Siemens Sentron PAC 4200 Modbus register map

Also covers SENTRON PAC4200, PAC4200, 7KM4211-1BA00-3AA0, 7KM4212-0BA00-3AA0

Power monitoring device for panel mounting with Ethernet (Modbus TCP); Modbus RTU through the PAC RS485 expansion module

  • Official
  • 267 registers
  • Modbus TCP and RTU
  • Revision 3 · 2026-11-10
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
267 holding registers
Groups
9
Revision
3 · 2026-11-10
Added
()
File
maps/siemens/sentron-pac-4200.mbmap.json · 44 KB · history
SHA-256
d0aebafeacd4ef7bbfdb0ff9ea47d4eb1518d5be845c9fc88a0e8e061f03078e
Manufacturer
siemens.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7 and 4.8).

From the device with FC43 Read Device Identification · answered by unit ID, not by a register address
RoleFieldWhere in the answerValues
— Manufacturer object 0 (VendorName)
— Manufacturer device name object 1 (ProductCode)
Firmware Firmware version / bootloader version object 2 (MajorMinorRevision)

Sources and notes

Source: Siemens, "SENTRON PAC4200 Power Monitoring Device, System Manual", A5E02316180B-03 (09/2010), appendix A.3

  • Addresses are the Modbus offsets of the manual. Values are read with FC03 or FC04; settings are written with FC10 and commands with FC06.
  • Read every value from its first register with its full length: a read that starts or ends inside a multi-register value returns an error.
  • Not in this map: load profile, maximum and minimum values with time stamps, harmonics, limit and I/O settings (50019 onwards) and the I&M data blocks.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1 float32 ABCD R V
HR 3 float32 ABCD R V
HR 5 float32 ABCD R V
HR 7 float32 ABCD R V
HR 9 float32 ABCD R V
HR 11 float32 ABCD R V
HR 13 float32 ABCD R A
HR 15 float32 ABCD R A
HR 17 float32 ABCD R A
HR 19 float32 ABCD R VA
HR 21 float32 ABCD R VA
HR 23 float32 ABCD R VA
HR 25 float32 ABCD R W
HR 27 float32 ABCD R W
HR 29 float32 ABCD R W
HR 31 float32 ABCD R var
HR 33 float32 ABCD R var
HR 35 float32 ABCD R var
HR 37 float32 ABCD R Range 0 ... 1
HR 39 float32 ABCD R Range 0 ... 1
HR 41 float32 ABCD R Range 0 ... 1
HR 43 float32 ABCD R % Range 0 ... 100
HR 45 float32 ABCD R % Range 0 ... 100
HR 47 float32 ABCD R % Range 0 ... 100
HR 55 float32 ABCD R Hz Range 45 ... 65
HR 57 float32 ABCD R V
HR 59 float32 ABCD R V
HR 61 float32 ABCD R A
HR 63 float32 ABCD R VA
HR 65 float32 ABCD R W
HR 67 float32 ABCD R var
HR 69 float32 ABCD R
HR 71 float32 ABCD R % Range 0 ... 100
HR 73 float32 ABCD R % Range 0 ... 100
HR 75 float32 ABCD R V
HR 77 float32 ABCD R V
HR 79 float32 ABCD R V
HR 81 float32 ABCD R V
HR 83 float32 ABCD R V
HR 85 float32 ABCD R V
HR 87 float32 ABCD R A
HR 89 float32 ABCD R A
HR 91 float32 ABCD R A
HR 93 float32 ABCD R VA
HR 95 float32 ABCD R VA
HR 97 float32 ABCD R VA
HR 99 float32 ABCD R W
HR 101 float32 ABCD R W
HR 103 float32 ABCD R W
HR 105 float32 ABCD R var
HR 107 float32 ABCD R var
HR 109 float32 ABCD R var
HR 111 float32 ABCD R Range 0 ... 1
HR 113 float32 ABCD R Range 0 ... 1
HR 115 float32 ABCD R Range 0 ... 1
HR 117 float32 ABCD R % Range 0 ... 100
HR 119 float32 ABCD R % Range 0 ... 100
HR 121 float32 ABCD R % Range 0 ... 100
HR 129 float32 ABCD R Hz Range 45 ... 65
HR 131 float32 ABCD R V
HR 133 float32 ABCD R V
HR 135 float32 ABCD R A
HR 137 float32 ABCD R VA
HR 139 float32 ABCD R W
HR 141 float32 ABCD R var
HR 143 float32 ABCD R
HR 145 float32 ABCD R V
HR 147 float32 ABCD R V
HR 149 float32 ABCD R V
HR 151 float32 ABCD R V
HR 153 float32 ABCD R V
HR 155 float32 ABCD R V
HR 157 float32 ABCD R A
HR 159 float32 ABCD R A
HR 161 float32 ABCD R A
HR 163 float32 ABCD R VA
HR 165 float32 ABCD R VA
HR 167 float32 ABCD R VA
HR 169 float32 ABCD R W
HR 171 float32 ABCD R W
HR 173 float32 ABCD R W
HR 175 float32 ABCD R var
HR 177 float32 ABCD R var
HR 179 float32 ABCD R var
HR 181 float32 ABCD R Range 0 ... 1
HR 183 float32 ABCD R Range 0 ... 1
HR 185 float32 ABCD R Range 0 ... 1
HR 187 float32 ABCD R Hz Range 45 ... 65
HR 189 float32 ABCD R V
HR 191 float32 ABCD R V
HR 193 float32 ABCD R A
HR 195 float32 ABCD R VA
HR 197 float32 ABCD R W
HR 199 float32 ABCD R var
HR 201 float32 ABCD R
HR 203 uint32 ABCD R
HR 205 uint32 ABCD R
HR 207 uint32 ABCD R
HR 209 uint32 ABCD R
HR 211 uint32 ABCD R