MBMap Registry
  1. Devices
  2. Victron Energy
  3. GX AC load meter

Victron Energy GX AC load meter Modbus register map

Energy meters configured as AC load meter, read through a GX device

  • Official
  • 22 registers
  • Modbus TCP
  • Revision 1 · 2026-10-14
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1default
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
22 holding registers
Revision
1 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-acload.mbmap.json · 4 KB · history
SHA-256
910f7aa0a95bd6b0bb4e05d82103f71a1e91f2bf414c657615da2dd3a2e04250
Manufacturer
victronenergy.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 3903 string[7]

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.acload service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 3900 uint16 R W D-Bus /Ac/L1/Power
HR 3901 uint16 R W D-Bus /Ac/L2/Power
HR 3902 uint16 R W D-Bus /Ac/L3/Power
HR 3903 string[7] R D-Bus /Serial
HR 3910 uint16 R V ×0.1 D-Bus /Ac/L1/Voltage
HR 3911 int16 R A ×0.1 D-Bus /Ac/L1/Current
HR 3912 uint16 R V ×0.1 D-Bus /Ac/L2/Voltage
HR 3913 int16 R A ×0.1 D-Bus /Ac/L2/Current
HR 3914 uint16 R V ×0.1 D-Bus /Ac/L3/Voltage
HR 3915 int16 R A ×0.1 D-Bus /Ac/L3/Current
HR 3916 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L1/Energy/Forward
HR 3918 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L2/Energy/Forward
HR 3920 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L3/Energy/Forward
HR 3922 uint16 R Hz ×0.01 D-Bus /Ac/Frequency
HR 3924 int32 ABCD R W D-Bus /Ac/L1/Power
HR 3926 int32 ABCD R W D-Bus /Ac/L2/Power
HR 3928 int32 ABCD R W D-Bus /Ac/L3/Power
HR 3930 int16 R ×0.001 D-Bus /Ac/L1/PowerFactor
HR 3931 int16 R ×0.001 D-Bus /Ac/L2/PowerFactor
HR 3932 int16 R ×0.001 D-Bus /Ac/L3/PowerFactor
HR 3933 int16 R ×0.001 D-Bus /Ac/PowerFactor
HR 3940 string[8] RW D-Bus /CustomName

Help improve this map