Siemens SINAMICS V20 Modbus register map

SINAMICS V20 compact drive (built-in RS485, Modbus RTU): control and status words, setpoints, diagnostics, faults and PID registers

  • Official
  • 127 registers
  • Modbus RTU
  • Revision 1 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
127 holding registers
Groups
11
Revision
1 · 2026-11-10
Added
()
File
maps/siemens/sinamics-v20.mbmap.json · 32 KB · history
SHA-256
502f3f17e516a0717cdf240a305ddf300f5994832e89dbbddace41519c22affa
Manufacturer
siemens.com

Sources and notes

Source: Siemens, "SINAMICS V20 Inverter Operating Instructions", 01/2018, A5E34559884-009, section 7.2 MODBUS communication, Mapping table; https://cache.industry.siemens.com/dl/files/193/109756193/att_942991/v1/V20_op_instr_0118_en-US.pdf

  • Set P0700 = 5 (USS/MODBUS on RS485), P2023 = 2 (Modbus) and power-cycle the inverter; P2021 sets the station address (1 to 247), P2010 the baud rate, P2034 the parity (default even) and P2035 the stop bits (default 1).
  • Addresses are the manual's register numbers: register 0 is 40001, so the map uses holding addresses 0-based. Only function codes 3, 6 and 16 are supported.
  • Two register blocks overlap in function. 40001-40062 is the older compatible block; 40100-40111 is the process-data block (control word, setpoint, status word, actual value) and 40200 onward is the parameter-data block.
  • Values with a scale factor in the manual are already multiplied by it on the wire (frequency 50.00 Hz reads 5000). Setpoint and actual-value percentages (40003, 40044) and the process-data words 40101 and 40111 are relative to the reference frequency P2000; for the process words 0x4000 = 100 %.
  • Registers 40014/40015 and 40200-40203 write BICO inputs: only 0 or 1 is accepted and it replaces the previous connection. Digital outputs 3-4 and digital inputs 5-6 exist only with the optional I/O Extension Module.
  • The manual lists no register with a fixed value, so the map has no reference values.
  • Written from the manufacturer's manual; not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint16 RW ms
HR 1 uint16 RW
HR 2 uint16 RW % ×0.01 Speed setpoint HSW as a percentage of the reference frequency (P2000); 0.00 to 100.00.
HR 3 uint16 RW Control word bit 3 (STW:3).
HR 4 uint16 RW Control word bit 11 (STW:11): 0 = forward, 1 = reverse.
HR 5 uint16 RW Control word bit 0 (STW:0): 1 = start.
HR 6 uint16 RW Control word bit 7 (STW:7).
HR 7 int16 RW % ×0.01
HR 8 uint16 RW Reads r0055.8; writing sets P2200 statically to 0 or 1 (BICO).
HR 9 uint16 RW % ×0.1
HR 10 uint16 RW s ×0.01
HR 11 uint16 RW s ×0.01
HR 13 uint16 RW Reads r0747.0; writing sets P0731 statically to 0 or 1 (BICO). HIGH = 1, LOW = 0.
HR 14 uint16 RW Reads r0747.1; writing sets P0732 statically to 0 or 1 (BICO). HIGH = 1, LOW = 0.
HR 15 uint16 RW Hz ×0.01
HR 16 int16 RW % ×0.01
HR 17 int16 RW % ×0.01
HR 18 uint16 RW ×0.001
HR 19 uint16 RW s
HR 20 uint16 RW
HR 21 uint16 RW % ×0.01
HR 22 uint16 RW ×0.01
HR 23 int16 R Hz ×0.01 r0024.
HR 24 int16 R RPM r0022.
HR 25 uint16 R A ×0.01 r0027.
HR 26 int16 R Nm ×0.01 r0031.
HR 27 uint16 R kW ×0.01 r0032.
HR 28 uint16 R kWh r0039.
HR 29 uint16 R V r0026.
HR 30 int16 R Hz ×0.01 r0020.
HR 31 uint16 R kW ×0.01 r0206.
HR 32 uint16 R V r0025.
HR 33 uint16 R Status word bit 14 (ZSW:14): FWD / REV.
HR 34 uint16 R Status word bit 2 (ZSW:2): STOP / RUN.
HR 35 uint16 R Status word bit 10 (ZSW:10): MAX / NO.
HR 36 uint16 R Status word bit 9 (ZSW:9): SERIAL / LOCAL.
HR 37 uint16 R Status word bit 0 (ZSW:0): ON / OFF.
HR 38 uint16 R Status word bit 1 (ZSW:1): READY / OFF.
HR 39 int16 R % ×0.01 r0754[0].
HR 40 int16 R % ×0.01 r0754[1].
HR 41 int16 R % ×0.01 r0774[0].
HR 43 int16 R % ×0.01 Actual speed HIW as a percentage of the reference frequency.
HR 44 int16 R % ×0.01 r2250.
HR 45 int16 R % ×0.01 r2294.
HR 46 int16 R % ×0.01 r2266.
HR 47 uint16 R r0722.0. HIGH = 1, LOW = 0.
HR 48 uint16 R r0722.1. HIGH = 1, LOW = 0.
HR 49 uint16 R r0722.2. HIGH = 1, LOW = 0.
HR 50 uint16 R r0722.3. HIGH = 1, LOW = 0.
HR 53 uint16 R Status word bit 3 (ZSW:3): FAULT / OFF.
HR 54 uint16 R r0947[0].
HR 55 uint16 R r0947[1].
HR 56 uint16 R r0947[2].
HR 57 uint16 R r0947[3].
HR 58 uint16 R Status word bit 7 (ZSW:7): WARN / OK.
HR 59 uint16 R r2110.
HR 60 uint16 R ×0.01 r0018 (firmware version).
HR 61 uint16 R r0201 (power unit code number).
HR 99 uint16 RW Process data 1 (PZD 1), written to the control word STW. Start = 0x047F, stop (OFF1) = 0x047E, fault acknowledge = 0x04FE then 0x047E, reverse start = 0x0C7F.
HR 100 uint16 RW Process data 2 (PZD 2): main setpoint HSW, 0x4000 (16384) = 100 % of the reference frequency (P2000).
HR 109 uint16 R Process data 1 (PZD 1): status word ZSW.
HR 110 uint16 R Process data 2 (PZD 2): main actual value HIW, 0x4000 (16384) = 100 % of the reference frequency (P2000).
HR 199 uint16 RW Reads r0747.0; writing sets P0731 statically to 0 or 1 (BICO). HIGH = 1, LOW = 0.
HR 200 uint16 RW Reads r0747.1; writing sets P0732 statically to 0 or 1 (BICO). HIGH = 1, LOW = 0.
HR 201 uint16 RW Only with the optional I/O Extension Module. Reads r0747.2; writing sets P0733 (BICO). HIGH = 1, LOW = 0.
HR 202 uint16 RW Only with the optional I/O Extension Module. Reads r0747.3; writing sets P0734 (BICO). HIGH = 1, LOW = 0.
HR 219 int16 R % ×0.01 r0774[0].
HR 239 uint16 R r0722.0. HIGH = 1, LOW = 0.
HR 240 uint16 R r0722.1. HIGH = 1, LOW = 0.
HR 241 uint16 R r0722.2. HIGH = 1, LOW = 0.
HR 242 uint16 R r0722.3. HIGH = 1, LOW = 0.
HR 243 uint16 R Only with the optional I/O Extension Module. r0722.4. HIGH = 1, LOW = 0.
HR 244 uint16 R Only with the optional I/O Extension Module. r0722.5. HIGH = 1, LOW = 0.
HR 259 int16 R % ×0.01 r0754[0].
HR 260 int16 R % ×0.01 r0754[1].
HR 299 uint16 R r0201 (power unit code number).
HR 300 uint16 R ×0.01 r0018 (firmware version).
HR 319 uint16 R kW ×0.01 r0206.
HR 320 uint16 RW % ×0.1
HR 321 uint16 RW s ×0.01
HR 322 uint16 RW s ×0.01
HR 323 uint16 RW Hz ×0.01
HR 324 int16 RW Hz ×0.01 P1001.
HR 325 int16 RW Hz ×0.01 P1002.
HR 326 int16 RW Hz ×0.01 P1003.
HR 327 int16 RW Hz ×0.01 P1004.
HR 329 int16 RW % ×0.01 P2889.
HR 330 int16 RW % ×0.01 P2890.
HR 339 int16 R Hz ×0.01 r0020.
HR 340 int16 R RPM r0022.
HR 341 int16 R Hz ×0.01 r0024.
HR 342 uint16 R V r0025.
HR 343 uint16 R V r0026.
HR 344 uint16 R A ×0.01 r0027.
HR 345 int16 R Nm ×0.01 r0031.
HR 346 uint16 R kW ×0.01 r0032.
HR 347 uint16 R kWh r0039.
HR 348 uint16 R r0807: HAND / AUTO.
HR 349 uint16 R A ×0.01 r0068.
HR 399 uint16 R r0947[0].