  • Official
  • 247 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
247 holding registers
Groups
8
Revision
3 · 2026-10-18
Added
()
File
maps/schneider-electric/pm700.mbmap.json · 66 KB · history
SHA-256
e5e3300b55634fd4e77d2e02abbacf298c10859f0fb50577ab6acd12adcbc495
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware Version, Operating System holding 7001 int16
Serial number Serial Number holding 7002 int32 ABCD
Model Device ID holding 7004 int16 15165 = PM700, PM700P, PM710, 15201 = PM200, PM200P, PM210, 15202 = PM750

Sources and notes

Source: Schneider Electric, Series 200 and 700 Power Meter (PM200, PM700, PM750) register list, firmware 3.050

  • Addresses are the register numbers of the register list (Modicon numbering, 1-based): the address on the wire is the register number minus 1.
  • The 4000 series holds integers scaled by the four scale factor registers (4105 to 4108): value = register x 10^scale factor, in the unit shown. The 1000 series holds the same values as floating-point numbers, already in engineering units.
  • Power factor registers 4009 and 4048: a negative signed value is reported as value + 32768 (see the register list).
  • The alarm configuration blocks (4140 and following, 16 registers per alarm position) are written with the command interface and are not in this map.
  • Registers that exist only on some of the models say so in their description.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1204 float32 ABCD R h This combination timer counts the total time for which the absolute current on at least one phase is > 0.1Amp. Only on PM700, PM700P, PM710, PM750
HR 1206 float32 ABCD R min This combination timer counts the total time for which the absolute current on at least one phase is > 0.1Amp. Only on PM700, PM700P, PM710, PM750
HR 4073 uint16 RW Counts the number of times the meter boots up. Only on PM750
HR 4105 int16 R
HR 4106 int16 R
HR 4107 int16 R
HR 4108 int16 R
HR 4110 int16 R h Only on PM700, PM700P, PM710, PM750
HR 4111 int16 R min Only on PM700, PM700P, PM710, PM750
HR 4112 int16 R
HR 4117 int16 RW min Current Demand Only
HR 4118 int16 RW min Duration in minutes
HR 4119 int16 RW s 0: Sliding Block Calculation If Reg[4118 <= 15 Minutes the Sub-interval is 15 Seconds if Reg[4118 > 15 Minutes the Sub-interval is 60 Seconds 1: Fixed Block Else: Rolling Block (Must be evenly divided into 4188 to the second)
HR 4120 int16 RW
HR 4121 int16 RW Range: 1 or 5
HR 4122 int16 RW
HR 4123 int16 RW Range: 0, 1, 10, 100
HR 4124 int16 RW Range: 100, 110, 115, 120
HR 4125 int16 RW Hz Range: 50 or 60
HR 4126 int16 W Write a reset command code (see the notes): 666 restart demand, 1115 reset meter, 3211 default alarms, 3320 de-energize output, 3321 energize output, 3361 reset output counter, 3365 reset input counters, 6209 preset energy from 4000-4005, 10001 clear usage timers, 14255 reset min/max, 21212 reset peak demand, 30078 clear energy
HR 4127 int16 RW System type code: 10, 11, 12, 30, 31, 32, 40, 42 or 44
HR 4128 int16 RW 0 = IEC Units 1 = IEEE Units. Range: 0,1
HR 1000 float32 ABCD R kWh
HR 1002 float32 ABCD R kVAh
HR 1004 float32 ABCD R kvarh
HR 1006 float32 ABCD R kW
HR 1008 float32 ABCD R kVA
HR 1010 float32 ABCD R kvar
HR 1012 float32 ABCD R
HR 1014 float32 ABCD R V Only on PM700, PM700P, PM710, PM750
HR 1016 float32 ABCD R V Only on PM700, PM700P, PM710, PM750
HR 1018 float32 ABCD R A Only on PM700, PM700P, PM710, PM750
HR 1020 float32 ABCD R Hz Derived from Phase A
HR 1034 float32 ABCD R A
HR 1036 float32 ABCD R A
HR 1038 float32 ABCD R A
HR 1040 float32 ABCD R A Only on PM700, PM700P, PM710, PM750
HR 1054 float32 ABCD R V
HR 1056 float32 ABCD R V
HR 1058 float32 ABCD R V
HR 1060 float32 ABCD R V
HR 1062 float32 ABCD R V
HR 1064 float32 ABCD R V
HR 1066 float32 ABCD R kW Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1068 float32 ABCD R kW Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1070 float32 ABCD R kW Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1072 float32 ABCD R kVA Only on PM700, PM700P, PM710, PM750
HR 1074 float32 ABCD R kVA Only on PM700, PM700P, PM710, PM750
HR 1076 float32 ABCD R kVA Only on PM700, PM700P, PM710, PM750
HR 1078 float32 ABCD R kvar Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1080 float32 ABCD R kvar Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1082 float32 ABCD R kvar Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 1084 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1086 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1088 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1092 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1094 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1096 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1098 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1100 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 1102 float32 ABCD R % Only on PM700, PM700P, PM710, PM750
HR 4000 int32 ABCD R kWh ×10^Scale factor E (energy) Signed in all PM2's, PM7s and PM750
HR 4002 int32 ABCD R kVAh ×10^Scale factor E (energy) Signed in all PM2's, PM7s and PM750
HR 4004 int32 ABCD R kvarh ×10^Scale factor E (energy) Signed in all PM2's, PM7s and PM750
HR 4006 int16 R kW ×10^Scale factor W (power)
HR 4007 int16 R kVA ×10^Scale factor W (power)
HR 4008 int16 R kvar ×10^Scale factor W (power) Signed in all PM2's, PM7s and PM750
HR 4009 int16 R ×0.0001
HR 4010 int16 R V ×10^Scale factor V (voltage) Only on PM700, PM700P, PM710, PM750
HR 4011 int16 R V ×10^Scale factor V (voltage) Only on PM700, PM700P, PM710, PM750
HR 4012 int16 R A ×10^Scale factor I (current) Only on PM700, PM700P, PM710, PM750
HR 4013 int16 R Hz ×0.01 Derived from Phase A
HR 4020 int16 R A ×10^Scale factor I (current)
HR 4021 int16 R A ×10^Scale factor I (current)
HR 4022 int16 R A ×10^Scale factor I (current)
HR 4023 int16 R A ×10^Scale factor I (current) Only on PM700, PM700P, PM710, PM750
HR 4030 int16 R V ×10^Scale factor V (voltage)
HR 4031 int16 R V ×10^Scale factor V (voltage)
HR 4032 int16 R V ×10^Scale factor V (voltage)
HR 4033 int16 R V ×10^Scale factor V (voltage)
HR 4034 int16 R V ×10^Scale factor V (voltage)
HR 4035 int16 R V ×10^Scale factor V (voltage)
HR 4036 int16 R kW ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4037 int16 R kW ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4038 int16 R kW ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4039 int16 R kVA ×10^Scale factor W (power) Only on PM700, PM700P, PM710, PM750
HR 4040 int16 R kVA ×10^Scale factor W (power) Only on PM700, PM700P, PM710, PM750
HR 4041 int16 R kVA ×10^Scale factor W (power) Only on PM700, PM700P, PM710, PM750
HR 4042 int16 R kvar ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4043 int16 R kvar ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4044 int16 R kvar ×10^Scale factor W (power) Signed in all PM7s and PM750. Only on PM700, PM700P, PM710, PM750
HR 4045 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4046 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4047 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4048 int16 R ×0.001 "-" sign indicates lag If a negative value is reported, add 32768 then divide by 1000 to find the lagging PF reported. Only on PM750
HR 4049 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4050 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4051 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4052 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750
HR 4053 int16 R % ×0.1 Only on PM700, PM700P, PM710, PM750

Help improve this map