Unipi Technology Extension xS54 Modbus register map

Modbus RTU extension with 4 digital inputs, 5 relay outputs and 8 configurable analog inputs (voltage, current, resistance)

  • Official
  • 90 registers
  • Modbus RTU
  • Revision 3 · 2026-11-10
  • Identity: firmware, serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
15
Serial
19200 8N1 · 19200 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
CDAB · bytes big-endian, words low first (word swap)
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
75 holding registers, 15 coils
Groups
11
Translation tables
3
Revision
3 · 2026-11-10
Added
()
File
maps/unipi/xs54.mbmap.json · 16 KB · history
SHA-256
6144c60f9b8bbf752f6d64d177cf387a64f0fa47bd2d1de805e94c114ff1a1ff
Manufacturer
www.unipi.technology

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Firmware Firmware version holding 1000 uint16
Serial number PCB serial number holding 1005 uint32 CDAB

Sources and notes

Source: Extension xS54 Modbus map v2.0, Unipi technology

  • Registers are 0-based. 32-bit values use word order CDAB (low word first). Defaults: slave address 15, 19200 bps, 8N1.
  • Registers marked Reserved in the manual are left out.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 bool bit 0 R
HR 0 bool bit 1 R
HR 0 bool bit 2 R
HR 0 bool bit 3 R
HR 1 bool bit 0 RW
HR 1 bool bit 1 RW
HR 1 bool bit 2 RW
HR 1 bool bit 3 RW
HR 1 bool bit 4 RW
HR 2 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 4 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 6 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 8 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 10 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 12 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 14 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 16 float32 CDAB R Value in the unit of the selected input mode (V, mA or ohm)
HR 18 bool bit 0 RW
HR 18 bool bit 1 RW
HR 19 uint32 CDAB RW Pulse counter; writable to reset
HR 21 uint32 CDAB RW Pulse counter; writable to reset
HR 23 uint32 CDAB RW Pulse counter; writable to reset
HR 25 uint32 CDAB RW Pulse counter; writable to reset
HR 27 bool bit 0 RW
HR 27 bool bit 1 RW
HR 27 bool bit 2 RW
HR 28 bool bit 0 RW
HR 28 bool bit 1 RW
HR 28 bool bit 2 RW
HR 28 bool bit 3 RW
HR 28 bool bit 4 RW
HR 29 bool bit 0 RW
HR 29 bool bit 1 RW
HR 29 bool bit 2 RW
HR 29 bool bit 3 RW
HR 29 bool bit 4 RW
HR 1000 uint16 R Firmware version of the extension (raw number)
HR 1001 uint16 bits 0–7 R
HR 1001 uint16 bits 8–15 R
HR 1002 uint16 bits 0–3 R
HR 1002 uint16 bits 4–7 R
HR 1002 uint16 bits 8–15 R
HR 1003 uint16 R
HR 1004 uint16 R
HR 1005 uint32 CDAB R
HR 1008 uint16 RW ms MasterWatchDog timeout; default 5000 ms
HR 1009 uint16 R Reference voltage of the MCU (raw)
HR 1010 uint16 RW ms ×0.1 Raw unit is 100 us; default 50 (5 ms)
HR 1011 uint16 RW ms ×0.1 Raw unit is 100 us; default 50 (5 ms)
HR 1012 uint16 RW ms ×0.1 Raw unit is 100 us; default 50 (5 ms)
HR 1013 uint16 RW ms ×0.1 Raw unit is 100 us; default 50 (5 ms)
HR 1014 bool bit 0 RW
HR 1014 bool bit 1 RW
HR 1014 bool bit 2 RW
HR 1014 bool bit 3 RW
HR 1015 bool bit 0 RW
HR 1015 bool bit 1 RW
HR 1015 bool bit 2 RW
HR 1015 bool bit 3 RW
HR 1016 bool bit 0 RW
HR 1016 bool bit 1 RW
HR 1016 bool bit 2 RW
HR 1016 bool bit 3 RW
HR 1017 uint16 RW Measurement type of the input; default 1
HR 1018 uint16 RW Measurement type of the input; default 1
HR 1019 uint16 RW Measurement type of the input; default 1
HR 1020 uint16 RW Measurement type of the input; default 1
HR 1021 uint16 RW Measurement type of the input; default 1
HR 1022 uint16 RW Measurement type of the input; default 1
HR 1023 uint16 RW Measurement type of the input; default 1
HR 1024 uint16 RW Measurement type of the input; default 1
HR 1025 uint16 bits 0–12 RW Applied after saving the configuration and restarting
HR 1025 bool bit 13 RW
HR 1025 bool bit 14 RW
HR 1026 uint16 RW Slave address, 1-254; default 15
CO 0 bool RW
CO 1 bool RW
CO 2 bool RW
CO 3 bool RW
CO 4 bool RW
CO 5 bool R
CO 6 bool R
CO 7 bool R
CO 8 bool R
CO 9 bool RW
CO 10 bool RW
CO 11 bool RW
CO 1000 bool RW Clears the MWD reboot indication
CO 1002 bool W
CO 1003 bool W Stores the current configuration so it is used at startup