Schneider Electric Sepam 60 Modbus register map

Also covers Easergy Sepam series 60

Digital protection relay (Modbus RTU and Modbus TCP)

  • Official
  • 136 registers
  • Revision 3 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
136 holding registers
Groups
5
Revision
3 · 2026-10-18
Added
()
File
maps/schneider-electric/sepam-60.mbmap.json · 35 KB · history
SHA-256
a4665336cc004ff687e2ef8beab8d90d615b98d3d6ede9d3e6b7bc369a471bbd
Manufacturer
se.com

Sources and notes

Source: Easergy Sepam series 60, user's manual, SEPED310017EN, Modbus communication chapter

  • Addresses are the word addresses of the manual (hexadecimal), as sent on the wire. Values are read with FC03 or FC04.
  • 32-bit values have the most significant word first. 16-bit signed values are two's complement.
  • Text values (ASCII) have character n in the low byte and character n+1 in the high byte of each word.
  • Not in this map: the event tables, the settings and disturbance recording zones (indirect access), the bit-by-bit definitions of the status words, the remote control orders and the 16-bit compatibility zones kept for Sepam 2000.
AreaAddressNameTypeAccessUnitScaleDescription
HR 6 uint16 R 0x0100 for Schneider Electric Sepam
HR 7 uint16 R
HR 8 uint16 R Marking and equipment type; 0x1200 Sepam series 80, 0x1300 series 60
HR 387 string[3] R
HR 390 string[10] R
HR 400 string[10] R
HR 410 string[3] R
HR 413 string[10] R
HR 423 uint16 R
HR 424 uint16 R
HR 431 uint16 R Version number: major index in the high byte, minor index in the low byte
HR 432 uint16 R Version number: major index in the high byte, minor index in the low byte
HR 433 uint16 R Version number: major index in the high byte, minor index in the low byte
HR 434 uint16 R Version number: major index in the high byte, minor index in the low byte
HR 435 uint16 R Version number: major index in the high byte, minor index in the low byte
HR 436 string[3] R
HR 439 string[3] R
HR 442 string[3] R
HR 445 string[3] R
HR 512 uint32 ABCD R A ×0.1
HR 514 uint32 ABCD R A ×0.1
HR 516 uint32 ABCD R A ×0.1
HR 518 uint32 ABCD R A ×0.1
HR 520 uint32 ABCD R A ×0.1
HR 522 uint32 ABCD R A ×0.1
HR 524 uint32 ABCD R A ×0.1
HR 526 uint32 ABCD R A ×0.1
HR 528 uint32 ABCD R A ×0.1
HR 530 uint32 ABCD R A ×0.1
HR 532 uint32 ABCD R A ×0.1
HR 534 uint32 ABCD R V
HR 536 uint32 ABCD R V
HR 538 uint32 ABCD R V
HR 540 uint32 ABCD R V
HR 542 uint32 ABCD R V
HR 544 uint32 ABCD R V
HR 546 uint32 ABCD R V
HR 548 uint32 ABCD R V
HR 550 uint32 ABCD R V
HR 552 uint32 ABCD R Hz ×0.01 00007FFFh means out of range or not computable
HR 554 int32 ABCD R kW ×0.1 7FFFFFFFh means out of range or not computable
HR 556 int32 ABCD R kvar ×0.1 7FFFFFFFh means out of range or not computable
HR 558 int32 ABCD R kVA ×0.1 7FFFFFFFh means out of range or not computable
HR 560 int32 ABCD R ×0.01 00007FFFh means out of range or not computable
HR 562 int32 ABCD R kW ×0.1
HR 564 int32 ABCD R kvar ×0.1
HR 566 int32 ABCD R kW ×0.1 7FFFFFFFh means out of range or not computable
HR 568 int32 ABCD R kW ×0.1 7FFFFFFFh means out of range or not computable
HR 570 int32 ABCD R kW ×0.1 7FFFFFFFh means out of range or not computable
HR 572 int32 ABCD R kvar ×0.1 7FFFFFFFh means out of range or not computable
HR 574 int32 ABCD R kvar ×0.1 7FFFFFFFh means out of range or not computable
HR 576 int32 ABCD R kvar ×0.1 7FFFFFFFh means out of range or not computable
HR 578 int32 ABCD R kVA ×0.1 7FFFFFFFh means out of range or not computable
HR 580 int32 ABCD R kVA ×0.1 7FFFFFFFh means out of range or not computable
HR 582 int32 ABCD R kVA ×0.1 7FFFFFFFh means out of range or not computable
HR 584 uint32 ABCD R kWh ×100
HR 586 uint32 ABCD R kWh ×100
HR 588 uint32 ABCD R kvarh ×100
HR 590 uint32 ABCD R kvarh ×100
HR 592 uint32 ABCD R kWh ×100
HR 594 uint32 ABCD R kWh ×100
HR 596 uint32 ABCD R kvarh ×100
HR 598 uint32 ABCD R kvarh ×100
HR 600 uint32 ABCD R V
HR 616 uint32 ABCD R
HR 618 uint32 ABCD R A ×0.1
HR 620 uint32 ABCD R A ×0.1
HR 622 uint32 ABCD R A ×0.1
HR 636 uint32 ABCD R
HR 650 uint32 ABCD R mΩ 7FFFFFFFh means out of range or not computable
HR 652 uint32 ABCD R mΩ 7FFFFFFFh means out of range or not computable
HR 654 uint32 ABCD R mΩ 7FFFFFFFh means out of range or not computable
HR 656 uint32 ABCD R mΩ 7FFFFFFFh means out of range or not computable
HR 678 uint32 ABCD R ,1 % of 7FFFFFFFh means out of range or not computable
HR 680 uint32 ABCD R Hz ×0.001 00007FFFh means out of range or not computable
HR 682 uint32 ABCD R ° ×0.1 00007FFFh means out of range or not computable
HR 684 uint32 ABCD R µF ×0.1 7FFFFFFFh means out of range or not computable
HR 686 uint32 ABCD R µF ×0.1 7FFFFFFFh means out of range or not computable
HR 688 uint32 ABCD R µF ×0.1 7FFFFFFFh means out of range or not computable
HR 768 int16 R °C 7FFFh means out of range or not computable
HR 769 int16 R °C 7FFFh means out of range or not computable
HR 770 int16 R °C 7FFFh means out of range or not computable
HR 771 int16 R °C 7FFFh means out of range or not computable
HR 772 int16 R °C 7FFFh means out of range or not computable
HR 773 int16 R °C 7FFFh means out of range or not computable
HR 774 int16 R °C 7FFFh means out of range or not computable
HR 775 int16 R °C 7FFFh means out of range or not computable
HR 776 int16 R °C 7FFFh means out of range or not computable
HR 777 int16 R °C 7FFFh means out of range or not computable
HR 778 int16 R °C 7FFFh means out of range or not computable
HR 779 int16 R °C 7FFFh means out of range or not computable
HR 780 int16 R °C 7FFFh means out of range or not computable
HR 781 int16 R °C 7FFFh means out of range or not computable
HR 782 int16 R °C 7FFFh means out of range or not computable
HR 783 int16 R °C 7FFFh means out of range or not computable
HR 784 uint16 R % ×0.1
HR 785 uint16 R % ×0.1
HR 786 uint16 R ° 7FFFh means out of range or not computable
HR 788 uint16 R ° 7FFFh means out of range or not computable
HR 790 uint16 R ° 7FFFh means out of range or not computable