Schneider Electric Conext CL 18/20/25 kVA (PVSCL20E) Modbus register map

Also covers PVSCL25E, PVSCL18NA, PVSCL25NA, PVSCL20E100, PVSCL20E200, PVSCL20E201, PVSCL20E300, PVSCL20E301, PVSCL25E100, PVSCL25E200, PVSCL25E201, PVSCL25E300, PVSCL25E301, PVSCL18NA100, PVSCL18NA200, PVSCL18NA201, PVSCL18NA300, PVSCL18NA301, PVSCL25NA100, PVSCL25NA200, PVSCL25NA201, PVSCL25NA300, PVSCL25NA301

Conext CL three-phase PV inverter (18/20/25 kVA, E and NA models) with Modbus RTU and Modbus TCP: identity, energy, AC and PV measurements, temperatures, state and alarms, event log, active and reactive power control, relay and the SunSpec models

  • Official
  • 183 registers
  • Modbus TCP and RTU
  • Revision 3 · 2026-10-31
  • Identity: model, firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
10
TCP port
502
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
183 holding registers
Groups
13
Translation tables
2
Revision
3 · 2026-10-31
Added
()
File
maps/schneider-electric/pvscl20e.mbmap.json · 37 KB · history
SHA-256
6ba6dbf5dbfe850c0f3786c1fce048009c592b8640d184af043e762feb695b8d
Manufacturer
se.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 20 string[10]
Model Inverter model holding 40 string[10]
Firmware Software version, processor A holding 832 string[5]

Sources and notes

Source: Schneider Electric Modbus Registers Map - Conext CL Three Phase PV Inverter 20/25kVA, doc. 503-0243-01-01 rev. 1.5 (2016-03-15)

  • Covers the Conext CL-E (PVSCL20E, PVSCL25E) and CL-NA (PVSCL18NA, PVSCL25NA) inverters; the file keeps its old name.
  • Modbus RTU defaults: address 10, 9600 bit/s, no parity, 1 stop bit (parity and stop bits can also be even/odd and 2). Modbus TCP: port 502, unit ID 10.
  • Functions 03, 06, 16 and 43 (device identification). Addresses are 0-based (on the wire). Unused addresses read 0xFF without an exception.
  • 32-bit values are high word first. Strings are null-terminated ASCII; unused characters read 0xFF.
  • The reactive power control registers apply to the E (IEC) models only. Registers the map marks 'not available' (rated powers, LVRT, P(f), anti-islanding) are left out.
  • The SunSpec block starts at 40000 (0x9C40): common model 1, three-phase inverter model 103 and multiple MPPT model 160, ending at 0x9CEC.
  • The register map carries a confidentiality notice, but Schneider Electric publishes it on its solar website.
  • Written from the manufacturer's register map; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 string[9] R Inverter and BOS, e.g. PVSCL25E301E
HR 20 string[10] R
HR 40 string[10] R e.g. PVSCL25E
HR 50 string[10] R
HR 130 string[10] R
HR 352 string[10] R e.g. COMM
HR 512 string[7] R
HR 832 string[5] R Communication processor, e.g. 02.02
HR 150 string[10] R
HR 362 string[10] R e.g. DC-DC
HR 519 string[7] R
HR 837 string[5] R e.g. 02.02
HR 170 string[10] R
HR 372 string[10] R e.g. DC-AC
HR 526 string[7] R
HR 842 string[5] R e.g. 02.02
HR 2050 uint32 ABCD R kWh ×0.1 Since commissioning
HR 2052 uint32 ABCD R kWh ×0.1
HR 2054 uint32 ABCD R kWh ×0.1 Yesterday
HR 2056 uint32 ABCD R kWh ×0.1 2 days ago
HR 2058 uint32 ABCD R kWh ×0.1 3 days ago
HR 2060 uint32 ABCD R kWh ×0.1 4 days ago
HR 2062 uint32 ABCD R kWh ×0.1 5 days ago
HR 2064 uint32 ABCD R kWh ×0.1 6 days ago
HR 2078 uint32 ABCD R h Lifetime
HR 5888 uint16 R
HR 6184 uint16 R Highest-priority active alarm
HR 5889 int16 R °C ×0.1 Ambient
HR 5890 int16 R °C ×0.1
HR 5891 int16 R °C ×0.1
HR 5894 int16 R °C ×0.1
HR 5895 int16 R °C ×0.1
HR 5896 int16 R °C ×0.1
HR 5893 uint16 R A ×0.1
HR 5897 int16 R V ×0.1
HR 5898 int16 R V ×0.1
HR 5899 int16 R V ×0.1
HR 6136 int16 R V ×0.1
HR 6137 int16 R V ×0.1
HR 6138 int16 R V ×0.1
HR 6139 int16 R A ×0.1
HR 6140 int16 R A ×0.1
HR 6141 int16 R A ×0.1
HR 6142 int16 R kW ×0.1
HR 6129 uint16 R kVA ×0.1
HR 6132 int16 R kvar ×0.1
HR 6171 int16 R kW ×0.1
HR 6172 int16 R kW ×0.1
HR 6173 int16 R kW ×0.1
HR 6146 uint16 R Hz ×0.1
HR 6168 uint16 R Hz ×0.1
HR 6169 uint16 R Hz ×0.1
HR 6170 uint16 R Hz ×0.1
HR 6143 int16 R V ×0.1
HR 6144 int16 R A ×0.1
HR 6145 int16 R kW ×0.1
HR 6185 int16 R V ×0.1
HR 6186 int16 R A ×0.1
HR 6191 int16 R kW ×0.1
HR 6400 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6402 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6404 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6406 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6408 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6410 uint32 ABCD R Bit-mapped; Schneider Electric has the bit meanings
HR 6432 uint32 ABCD RW s UTC, seconds since 1970-01-01
HR 6434 uint16 R
HR 6435 uint32 ABCD R s UTC seconds
HR 6437 uint16 R
HR 6438 uint32 ABCD R s UTC seconds
HR 6440 uint16 R
HR 6441 uint32 ABCD R s UTC seconds
HR 6443 uint16 R
HR 6444 uint32 ABCD R s UTC seconds
HR 6446 uint16 R
HR 6447 uint32 ABCD R s UTC seconds
HR 6449 uint16 R
HR 6450 uint32 ABCD R s UTC seconds
HR 6452 uint16 R
HR 6453 uint32 ABCD R s UTC seconds
HR 6455 uint16 R
HR 6456 uint32 ABCD R s UTC seconds
HR 6458 uint16 R
HR 6459 uint32 ABCD R s UTC seconds
HR 6461 uint16 R
HR 6462 uint32 ABCD R s UTC seconds
HR 32771 uint16 RW Takes effect after a power cycle
HR 32784 uint16 RW May need a power cycle
HR 61438 uint16 RW A reset gets no response; reads 0 after a reboot
HR 64025 uint16 RW kW ×0.1 Default depends on the inverter rating
HR 64241 uint16 RW %
HR 64144 uint16 RW Local consumption disables the 10 min power ramp after a grid fault and the frequency derating
HR 64096 uint16 RW
HR 64097 int16 RW ×0.001 +800 to +1000 capacitive, -800 to -999 inductive; 1000 = unity
HR 64129 uint16 RW s
HR 64098 int16 RW ×0.0001 Capacitive, 8000 to 9999 (10000 = unity)
HR 64099 int16 RW ×0.0001 Inductive, 8000 to 9999
HR 64100 uint16 RW %
HR 64128 uint16 RW %
HR 64101 uint16 RW %