MBMap Registry
  1. Devices
  2. Schneider Electric
  3. PM5100 / PM5300

Schneider Electric PM5100 / PM5300 Modbus register map

Also covers PM5110, PM5111, PM5310, PM5320, PM5330, PM5331, PM5340, PM5341

Power meter

  • Official
  • 2,277 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18
  • Identity: model, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
2277 holding registers
Groups
14
Revision
3 · 2026-10-18
Added
()
File
maps/schneider-electric/pm5100-pm5300.mbmap.json · 528 KB · history
SHA-256
23a235221cb909c6094a232f4756bef74c748951c6251c6a05a0aad48898803f
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter Model holding 50 string[20]
Serial number Serial Number holding 130 uint32 ABCD

Sources and notes

Source: Schneider Electric, PM5100 and PM5300 Modbus register list

  • Addresses are the register numbers of the register list (Modicon numbering, 1-based): the address on the wire is the register number minus 1.
  • Registers marked RWC in the register list are changed through the command interface (registers 5000 and following), so they are listed as read-only.
  • Values the meter cannot provide read as the N/A value of their data type (0xFFFF, 0xFFFFFFFF, 0x8000 or a float NaN).
  • Power factor registers are four-quadrant values from -2 to 2, not plain power factors: 0° = 1, 90° = 0, 180° = -1, 270° = 2. Above 1, the power factor is 2 minus the value and leading; below -1 it is -2 minus the value and leading; otherwise it is the value, lagging (unity at ±1).
  • Registers that exist only on some of the models say so in their description.
  • Where the register list names the models PM5110_11, PM5330_31 or PM5340_41, the description shows those names.
AreaAddressNameTypeAccessUnitScaleDescription
HR 30 string[20] R
HR 50 string[20] R
HR 70 string[20] R
HR 90 uint16 R
HR 91 uint64 ABCD R Bitmap. Range: 0x0000 – 0xFFFF. Bitmap indicating base hardware options detected Bit 01 = HMI Bit 02 = Modbus Serial Communications Port Bit 03 = Modbus Ethernet Communications Port Bit 04 = Digital Inputs Bit 05 = Digital Outputs Bit 06-16 Not Used
HR 95 uint64 ABCD R Bitmap. Range: 0x0000 – 0xFFFF
HR 129 uint16 R Manufacturing Unit ID
HR 130 uint32 ABCD R
HR 132 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 136 string[5] R
HR 141 uint16 R
HR 142 uint16 R
HR 143 uint16 R
HR 144 uint16 R
HR 145 uint16 R
HR 146 uint16 R
HR 147 uint16 R
HR 148 uint16 R
HR 149 uint16 R
HR 150 uint16 R
HR 151 uint16 R
HR 152 uint16 R
HR 153 uint16 R
HR 154 uint16 R
HR 155 uint16 R
HR 156 uint16 R
HR 157 uint16 R
HR 158 uint16 R
HR 159 uint16 R
HR 160 uint16 R
HR 161 uint16 R
HR 1637 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1638 uint16 R Range: 00 – 99
HR 1639 uint16 R Range: 0000 – 9999
HR 1640 uint16 R Range: 0000 – 9999
HR 1641 uint16 R Range: 0000 – 9999
HR 1642 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1643 uint16 R Range: 00 – 99
HR 1644 uint16 R Range: 0000 – 9999
HR 1645 uint16 R Range: 0000 – 9999
HR 1646 uint16 R Range: 0000 – 9999
HR 1647 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1701 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1702 uint16 R Range: 00 – 99
HR 1703 uint16 R Range: 0000 – 9999
HR 1704 uint16 R Range: 0000 – 9999
HR 1705 uint16 R Range: 0000 – 9999
HR 1706 uint16 R Range: 0 – 32,767
HR 1707 uint16 R Range: 00 – 99
HR 1708 uint16 R Range: 0000 – 9999
HR 1709 uint16 R Range: 0000 – 9999
HR 1710 uint16 R Range: 0000 – 9999
HR 1711 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1715 uint16 R
HR 1716 uint16 R
HR 1751 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1755 uint16 R
HR 1756 uint16 R
HR 1757 uint16 R
HR 1758 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1762 uint16 R
HR 1763 uint16 R
HR 1764 uint16 R
HR 1765 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1769 uint16 R
HR 1770 uint16 R
HR 1771 uint16 R
HR 1772 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1776 uint16 R
HR 1777 uint16 R
HR 1778 uint16 R
HR 1779 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1783 uint16 R
HR 1784 uint16 R
HR 1785 uint16 R
HR 1786 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1790 uint16 R
HR 1791 uint16 R
HR 1792 uint16 R
HR 1793 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1797 uint16 R
HR 1798 uint16 R
HR 1799 uint16 R
HR 1800 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1804 uint16 R
HR 1805 uint16 R
HR 1806 uint16 R
HR 1807 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1811 uint16 R
HR 1812 uint16 R
HR 1813 uint16 R
HR 1814 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1818 uint16 R
HR 1819 uint16 R
HR 1820 uint16 R
HR 1821 uint16 R Range: 0 – 10
HR 1824 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1828 uint16 R
HR 1829 uint16 R
HR 1830 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)

Help improve this map