MBMap Registry
  1. Devices
  2. Siemens
  3. Sentron PAC 2200

Siemens Sentron PAC 2200 Modbus register map

Also covers SENTRON PAC2200, PAC2200, 7KM2200

DIN-rail energy meter with RS-485 (Modbus RTU) or Ethernet (Modbus TCP)

  • Official
  • 248 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
126
Serial
19200 8N2 · 19200 baud, 8 data bits, none parity, 2 stop bits
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
248 holding registers
Groups
12
Revision
3 · 2026-10-18
Added
()
File
maps/siemens/sentron-pac-2200.mbmap.json · 60 KB · history
SHA-256
ec24daf083e9f3d8c859e834effbdc94848453a5dce27f6e55777406aaa9b631
Manufacturer
siemens.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 64012 string[8]
Firmware Firmware version major holding 64021 uint16 bits 0–7
Firmware Firmware version minor holding 64022 uint16 bits 8–15
Firmware Firmware version patch holding 64022 uint16 bits 0–7

Sources and notes

Source: Siemens, "PAC2200 measuring device manual", L1V30415167B-06 (12/2022), appendix A.1

  • Addresses are the Modbus offsets of the manual. Values are read with FC03 or FC04; settings are written with FC10 and commands with FC06.
  • Read every value from its first register with its full length: a read that starts or ends inside a multi-register value returns an error. The I&M data is read and written as a whole block (64001-64027 and 64028-64116).
  • Factory settings of the RS-485 versions: address 126, 19200 baud, 8N2. The Ethernet versions use Modbus TCP, port 502.
  • The 65 A devices have a fixed primary and secondary current; those two settings can be written on the 5 A devices only.
  • Not in this map: the status bits read with FC01/FC02, the 10 s and 15 min load profiles and the daily and monthly energy history read with FC20 (files 1, 2, 90 and 91), the user-defined FC100 and the Modbus device identification (FC43).
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 float32 ABCD R V
HR 3 float32 ABCD R V
HR 5 float32 ABCD R V
HR 7 float32 ABCD R V
HR 9 float32 ABCD R V
HR 11 float32 ABCD R V
HR 13 float32 ABCD R A
HR 15 float32 ABCD R A
HR 17 float32 ABCD R A
HR 19 float32 ABCD R VA
HR 21 float32 ABCD R VA
HR 23 float32 ABCD R VA
HR 25 float32 ABCD R W
HR 27 float32 ABCD R W
HR 29 float32 ABCD R W
HR 31 float32 ABCD R var
HR 33 float32 ABCD R var
HR 35 float32 ABCD R var
HR 37 float32 ABCD R
HR 39 float32 ABCD R
HR 41 float32 ABCD R
HR 55 float32 ABCD R Hz
HR 57 float32 ABCD R V
HR 59 float32 ABCD R V
HR 61 float32 ABCD R A
HR 63 float32 ABCD R VA
HR 65 float32 ABCD R W
HR 67 float32 ABCD R var
HR 69 float32 ABCD R
HR 71 float32 ABCD R A
HR 205 uint16 R Byte 0 and byte 1 of the status word (offset 205)
HR 206 uint16 R Byte 2 and byte 3 of the status word (offset 205). Byte 2 holds the stored diagnostics bits to acknowledge with offset 60007
HR 205 bool bit 8 R Bit of the device status word at offset 205
HR 205 bool bit 9 R Bit of the device status word at offset 205
HR 205 bool bit 10 R Bit of the device status word at offset 205
HR 205 bool bit 11 R Bit of the device status word at offset 205
HR 205 bool bit 13 R Bit of the device status word at offset 205
HR 205 bool bit 14 R Bit of the device status word at offset 205
HR 205 bool bit 15 R Bit of the device status word at offset 205
HR 205 bool bit 1 R Bit of the device status word at offset 205
HR 205 bool bit 6 R Bit of the device status word at offset 205
HR 205 bool bit 7 R Bit of the device status word at offset 205
HR 206 bool bit 8 R Bit of the device status word at offset 205
HR 206 bool bit 10 R Bit of the device status word at offset 205
HR 206 bool bit 11 R Bit of the device status word at offset 205
HR 206 bool bit 12 R Bit of the device status word at offset 205
HR 207 uint32 ABCD R Bit 0 = digital output 0
HR 209 uint32 ABCD R Bit 0 = digital input 0
HR 211 uint32 ABCD R
HR 215 uint32 ABCD RW
HR 217 uint32 ABCD R
HR 219 uint32 ABCD R
HR 231 float32 ABCD R kWh kWh or kvarh, depending on the configured counter source
HR 265 uint32 ABCD R
HR 267 uint32 ABCD R
HR 269 uint32 ABCD R
HR 501 float32 ABCD R W
HR 503 float32 ABCD R var
HR 505 float32 ABCD R W
HR 507 float32 ABCD R var
HR 509 float32 ABCD R W
HR 511 float32 ABCD R W
HR 513 float32 ABCD R var
HR 515 float32 ABCD R var
HR 517 uint32 ABCD R s
HR 519 uint32 ABCD R s
HR 545 uint32 ABCD R Unix time, UTC
HR 547 uint32 ABCD R
HR 549 float32 ABCD R Wh
HR 551 float32 ABCD R varh
HR 553 float32 ABCD R Wh
HR 555 float32 ABCD R varh
HR 557 uint32 ABCD R ms
HR 559 uint32 ABCD R
HR 561 float64 ABCD R Wh
HR 565 float64 ABCD R Wh
HR 569 float64 ABCD R varh
HR 573 float64 ABCD R varh
HR 577 float64 ABCD R Wh
HR 581 float64 ABCD R Wh
HR 585 float64 ABCD R varh
HR 589 float64 ABCD R varh
HR 593 float64 ABCD R Wh
HR 597 float64 ABCD R Wh
HR 799 uint32 ABCD RW Unix time, UTC
HR 801 float64 ABCD R Wh Overflows at 1.0e12
HR 805 float64 ABCD R Wh Overflows at 1.0e12
HR 809 float64 ABCD R Wh Overflows at 1.0e12
HR 813 float64 ABCD R Wh Overflows at 1.0e12
HR 817 float64 ABCD R varh Overflows at 1.0e12
HR 821 float64 ABCD R varh Overflows at 1.0e12
HR 825 float64 ABCD R varh Overflows at 1.0e12
HR 829 float64 ABCD R varh Overflows at 1.0e12
HR 833 float64 ABCD R VAh Overflows at 1.0e12
HR 837 float64 ABCD R VAh Overflows at 1.0e12
HR 841 float64 ABCD R Wh Overflows at 1.0e12
HR 845 float64 ABCD R Wh Overflows at 1.0e12
HR 849 float64 ABCD R Wh Overflows at 1.0e12
HR 853 float64 ABCD R Wh Overflows at 1.0e12
HR 857 float64 ABCD R varh Overflows at 1.0e12