Socomec COUNTIS E24 Modbus register map
Three-phase direct-connection (80 A) MID energy meter with Modbus RS485 (ref. 4850 3051)
- Official
- 71 registers
- Modbus RTU
- Revision 3 · 2026-11-10
- Identity: firmware
Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus RTU
- Unit ID
- 1
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
- Max read
- 125 registers per request
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 71 holding registers
- Groups
- 10
- Revision
- 3 · 2026-11-10
- Added
- ()
- File
- maps/socomec/countis-e24.mbmap.json · 13 KB · history
- SHA-256
- 9ad8e42cee96aa97625332c2bb39818f7cab18c355d075101b111938e465b937
- Manufacturer
- socomec.com
Device identity
What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.
| Role | Register | Address | Type | Values |
|---|---|---|---|---|
| Firmware | Software version | holding 50007 | uint16 |
Sources and notes
- MODBUS tables of Countis_E24 · version V103.8, 2017-08 apac.socomec.com communication table (archived 2024-04-23); instruction manual 545 877 A
Source: Socomec, "MODBUS tables of Countis_E24", V103.8 (2017-08), apac.socomec.com communication table (archived 2024-04-23); instruction manual 545 877 A
- Socomec COUNTIS E24 (MID) three-phase direct 80 A energy meter with Modbus RTU over RS485.
- The COUNTIS E23 (non-MID, ref. 4850 3050) shares the manual but has its own communication table, not checked here.
- Addresses are the decimal addresses from Socomec's table, sent as-is. FC03 reads up to 128 words, FC06/FC16 write.
- Values read 0xFFFF... when not available. The factory RS485 settings are not given in text form; check SETUP 2 on the display.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 50004 | uint16 | R | 100 = Countis | |||
| HR | 50005 | uint16 | R | ||||
| HR | 50006 | uint16 | R | e.g. 101 = 1.01 | |||
| HR | 50007 | uint16 | R | ×0.01 | e.g. 100 = 1.00 | ||
| HR | 50042 | string[8] | R | ||||
| HR | 50050 | string[8] | R | ||||
| HR | 40545 | uint16 | R | ||||
| HR | 57344 | uint16 | RW | 1-247 | |||
| HR | 57345 | uint16 | RW | ||||
| HR | 57346 | uint16 | RW | ||||
| HR | 57347 | uint16 | RW | ||||
| HR | 50514 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50516 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50518 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50520 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50522 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50524 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50526 | uint32 ABCD | R | Hz | ×0.001 | ||
| HR | 50528 | uint32 ABCD | R | A | ×0.001 | ||
| HR | 50530 | uint32 ABCD | R | A | ×0.001 | ||
| HR | 50532 | uint32 ABCD | R | A | ×0.001 | ||
| HR | 50534 | uint32 ABCD | R | A | ×0.001 | ||
| HR | 50536 | int32 ABCD | R | W | ×10 | Signed; 10 W resolution | |
| HR | 50538 | int32 ABCD | R | var | ×10 | ||
| HR | 50540 | uint32 ABCD | R | VA | ×10 | ||
| HR | 50542 | int32 ABCD | R | ×0.001 | Negative = leading, positive = lagging | ||
| HR | 50544 | int32 ABCD | R | W | ×10 | ||
| HR | 50546 | int32 ABCD | R | W | ×10 | ||
| HR | 50548 | int32 ABCD | R | W | ×10 | ||
| HR | 50550 | int32 ABCD | R | var | ×10 | ||
| HR | 50552 | int32 ABCD | R | var | ×10 | ||
| HR | 50554 | int32 ABCD | R | var | ×10 | ||
| HR | 50556 | uint32 ABCD | R | VA | ×10 | ||
| HR | 50558 | uint32 ABCD | R | VA | ×10 | ||
| HR | 50560 | uint32 ABCD | R | VA | ×10 | ||
| HR | 50562 | int32 ABCD | R | ×0.001 | Negative = leading, positive = lagging | ||
| HR | 50564 | int32 ABCD | R | ×0.001 | Negative = leading, positive = lagging | ||
| HR | 50566 | int32 ABCD | R | ×0.001 | Negative = leading, positive = lagging | ||
| HR | 50568 | uint32 ABCD | R | A | ×0.001 | ||
| HR | 50570 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 50572 | uint32 ABCD | R | V | ×0.01 | ||
| HR | 51315 | uint16 | R | ||||
| HR | 50770 | uint32 ABCD | R | kWh | Whole units; totals cannot be reset | ||
| HR | 50772 | uint32 ABCD | R | kvarh | Whole units; totals cannot be reset | ||
| HR | 50774 | uint32 ABCD | R | kVAh | Whole units; totals cannot be reset | ||
| HR | 50776 | uint32 ABCD | R | kWh | Whole units; totals cannot be reset | ||
| HR | 50778 | uint32 ABCD | R | kvarh | Whole units; totals cannot be reset | ||
| HR | 50780 | uint32 ABCD | R | kWh | Whole units | ||
| HR | 50782 | uint32 ABCD | R | kvarh | Whole units | ||
| HR | 50784 | uint32 ABCD | R | kVAh | Whole units | ||
| HR | 50786 | uint32 ABCD | R | kWh | Whole units | ||
| HR | 50788 | uint32 ABCD | R | kvarh | Whole units | ||
| HR | 50946 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 50948 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 50950 | uint32 ABCD | R | kVAh | ×0.01 | ||
| HR | 50952 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 50954 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 50956 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 50958 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 50960 | uint32 ABCD | R | kVAh | ×0.01 | ||
| HR | 50962 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 50964 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 50849 | uint16 | R | ||||
| HR | 51202 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 51204 | uint32 ABCD | R | kWh | ×0.01 | ||
| HR | 51218 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 51220 | uint32 ABCD | R | kvarh | ×0.01 | ||
| HR | 51234 | uint32 ABCD | R | h | ×0.01 | ||
| HR | 51236 | uint32 ABCD | R | h | ×0.01 | ||
| HR | 40481 | uint16 | W | Broadcast allowed | |||
| HR | 40512 | uint16 | W |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).