MBMap Registry
  1. Devices
  2. Socomec
  3. Countis E14

Socomec Countis E14 Modbus register map

  • Official
  • 127 registers
  • Revision 3 · 2026-11-10
  • Identity: firmware

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
127 holding registers
Groups
6
Revision
3 · 2026-11-10
Added
()
File
maps/socomec/countis-e14.mbmap.json · 23 KB · history
SHA-256
5d5868a05b9ed9b8e91194bf751e2584f9cd981ec247efec05ffc11596d75cdb
Manufacturer
socomec.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Software version holding 50007 uint16

Sources and notes

  • Single-phase meter: only phase 1 voltage, current and power are listed.
  • Addresses are the decimal addresses printed in the table, sent as written (address_base 0). Registers are read as holding registers.
  • Scales follow the table's unit column (for example V/100 becomes a scale of 0.01); energy counters are in kWh, kvarh and kVAh, or in 10 Wh steps in the second set.
  • The table gives neither function codes nor byte or word order: big-endian with the high word first is assumed (Socomec convention). Not tested on a device.
  • Values the table types as 8-bit sit in one 16-bit register and are read as uint16. Date and time, 64-bit, record and command registers (resets, tariff selection) are not mapped.
AreaAddressNameTypeAccessUnitScaleDescription
HR 50000 string[4] R
HR 50004 uint16 R
HR 50005 uint16 R
HR 50006 uint16 R ×0.01
HR 50007 uint16 R ×0.01
HR 50018 uint16 R
HR 50019 uint16 R
HR 50030 string[4] R
HR 50042 string[8] R
HR 50050 string[8] R
HR 50058 string[8] R
HR 57344 uint16 RW
HR 57345 uint16 RW
HR 57346 uint16 RW
HR 57347 uint16 RW
HR 50520 uint32 ABCD R V ×0.01
HR 50526 uint32 ABCD R Hz ×0.001
HR 50528 uint32 ABCD R A ×0.001
HR 50536 int32 ABCD R W ×10
HR 50538 int32 ABCD R var ×10
HR 50540 uint32 ABCD R VA ×10
HR 50542 int32 ABCD R ×0.001
HR 50544 int32 ABCD R W ×10
HR 50550 int32 ABCD R var ×10
HR 50556 uint32 ABCD R VA ×10
HR 50562 int32 ABCD R ×0.001
HR 51284 uint16 R V ×0.01 Reading before the transformer ratio is applied.
HR 51287 uint16 R Hz ×0.001 Reading before the transformer ratio is applied.
HR 51295 int16 R ×0.001 Reading before the transformer ratio is applied.
HR 51305 int16 R ×0.001 Reading before the transformer ratio is applied.
HR 51311 uint16 R MWh
HR 51312 uint16 R Mvarh
HR 51313 uint16 R MWh
HR 51314 uint16 R Mvarh
HR 50770 uint32 ABCD R kWh
HR 50772 uint32 ABCD R kvarh
HR 50774 uint32 ABCD R kVAh
HR 50776 uint32 ABCD R kWh
HR 50778 uint32 ABCD R kvarh
HR 50780 uint32 ABCD R kWh
HR 50782 uint32 ABCD R kvarh
HR 50784 uint32 ABCD R kVAh
HR 50786 uint32 ABCD R kWh
HR 50788 uint32 ABCD R kvarh
HR 50946 uint32 ABCD R Wh ×10
HR 50948 uint32 ABCD R varh ×10
HR 50952 uint32 ABCD R Wh ×10
HR 50954 uint32 ABCD R varh ×10
HR 50956 uint32 ABCD R Wh ×10
HR 50958 uint32 ABCD R varh ×10
HR 50962 uint32 ABCD R Wh ×10
HR 50964 uint32 ABCD R varh ×10
HR 50849 uint16 R
HR 50850 uint32 ABCD R kWh
HR 50852 uint32 ABCD R kWh
HR 50866 uint32 ABCD R kvarh
HR 50868 uint32 ABCD R kvarh
HR 50882 uint32 ABCD R h ×0.01
HR 50884 uint32 ABCD R h ×0.01
HR 51201 uint16 R
HR 51202 uint32 ABCD R Wh ×10
HR 51204 uint32 ABCD R Wh ×10
HR 51218 uint32 ABCD R varh ×10
HR 51220 uint32 ABCD R varh ×10
HR 51234 uint32 ABCD R h ×0.01
HR 51236 uint32 ABCD R h ×0.01
HR 25987 uint32 ABCD R kWh
HR 25989 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 25990 uint32 ABCD R kWh
HR 25992 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 25993 uint32 ABCD R kvarh
HR 25995 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 25996 uint32 ABCD R kvarh
HR 25998 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 25999 uint32 ABCD R kVAh
HR 26001 uint16 R VAh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 26002 uint32 ABCD R kvarh
HR 26004 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 26005 uint32 ABCD R kvarh
HR 26007 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 26008 uint32 ABCD R kvarh
HR 26010 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 26011 uint32 ABCD R kvarh
HR 26013 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 32768 uint32 ABCD R kWh
HR 32770 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 32771 uint32 ABCD R kWh
HR 32773 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 32792 uint32 ABCD R kWh
HR 32794 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 32795 uint32 ABCD R kWh
HR 32797 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 33024 uint32 ABCD R kWh
HR 33026 uint16 R Wh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 33027 uint32 ABCD R kvarh
HR 33029 uint16 R varh ×0.1 Remainder below the main counter step, to add to the counter above.
HR 26368 uint16 R
HR 26369 uint32 ABCD R kWh
HR 26371 uint32 ABCD R kWh
HR 26385 uint32 ABCD R kWh

Help improve this map