Schneider Electric PowerLogic ION6200 Modbus register map

Panel-mount power and energy meter, Modbus RTU on RS-485

  • Official
  • 134 registers
  • Modbus RTU
  • Revision 3 · 2026-10-24
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
100
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
1-based · wire address = address − 1

Connection values are defaults: the device may be configured differently.

Map

Registers
134 holding registers
Groups
9
Revision
3 · 2026-10-24
Added
()
File
maps/schneider-electric/powerlogic-ion6200.mbmap.json · 26 KB · history
SHA-256
88043c1b2a5d5ceabda99f8e1ba90f11c0412ac93d08f28ea47cd027ce8634bf
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 1 uint32 CDAB
Firmware Firmware revision holding 3 uint16

Sources and notes

Source: PowerLogic ION6200 Serial Communications Protocol and ION / Modbus Register Map, 70022-0115, 04/2007

  • Function 03 reads and function 16 writes; the meter does not support function 06. Registers are numbered from 1 as in the document (40001 is address 1, sent as 0).
  • RTU only, 8 data bits, no parity, 1 stop bit. Factory defaults: 9600 bps, protocol Modbus, unit ID 100 plus the last two digits of the serial number (so the unit_id here is only a starting point).
  • Voltage, current and power use programmable scales (PVS, PCS, PnS, PPS, registers 44012-44015). The scales in this map are for the factory settings: voltage and current x10 (0.1 V, 0.1 A), power x1 (1 kW). Change the scale here if the meter is set otherwise.
  • On ION6200 Megawatt meters the same registers hold kV, MW, Mvar, MVA and MWh instead of V, kW, kvar, kVA and kWh.
  • 32-bit energy values at 40138-40188 send the low word first; the same values at 41138-41188 send the high word first.
  • Reserved registers read 0xFFFF. The control registers (42001-42005) need firmware 202 or later; the reset registers return an error when read.
  • Written from the manufacturer's register map; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 uint32 CDAB R YYMM##### (manufacture year and month, then a number)
HR 3 uint16 R
HR 4 uint16 R
HR 5 uint32 CDAB R Options code; see the ION6200 options card retrofit instructions
HR 7 uint16 R
HR 8 uint16 R
HR 9 uint32 CDAB R s
HR 11 uint32 CDAB R
HR 13 uint16 R
HR 15 uint16 R
HR 100 uint16 R V ×0.1 Scale for PVS = x10 (default); invalid in delta modes
HR 101 uint16 R V ×0.1 Scale for PVS = x10 (default); invalid in delta modes
HR 102 uint16 R V ×0.1 Scale for PVS = x10 (default); invalid in delta modes
HR 103 uint16 R V ×0.1 Scale for PVS = x10 (default); invalid in delta modes
HR 104 uint16 R V ×0.1 Scale for PVS = x10 (default)
HR 105 uint16 R V ×0.1 Scale for PVS = x10 (default)
HR 106 uint16 R V ×0.1 Scale for PVS = x10 (default)
HR 107 uint16 R V ×0.1 Scale for PVS = x10 (default)
HR 108 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 109 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 110 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 111 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 112 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 113 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 114 uint16 R A ×0.1 Scale for PnS = x10 (default)
HR 115 int16 R Hz ×0.01
HR 116 int16 R ×0.01 Signed
HR 117 int16 R ×0.01 Signed
HR 118 int16 R ×0.01 Signed
HR 119 int16 R ×0.01 Signed
HR 120 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 121 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 122 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 123 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 124 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 125 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 126 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 127 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 128 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 129 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 130 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 131 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 132 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 133 int16 R kW Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 134 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 135 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 136 int16 R kvar Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 137 int16 R kVA Scale for PPS = x1 (default); MW, Mvar, MVA on Megawatt meters
HR 138 uint32 CDAB R kWh Low word first; MWh, Mvarh, MVAh on Megawatt meters
HR 140 uint32 CDAB R kWh Low word first; MWh, Mvarh, MVAh on Megawatt meters
HR 142 uint32 CDAB R kvarh Low word first; MWh, Mvarh, MVAh on Megawatt meters
HR 144 uint32 CDAB R kvarh Low word first; MWh, Mvarh, MVAh on Megawatt meters
HR 146 uint32 CDAB R kVAh Low word first; MWh, Mvarh, MVAh on Megawatt meters
HR 148 uint16 R % ×0.1
HR 149 uint16 R % ×0.1
HR 150 uint16 R % ×0.1
HR 151 uint16 R % ×0.1
HR 152 uint16 R % ×0.1
HR 153 uint16 R % ×0.1
HR 154 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 155 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 156 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 157 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 158 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 159 uint16 R A ×0.1 Scale for PCS = x10 (default)
HR 160 uint32 CDAB R kWh Low word first
HR 162 uint32 CDAB R kWh Low word first
HR 164 uint32 CDAB R kWh Low word first
HR 166 uint32 CDAB R kWh Low word first
HR 168 uint32 CDAB R kWh Low word first
HR 170 uint32 CDAB R kWh Low word first
HR 172 uint32 CDAB R kvarh Low word first
HR 174 uint32 CDAB R kvarh Low word first
HR 176 uint32 CDAB R kvarh Low word first
HR 178 uint32 CDAB R kvarh Low word first
HR 180 uint32 CDAB R kvarh Low word first
HR 182 uint32 CDAB R kvarh Low word first
HR 184 uint32 CDAB R kVAh Low word first
HR 186 uint32 CDAB R kVAh Low word first
HR 188 uint32 CDAB R kVAh Low word first
HR 1138 uint32 ABCD R kWh
HR 1140 uint32 ABCD R kWh
HR 1142 uint32 ABCD R kvarh
HR 1144 uint32 ABCD R kvarh
HR 1146 uint32 ABCD R kVAh
HR 1160 uint32 ABCD R kWh
HR 1162 uint32 ABCD R kWh
HR 1164 uint32 ABCD R kWh
HR 1166 uint32 ABCD R kWh
HR 1168 uint32 ABCD R kWh
HR 1170 uint32 ABCD R kWh
HR 1172 uint32 ABCD R kvarh
HR 1174 uint32 ABCD R kvarh
HR 1176 uint32 ABCD R kvarh
HR 1178 uint32 ABCD R kvarh
HR 1180 uint32 ABCD R kvarh
HR 1182 uint32 ABCD R kvarh
HR 1184 uint32 ABCD R kVAh
HR 1186 uint32 ABCD R kVAh
HR 1188 uint32 ABCD R kVAh