Siemens SEM3 Three Phase Modbus register map

SEM3 embedded micro metering module, three-pole monitors (Modbus RTU and TCP)

  • Official
  • 3,727 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
126
Serial
38400 8E1 · 38400 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
3727 holding registers
Groups
70
Revision
3 · 2026-10-18
Added
()
File
maps/siemens/sem3-three-phase.mbmap.json · 817 KB · history
SHA-256
53c6ce477b6325633a302f326a4c5f8439c189b094dbd855bb0eadae51e8682e
Manufacturer
siemens.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware version holding 20000 string[4]
Serial number Serial number holding 20004 string[16]

Sources and notes

Source: Siemens, "SEM3 Embedded Micro Metering Module User Manual", chapter Modbus Information

  • Addresses are the wire addresses: the manual's external addresses (40001 for the first register) minus 40001. The double precision energy registers are given by the manual with an internal address, which is used as it is.
  • Each monitor has its own block of registers: three-pole monitors start at a fixed base address plus the size of the block times the monitor number.
  • The mini-monitor registers (10 registers per monitor, from address 40301) hold up to 10 data points chosen in the web interface, so their content depends on the configuration and they are not in this map.
  • The manual does not state the order of the two registers of a 32-bit value or the byte order of floats; this map assumes the most significant register first.
  • Factory settings of the RS-485 port: address 126, 38400 baud, even parity.
  • The manual lists the monitor values in kilowatts, kilovolt-amperes and kilovolt-ampere-hours with a resolution of 0.001; the units shown are those names.
AreaAddressNameTypeAccessUnitScaleDescription
HR 19900 float32 ABCD R kWh
HR 19902 float32 ABCD R kvarh
HR 19904 uint32 ABCD R
HR 19906 uint32 ABCD R
HR 19908 uint16 R Set when any mini-monitor sets the same alarm bit; cleared with the global resets register
HR 20000 string[4] R
HR 20004 string[16] R
HR 20020 string[32] RW Free text; default spaces
HR 20052 uint16 RW Default 15
HR 20053 uint16 RW min Default 1
HR 20054 uint16 RW Type of transformer providing the voltage signal; default 0
HR 20055 uint16 RW V Line to neutral voltage; default 120
HR 20056 uint16 RW V Default 120
HR 20057 uint16 RW V Default 120
HR 20058 uint16 RW V 0 disables
HR 20059 uint16 RW s
HR 20060 uint16 RW V 0 disables
HR 20061 uint16 RW s
HR 20062 uint16 RW 0x0001 under voltage, 0x0002 over voltage; write 1 to a bit to clear the alarm
HR 20063 uint32 ABCD RW 0 disables; a write overwrites the local monitor settings
HR 20065 uint16 RW s
HR 20066 uint16 RW A write overwrites the local monitor settings
HR 20067 uint16 RW s
HR 20068 uint16 RW 0 disables
HR 20069 uint16 RW s
HR 20070 uint16 RW 0 disables
HR 20071 uint16 RW s
HR 20072 uint16 W Write 1 to a bit: 0x0001 new demand interval, 0x0002 reset all demands, 0x0004 reset maximum demand values, 0x0008 reset all energy values, 0x0010 reset maximum currents, 0x0020 reset maximum kW values, 0x0040 reset pulse input 1 count, 0x0080 reset pulse input 2 count, 0x0100 reset mini-monitor alarm flags
HR 20073 uint16 RW
HR 20074 uint16 RW
HR 20075 uint16 RW
HR 20076 uint16 RW
HR 20077 uint32 ABCD RW s Seconds since the UTC epoch
HR 20300 uint16 R One bit per monitor, bit 0 = monitor 1
HR 20301 uint16 R One bit per monitor, bit 0 = monitor 17
HR 20302 uint16 R One bit per monitor, bit 0 = monitor 33
HR 20303 uint16 R One bit per monitor, bit 0 = monitor 49
HR 20400 uint16 RW Default 126
HR 20401 uint16 RW Default 5 = 38400
HR 20402 uint16 RW Default 0 = even
HR 20403 uint16 RW s Default 30
HR 20404 uint16 RW
HR 20405 uint16 RW IPv4 or IPv6
HR 20406 uint16 RW IPv4: one octet per word
HR 20407 uint16 RW IPv4: one octet per word
HR 20408 uint16 RW IPv4: one octet per word
HR 20409 uint16 RW IPv4: one octet per word
HR 20410 uint16 RW IPv4: one octet per word
HR 20411 uint16 RW IPv4: one octet per word
HR 20412 uint16 RW IPv4: one octet per word
HR 20413 uint16 RW IPv4: one octet per word
HR 20414 uint16 RW IPv4: one octet per word
HR 20415 uint16 RW IPv4: one octet per word
HR 20416 uint16 RW IPv4: one octet per word
HR 20417 uint16 RW IPv4: one octet per word
HR 20418 uint16 RW IPv4: one octet per word
HR 20419 uint16 RW IPv4: one octet per word
HR 20420 uint16 RW IPv4: one octet per word
HR 20421 uint16 RW IPv4: one octet per word
HR 20422 uint16 RW IPv4: one octet per word
HR 20423 uint16 RW IPv4: one octet per word
HR 20424 uint16 RW IPv4: one octet per word
HR 20425 uint16 RW IPv4: one octet per word
HR 20426 uint16 RW IPv4: one octet per word
HR 20427 uint16 RW IPv4: one octet per word
HR 20428 uint16 RW IPv4: one octet per word
HR 20429 uint16 RW IPv4: one octet per word
HR 200 uint16 RW Write 1 to an alarm bit to clear it
HR 201 uint16 RW Write 1 to an alarm bit to clear it
HR 202 uint16 RW Write 1 to an alarm bit to clear it
HR 203 uint16 RW Write 1 to an alarm bit to clear it
HR 204 uint16 RW Write 1 to an alarm bit to clear it
HR 205 uint16 RW Write 1 to an alarm bit to clear it
HR 206 uint16 RW Write 1 to an alarm bit to clear it
HR 207 uint16 RW Write 1 to an alarm bit to clear it
HR 208 uint16 RW Write 1 to an alarm bit to clear it
HR 209 uint16 RW Write 1 to an alarm bit to clear it
HR 210 uint16 RW Write 1 to an alarm bit to clear it
HR 211 uint16 RW Write 1 to an alarm bit to clear it
HR 212 uint16 RW Write 1 to an alarm bit to clear it
HR 213 uint16 RW Write 1 to an alarm bit to clear it
HR 214 uint16 RW Write 1 to an alarm bit to clear it
HR 215 uint16 RW Write 1 to an alarm bit to clear it
HR 216 uint16 RW Write 1 to an alarm bit to clear it
HR 217 uint16 RW Write 1 to an alarm bit to clear it
HR 218 uint16 RW Write 1 to an alarm bit to clear it
HR 219 uint16 RW Write 1 to an alarm bit to clear it
HR 220 uint16 RW Write 1 to an alarm bit to clear it
HR 221 uint16 RW Write 1 to an alarm bit to clear it
HR 222 uint16 RW Write 1 to an alarm bit to clear it
HR 223 uint16 RW Write 1 to an alarm bit to clear it
HR 224 uint16 RW Write 1 to an alarm bit to clear it
HR 225 uint16 RW Write 1 to an alarm bit to clear it
HR 226 uint16 RW Write 1 to an alarm bit to clear it
HR 227 uint16 RW Write 1 to an alarm bit to clear it
HR 228 uint16 RW Write 1 to an alarm bit to clear it
HR 229 uint16 RW Write 1 to an alarm bit to clear it
HR 230 uint16 RW Write 1 to an alarm bit to clear it
HR 231 uint16 RW Write 1 to an alarm bit to clear it
HR 232 uint16 RW Write 1 to an alarm bit to clear it