Unipi Technology Patron S107 / S117 Modbus register map

Also covers Patron S117

Modbus TCP PLC unit with 4 digital inputs, 4 digital outputs, 1 analog output and 1 analog input

  • Official
  • 96 registers
  • Modbus TCP
  • Revision 3 · 2026-11-10
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
0
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
80 holding registers, 16 coils
Groups
14
Translation tables
2
Revision
3 · 2026-11-10
Added
()
File
maps/unipi/patron-s107-s117.mbmap.json · 21 KB · history
SHA-256
b659e6acc23178330d56d84f6cb8b1237455de1b75af19c238b04188fb26d823
Manufacturer
www.unipi.technology

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware Version holding 1000 uint16
Serial number PCB Serial Number holding 1005 uint32 ABCD

Sources and notes

Source: Patron S107 Modbus map v2.0, Unipi technology; Patron S117 Modbus map v2.0, Unipi technology, Unipi knowledge base page https://kb.unipi.technology/en:hw:04-extensions:downloads

  • Registers are 0-based and use the Unit 0 addresses of the document, which cover every section of the device. Multi-register values (32-bit counters, serial number, floats) are read here with the most significant register first, as the document states.
  • Reserved, obsolete and internal registers, and registers reachable only through a section unit (Unit 1 to 3), are left out.
  • The documents of S107, S117 list identical registers, so they share this map.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 bool bit 0 R
HR 0 bool bit 1 R
HR 0 bool bit 2 R
HR 0 bool bit 3 R
HR 1 bool bit 0 RW
HR 1 bool bit 1 RW
HR 1 bool bit 2 RW
HR 1 bool bit 3 RW
HR 5 uint16 R Reference voltage of the MCU (raw)
HR 6 bool bit 0 RW
HR 6 bool bit 1 RW
HR 8 uint32 ABCD RW Pulse counter; writable to reset
HR 10 uint32 ABCD RW Pulse counter; writable to reset
HR 12 uint32 ABCD RW Pulse counter; writable to reset
HR 14 uint32 ABCD RW Pulse counter; writable to reset
HR 16 uint16 RW PWM duty cycle of the digital output
HR 17 uint16 RW PWM duty cycle of the digital output
HR 18 uint16 RW PWM duty cycle of the digital output
HR 19 uint16 RW PWM duty cycle of the digital output
HR 20 bool bit 0 RW
HR 20 bool bit 1 RW
HR 20 bool bit 2 RW
HR 20 bool bit 3 RW
HR 21 bool bit 0 RW
HR 21 bool bit 1 RW
HR 21 bool bit 2 RW
HR 21 bool bit 3 RW
HR 22 bool bit 0 RW
HR 22 bool bit 1 RW
HR 22 bool bit 2 RW
HR 22 bool bit 3 RW
HR 1000 uint16 R Firmware version of the section (raw number)
HR 1001 uint16 bits 0–7 R
HR 1001 uint16 bits 8–15 R
HR 1002 uint16 bits 0–3 R
HR 1002 uint16 bits 4–7 R
HR 1002 uint16 bits 8–15 R
HR 1003 uint16 R
HR 1004 uint16 R
HR 1005 uint32 ABCD R
HR 1007 bool bit 0 RW
HR 1007 bool bit 1 RW
HR 1007 bool bit 2 RW
HR 1007 bool bit 3 RW
HR 1008 uint16 RW ms
HR 1009 uint16 R Reference voltage of the MCU (raw)
HR 1010 uint16 RW ms ×0.1 Raw unit is 100 us
HR 1011 uint16 RW ms ×0.1 Raw unit is 100 us
HR 1012 uint16 RW ms ×0.1 Raw unit is 100 us
HR 1013 uint16 RW ms ×0.1 Raw unit is 100 us
HR 1014 bool bit 0 RW
HR 1014 bool bit 1 RW
HR 1014 bool bit 2 RW
HR 1014 bool bit 3 RW
HR 1015 bool bit 0 RW
HR 1015 bool bit 1 RW
HR 1015 bool bit 2 RW
HR 1015 bool bit 3 RW
HR 1016 bool bit 0 RW
HR 1016 bool bit 1 RW
HR 1016 bool bit 2 RW
HR 1016 bool bit 3 RW
HR 1017 uint16 RW
HR 1018 uint16 RW
HR 1019 uint16 RW
HR 1020 uint16 RW
HR 1021 uint16 RW
HR 1022 uint16 RW
HR 1023 uint16 RW
HR 1024 uint16 RW
HR 1025 uint16 RW
HR 1026 uint16 RW
HR 1027 uint16 RW
HR 1028 uint16 RW
HR 1029 uint16 RW
HR 1030 uint16 RW
HR 3000 float32 ABCD RW Value in the unit of the configured mode (V, mA or ohm)
HR 3002 float32 ABCD R Value in the unit of the configured mode (V, mA or ohm)
HR 4000 uint16 R %
HR 4001 uint16 R %
CO 0 bool RW
CO 1 bool RW
CO 2 bool RW
CO 3 bool RW
CO 4 bool R
CO 5 bool R
CO 6 bool R
CO 7 bool R
CO 8 bool RW
CO 9 bool RW
CO 10 bool RW
CO 11 bool RW
CO 1000 bool RW Clears the MWD reboot indication
CO 1001 bool RW Enable or disable the 1-Wire bus
CO 1002 bool W
CO 1003 bool W Stores the current configuration so it is used at startup