32 CDAB R V
HR 3929 float32 CDAB R A
HR 3931 float32 CDAB R VA
HR 3933 float32 CDAB R W
HR 3935 float32 CDAB R var
HR 3937 float32 CDAB R
HR 3939 float32 CDAB R V
HR 3941 float32 CDAB R V
HR 3943 float32 CDAB R A
HR 3945 float32 CDAB R VA
HR 3947 float32 CDAB R W
HR 3949 float32 CDAB R var
HR 3951 float32 CDAB R
HR 3953 float32 CDAB R V
HR 3955 float32 CDAB R V
HR 3957 float32 CDAB R A
HR 3959 float32 CDAB R VAh
HR 3961 float32 CDAB R Wh
HR 3963 float32 CDAB R varh
HR 3965 float32 CDAB R varh
HR 3967 float32 CDAB R VAh
HR 3969 float32 CDAB R Wh
HR 3971 float32 CDAB R varh
HR 3973 float32 CDAB R varh
HR 3975 float32 CDAB R In the unit of the demand parameter selected on the meter (W or VA)
HR 3977 float32 CDAB R
HR 3979 float32 CDAB R
HR 3981 uint32 CDAB R Occurrence time of the maximum demand
HR 3993 uint32 CDAB R Run hours counter
HR 3995 uint32 CDAB R s
HR 3997 uint32 CDAB R s
HR 3999 uint32 CDAB R Number of supply interruptions