Socomec Countis E63 Modbus register map
- Unofficial
- 50 registers
- Revision 2
Unofficial: Copied from an unofficial source and not tested. Read it as a draft and check a value on the real device before you rely on the rest. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.
Communication
- Protocol
- Modbus TCP and RTUdefault
- Unit ID
- 1default
- TCP port
- 502default
- Serial
- 9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
- Byte / word order
- ABCD · bytes big-endian, words high first
- Addresses
- 0-based
Connection values are defaults: the device may be configured differently.
Map
- Registers
- 50 holding registers
- Revision
- 2
- Added
- ()
- File
- maps/socomec/countis-e63.mbmap.json · 7 KB · history
- SHA-256
- d7952fa5cc2a845514eef35480d33c19c01d9f9924b90067917fb0614b588173
- Manufacturer
- socomec.com
Sources and notes
Source: Modbus Database (Jibril Sharafi, MIT licence), table socomec/countis-e63; https://www.aggsoft.com/serial-data-logger/tutorials/modbus-data-logging/socomec-countis-e63.htm. Not verified against the manufacturer's documentation
- Socomec Countis E63.
- Converted automatically from the Modbus Database (MIT licence, Jibril Sharafi).
- Not verified against the manufacturer's documentation. The byte order is a guess: the source does not give one.
- Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.
| Area | Address | Name | Type | Access | Unit | Scale | Description |
|---|---|---|---|---|---|---|---|
| HR | 38912 | uint16 | R | ||||
| HR | 38913 | uint16 | R | ||||
| HR | 38914 | uint16 | R | ||||
| HR | 38915 | uint16 | R | ||||
| HR | 38919 | string[4] | R | ||||
| HR | 50000 | string[4] | R | ||||
| HR | 50004 | uint16 | R | ||||
| HR | 50005 | uint16 | R | ||||
| HR | 50007 | uint16 | R | ||||
| HR | 50018 | uint16 | R | ||||
| HR | 50019 | uint16 | R | ||||
| HR | 50020 | uint16 | R | ||||
| HR | 50021 | uint16 | R | ||||
| HR | 50025 | uint16 | R | ||||
| HR | 50026 | uint16 | R | ||||
| HR | 50027 | uint16 | R | ||||
| HR | 50028 | uint16 | R | ||||
| HR | 50029 | uint16 | R | ||||
| HR | 50030 | string[4] | R | ||||
| HR | 50034 | string[4] | R | ||||
| HR | 50038 | string[4] | R | ||||
| HR | 50042 | string[8] | R | ||||
| HR | 50050 | string[8] | R | ||||
| HR | 50058 | string[8] | R | ||||
| HR | 50514 | uint32 ABCD | R | ||||
| HR | 50516 | uint32 ABCD | R | ||||
| HR | 50518 | uint32 ABCD | R | ||||
| HR | 50520 | uint32 ABCD | R | ||||
| HR | 50522 | uint32 ABCD | R | ||||
| HR | 50524 | uint32 ABCD | R | ||||
| HR | 50526 | uint32 ABCD | R | ||||
| HR | 50528 | uint32 ABCD | R | ||||
| HR | 50530 | uint32 ABCD | R | ||||
| HR | 50532 | uint32 ABCD | R | ||||
| HR | 50536 | int32 ABCD | R | ||||
| HR | 50540 | uint32 ABCD | R | ||||
| HR | 50542 | int32 ABCD | R | ||||
| HR | 50544 | int32 ABCD | R | ||||
| HR | 50546 | int32 ABCD | R | ||||
| HR | 50548 | int32 ABCD | R | ||||
| HR | 50556 | uint32 ABCD | R | ||||
| HR | 50558 | uint32 ABCD | R | ||||
| HR | 50560 | uint32 ABCD | R | ||||
| HR | 50562 | int32 ABCD | R | ||||
| HR | 50564 | int32 ABCD | R | ||||
| HR | 50770 | uint32 ABCD | R | ||||
| HR | 50780 | uint32 ABCD | R | ||||
| HR | 57346 | uint16 | R | ||||
| HR | 57355 | uint16 | R | ||||
| HR | 57602 | uint16 | R |
No registers match
Try part of the name, an address (decimal or 0x hex) or clear the filters.
Help improve this map
- I tested it on a deviceReport whether it worked, even if you did not write the map.
- Suggest a correctionEdit the file on GitHub; it opens a pull request.
- Report a problemA wrong address, type, scale or byte order.
- Read the formatWhat each key of the file means (SPEC.md).