Schneider Electric PM5500 Modbus register map

Also covers PM5560, PM5561, PM5563, PM5570, PM5580

Power meter

  • Official
  • 4,703 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18
  • Identity: model, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
4703 holding registers
Groups
14
Revision
3 · 2026-10-18
Added
()
File
maps/schneider-electric/pm5500.mbmap.json · 1.0 MB · history
SHA-256
15930723fb8ed980eb1c4969bd250d3bbd475dab6a293a35e2756e2c83678791
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Model Meter Model holding 50 string[20]
Serial number Serial Number holding 130 uint32 ABCD

Sources and notes

Source: Schneider Electric, PM5560, PM5561, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760 and PM5761 public Modbus register list

  • Addresses are the register numbers of the register list (Modicon numbering, 1-based): the address on the wire is the register number minus 1.
  • Registers marked RWC in the register list are changed through the command interface (registers 5000 and following), so they are listed as read-only.
  • Values the meter cannot provide read as the N/A value of their data type (0xFFFF, 0xFFFFFFFF, 0x8000 or a float NaN).
  • Power factor registers are four-quadrant values from -2 to 2, not plain power factors: 0° = 1, 90° = 0, 180° = -1, 270° = 2. Above 1, the power factor is 2 minus the value and leading; below -1 it is -2 minus the value and leading; otherwise it is the value, lagging (unity at ±1).
  • Registers that exist only on some of the models say so in their description.
AreaAddressNameTypeAccessUnitScaleDescription
HR 30 string[20] R
HR 50 string[20] R
HR 70 string[20] R
HR 90 uint16 R PM5350 = 15234, PM5350RB = 15283
HR 130 uint32 ABCD R
HR 132 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 136 string[5] R
HR 1637 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1638 uint16 R Range: 00 – 99
HR 1639 uint16 R Range: 0000 – 9999
HR 1640 uint16 R Range: 0000 – 9999
HR 1642 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1643 uint16 R Range: 00 – 99
HR 1644 uint16 R Range: 0000 – 9999
HR 1645 uint16 R Range: 0000 – 9999
HR 1647 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1669 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1701 uint16 R Range: 0 – 32,767. The firmware version takes the following form: XXYYT
HR 1824 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1828 uint16 R
HR 1829 uint16 R
HR 1830 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 1834 uint32 ABCD R s
HR 1836 uint16 R Range: 0 – 2. 0 = Unknown 1 = Reset command 2 = Power failure
HR 1837 uint16 R year Range: 2000 – 2127
HR 1838 uint16 R month Range: 1 – 12
HR 1839 uint16 R days Range: 1 – 31
HR 1840 uint16 R hours Range: 0 – 23
HR 1841 uint16 R min Range: 0 – 59
HR 1842 uint16 R s Range: 0 – 59
HR 1843 uint16 R ms Range: 0 – 999
HR 1845 uint16 R Range: 0 – 127
HR 1846 uint16 R Range: 1 – 12, 1 – 31
HR 1847 uint16 R Range: 0 – 23, 0 – 59
HR 1848 uint16 R Range: 0 – 59,999
HR 1920 uint16 R Range: 0 – 1. 0 = disabled, 1 = enabled
HR 1921 uint16 R Range: 0 – 4. 0 = inactive, 1 = active, For RMICAN 3 = inactive, 4 = active,
HR 1922 uint64 ABCD R DATETIME, 4 registers (IEC 870-5-4: year, day/weekday/month, hour/minute, milliseconds)
HR 2002 uint32 ABCD R s Increments when average current exceeds the Active Load Timer Setpoint
HR 2004 uint32 ABCD R s
HR 2014 uint16 R Range: 1 or 3. Must match Power System Configuration Enumeration
HR 2015 uint16 R Range: 2 – 4. Must match Power System Configuration Enumeration
HR 2016 uint16 R Range: 0 – 13 PM5350: 0 - 12
HR 2017 uint16 R Hz Range: 50, 60, 400 PM5350: 50, 60. PM5350 does not support 400Hz
HR 2018 float32 ABCD R V Range: 0 – (2xVT Primary or 2,000,000)
HR 2020 float32 ABCD R A Range: 0 – (4xCT Primary or 50,000)
HR 2022 float32 ABCD R Four-quadrant power factor. Range: +/- 0.0 – 2.0
HR 2024 uint16 R Range: 0 – 1
HR 2025 uint16 R Range: Depends on Power System
HR 2026 float32 ABCD R V Range: VT Secondary – 1,000,000
HR 2028 uint16 R V Range: 100, 110, 115, 120
HR 2029 uint16 R Range: Depends on Power System
HR 2030 uint16 R A Range: 1 – 32,767
HR 2031 uint16 R A Range: 1 , 5
HR 2032 uint16 R A Range: 1 – 32,767
HR 2033 uint16 R A Range: 1, 5
HR 2034 uint16 R Range: 1 – 3. If 1 CT, value is meter terminal connected If 2 CT, value is meter terminal not connected 1 = Phase A, 2 = Phase B, 3 = Phase C
HR 2035 uint16 R Range: 1 – 3. Must match CT Location
HR 2036 uint16 R Range: 0 –4. 0 = Direct Connect 1 = Delta (2 VT) 2 = Wye (3 VT) 3 = L-N (1 VT) 4 = L-L (1 VT) 5 = L-L W/N (2 VT)
HR 2037 uint16 R Range: 0 – 1. 0 = Default Mapping; 1 = Remapping in Use
HR 2038 uint16 R Range: 10 – 31. Add 1 if reversed
HR 2039 uint16 R Range: 10 – 31. Add 1 if reversed
HR 2040 uint16 R Range: 10 – 31. Add 1 if reversed
HR 2041 uint16 R Range: 10 – 41. Add 1 if reversed
HR 2042 uint16 R Range: 10 – 41. Add 1 if reversed
HR 2043 uint16 R Range: 10 – 41. Add 1 if reversed
HR 2044 uint16 R Range: 10 – 41. Add 1 if reversed
HR 2045 uint16 R Range: 10 – 41. Add 1 if reversed
HR 2048 float32 ABCD R A Entered by the user for use in calculation of Total Demand Distortion. 0 = Calculation performed using peak demand of 3-phase average current
HR 2050 float32 ABCD R A Range: 0 – (10 * CT Ratio)
HR 2126 uint16 R Range: 0 – 2. 0 = Disable, 1 = Active Alarm (default), 2 = Energy
HR 2129 uint16 R mSec Range: 10, 25, 50, 100, 150, 200, 300, 500, 1000. Only on PM5580, PM5560, PM5563
HR 2130 uint16 R Range: 0 – 18 PM5350 / PM5500: 0 - 9
HR 2131 uint16 R Range: 0 – 99. 0 = No association 1 - 2 = Digital Output 99 = LED A digital output shall be permitted to be associated with only 1 energy value. If the Energy Channel is not 0, a valid digital output association must be made
HR 2132 float32 ABCD R FLOAT32 or INT32U, depending on the unit configured. Range: 1E-10 – 1E10. If the Energy Channel is not 0, a non-zero pulse weight must be entered. In PM5500 and PM5350 R2 it is an INT32U. The range is 1-9999999, the default value is 1, and the units are pulses / k_h
HR 2134 uint16 R Range: 0 – 18
HR 2135 uint16 R Range: 0 – 99
HR 2136 float32 ABCD R FLOAT32 or INT32U, depending on the unit configured. Range: 1E-10 – 1E10. If the Energy Channel is not 0, a non-zero pulse weight must be entered. In PM5500 and PM5350 R2 it is an INT32U. The range is 1-9999999, the default value is 1, and the units are pulses / k_h
HR 2138 uint16 R Range: 0 – 18
HR 2139 uint16 R Range: 0 – 99
HR 2140 float32 ABCD R FLOAT32 or INT32U, depending on the unit configured. Range: 1E-10 – 1E10. If the Energy Channel is not 0, a non-zero pulse weight must be entered. In PM5500 and PM5350 R2 it is an INT32U. The range is 1-9999999, the default value is 1, and the units are pulses / k_h
HR 2300 uint16 R Range: 0 - 6. 0 to 6 0= Auto, 1= Kilo, 2= Mega, 3= Giga, 4= Tera, 5=Peta, 6=Exa. Only on PM5561
HR 2400 uint16 R Bitmap. Range: 0x0000 – 0x000F
HR 2401 uint16 R Bitmap. Range: 0x0000 – 0x000F
HR 2402 uint16 R Bitmap. Range: 0x0000 – 0x000F
HR 2403 uint16 R Bitmap. Range: 0x0000 – 0x000F
HR 2420 uint16 R Bitmap. See PTI document for definition
HR 2421 uint16 R Bitmap. 0 = Not Detected; 1 = Detected
HR 2422 uint16 R Bitmap
HR 2423 uint16 R Bitmap
HR 2440 uint16 R Bitmap
HR 2441 uint16 R Bitmap
HR 2700 float32 ABCD R kWh
HR 2702 float32 ABCD R kWh
HR 2704 float32 ABCD R kWh
HR 2706 float32 ABCD R kWh
HR 2708 float32 ABCD R kvarh
HR 2710 float32 ABCD R kvarh
HR 2712 float32 ABCD R kvarh
HR 2714 float32 ABCD R kvarh