Schneider Electric ION7300 series Modbus register map

Also covers ION7330, ION7350

Power and energy meter (default Modbus register map)

  • Official
  • 47 registers
  • Revision 3 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
47 holding registers
Groups
3
Revision
3 · 2026-10-18
Added
()
File
maps/schneider-electric/powerlogic-ion7300.mbmap.json · 11 KB · history
SHA-256
d3e148be71652e50815cf7a4b4361a09d43119c0fbc677daabf8e96ef1f3da0c
Manufacturer
se.com

Sources and notes

Source: Schneider Electric, Modbus protocol and register map for ION devices, 70022-0124-01 (08/2011), section Modbus register map ION7300 series

  • The register map of an ION meter has a part you configure (the Modbus Slave modules) and a fixed part. This map is the default Modbus Slave module map of the template revisions named by the manufacturer; if the meter has a custom framework, the registers can be elsewhere.
  • Addresses are the 4xxxx register numbers of the manual minus 40000, as sent on the wire (register 40011 is address 10). Values are read with FC03; FC16 writes the registers marked read/write.
  • 32-bit values have the high-order register first. A value shown with a scale is the register divided by the scaling of the module (11982 with scaling 10 is 1198.2). The units are inferred from the register labels.
  • Unmapped registers between blocks read as 0xFFFF.
  • Not in this map: the 32-bit modulus-10000 (M10K) energy registers, and the common Modbus registers for setup and control.
  • Default template revisions: This table outlines the default data registers available on the ION7300 series power meters. For further information on accessing configuration and control registers using the Modbus protocol, please see the ION7300 series Modicon Modbus Serial Communications Protocol document. This register map is applicable to the following template revisions:  7300_FAC-4WYE_V2.2.0.0.0  7330_FAC-4WYE_V2.3.0.1.1  7350_FAC-4WYE_V1
AreaAddressNameTypeAccessUnitScaleDescription
HR 11 uint16 R V ×0.1
HR 12 uint16 R V ×0.1
HR 13 uint16 R V ×0.1
HR 14 uint16 R V ×0.1
HR 15 uint16 R V ×0.1
HR 16 uint16 R V ×0.1
HR 17 uint16 R V ×0.1
HR 18 uint16 R V ×0.1
HR 19 uint16 R A ×0.1
HR 20 uint16 R A ×0.1
HR 21 uint16 R A ×0.1
HR 22 uint16 R A ×0.1
HR 23 uint16 R % ×0.1
HR 24 uint16 R % ×0.1
HR 25 uint16 R Hz ×0.1
HR 26 uint16 R ×0.1
HR 27 int32 ABCD R kW ×0.1
HR 29 int32 ABCD R kW ×0.1
HR 31 int32 ABCD R kW ×0.1
HR 33 int32 ABCD R kW ×0.1
HR 35 int32 ABCD R kvar ×0.1
HR 37 int32 ABCD R kvar ×0.1
HR 39 int32 ABCD R kvar ×0.1
HR 41 int32 ABCD R kvar ×0.1
HR 43 int32 ABCD R kVA ×0.1
HR 45 int32 ABCD R kVA ×0.1
HR 47 int32 ABCD R kVA ×0.1
HR 49 int32 ABCD R kVA ×0.1
HR 51 int32 ABCD R ×0.1
HR 53 int32 ABCD R ×0.1
HR 55 int32 ABCD R ×0.1
HR 57 int32 ABCD R ×0.1
HR 59 int32 ABCD R kW ×0.1
HR 61 int32 ABCD R kvar ×0.1
HR 63 int32 ABCD R kVA ×0.1
HR 65 int32 ABCD R kW ×0.1
HR 67 int32 ABCD R kvar ×0.1
HR 69 int32 ABCD R kVA ×0.1
HR 71 int32 ABCD R V ×0.1
HR 73 int32 ABCD R A ×0.1
HR 75 int32 ABCD R kW ×0.1
HR 77 int32 ABCD R kvar ×0.1
HR 79 int32 ABCD R kVA ×0.1
HR 81 int32 ABCD R Hz ×0.1
HR 83 int32 ABCD R V ×0.1
HR 85 int32 ABCD R A ×0.1
HR 87 int32 ABCD R Hz ×0.1