Victron Energy GX battery Modbus register map

Battery monitors (BMV, SmartShunt, Lynx) and managed batteries, read through a GX device

  • Official
  • 106 registers
  • Modbus TCP
  • Revision 2 · 2026-10-14

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
225
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
106 holding registers
Revision
2 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-battery.mbmap.json · 26 KB · history
SHA-256
afe718e48cd1b6e224e49fd5697ea1199aafd43f4b33540fa8a0378c2a4b6971
Manufacturer
victronenergy.com

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.battery service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 256 int32 ABCD R W D-Bus /Dc/0/Power
HR 258 int16 R W D-Bus /Dc/0/Power; Older 16-bit variant of 256
HR 259 uint16 R V ×0.01 D-Bus /Dc/0/Voltage
HR 260 uint16 R V ×0.01 D-Bus /Dc/1/Voltage
HR 261 int16 R A ×0.1 D-Bus /Dc/0/Current; Postive: battery begin charged. Negative: battery being discharged
HR 262 int16 R °C ×0.1 D-Bus /Dc/0/Temperature; In degrees Celsius
HR 263 uint16 R V ×0.01 D-Bus /Dc/0/MidVoltage
HR 264 uint16 R % ×0.01 D-Bus /Dc/0/MidVoltageDeviation
HR 265 uint16 R Ah ×-0.1 D-Bus /ConsumedAmphours; Always negative (to have the same sign as the current)
HR 266 uint16 R % ×0.1 D-Bus /Soc
HR 267 uint16 R D-Bus /Alarms/Alarm; 2015-01-19: Deprecated for CCGX. Value is always 0
HR 268 uint16 R D-Bus /Alarms/LowVoltage
HR 269 uint16 R D-Bus /Alarms/HighVoltage
HR 270 uint16 R D-Bus /Alarms/LowStarterVoltage
HR 271 uint16 R D-Bus /Alarms/HighStarterVoltage
HR 272 uint16 R D-Bus /Alarms/LowSoc
HR 273 uint16 R D-Bus /Alarms/LowTemperature
HR 274 uint16 R D-Bus /Alarms/HighTemperature
HR 275 uint16 R D-Bus /Alarms/MidVoltage
HR 276 uint16 R D-Bus /Alarms/LowFusedVoltage; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 277 uint16 R D-Bus /Alarms/HighFusedVoltage; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 278 uint16 R D-Bus /Alarms/FuseBlown
HR 279 uint16 R D-Bus /Alarms/HighInternalTemperature
HR 280 uint16 RW D-Bus /Relay/0/State; Not supported by CAN.Bus BMS batteries
HR 281 uint16 R Ah ×-0.1 D-Bus /History/DeepestDischarge; Not supported by CAN.Bus BMS batteries
HR 282 uint16 R Ah ×-0.1 D-Bus /History/LastDischarge; Not supported by CAN.Bus BMS batteries
HR 283 uint16 R Ah ×-0.1 D-Bus /History/AverageDischarge; Not supported by CAN.Bus BMS batteries
HR 284 uint16 R D-Bus /History/ChargeCycles; Not supported by CAN.Bus BMS batteries
HR 285 uint16 R D-Bus /History/FullDischarges; Not supported by CAN.Bus BMS batteries
HR 286 uint16 R Ah ×-0.1 D-Bus /History/TotalAhDrawn; Not supported by CAN.Bus BMS batteries
HR 287 uint16 R V ×0.01 D-Bus /History/MinimumVoltage; Not supported by CAN.Bus BMS batteries
HR 288 uint16 R V ×0.01 D-Bus /History/MaximumVoltage; Not supported by CAN.Bus BMS batteries
HR 289 uint16 R s ×100 D-Bus /History/TimeSinceLastFullCharge; Not supported by CAN.Bus BMS batteries
HR 290 uint16 R D-Bus /History/AutomaticSyncs; Not supported by CAN.Bus BMS batteries
HR 291 uint16 R D-Bus /History/LowVoltageAlarms; Not supported by CAN.Bus BMS batteries
HR 292 uint16 R D-Bus /History/HighVoltageAlarms; Not supported by CAN.Bus BMS batteries
HR 293 uint16 R D-Bus /History/LowStarterVoltageAlarms; Not supported by CAN.Bus BMS batteries
HR 294 uint16 R D-Bus /History/HighStarterVoltageAlarms; Not supported by CAN.Bus BMS batteries
HR 295 uint16 R V ×0.01 D-Bus /History/MinimumStarterVoltage; Not supported by CAN.Bus BMS batteries
HR 296 uint16 R V ×0.01 D-Bus /History/MaximumStarterVoltage; Not supported by CAN.Bus BMS batteries
HR 297 uint16 R D-Bus /History/LowFusedVoltageAlarms; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 298 uint16 R D-Bus /History/HighFusedVoltageAlarms; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 299 uint16 R V ×0.01 D-Bus /History/MinimumFusedVoltage; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 300 uint16 R V ×0.01 D-Bus /History/MaximumFusedVoltage; 2014-12-13: Deprecated because over-engineered. Value is always 0
HR 301 uint16 R kWh ×0.1 D-Bus /History/DischargedEnergy; Not supported by CAN.Bus BMS batteries
HR 302 uint16 R kWh ×0.1 D-Bus /History/ChargedEnergy; Not supported by CAN.Bus BMS batteries
HR 303 uint16 R s ×100 D-Bus /TimeToGo; Special value: 0 = charging. Not supported by CAN.Bus BMS batteries
HR 304 uint16 R % ×0.1 D-Bus /Soh; Not supported by all Victron products. Supported by third-party CAN.Bus batteries and Lynx NG
HR 305 uint16 R V ×0.1 D-Bus /Info/MaxChargeVoltage; Not supported by all Victron products. Supported by third-party CAN.Bus batteries and Lynx NG
HR 306 uint16 R V ×0.1 D-Bus /Info/BatteryLowVoltage; Not supported by all Victron products. Supported by third-party CAN.Bus batteries and Lynx NG
HR 307 uint16 R A ×0.1 D-Bus /Info/MaxChargeCurrent; Not supported by all Victron products. Supported by third-party CAN.Bus batteries and Lynx NG
HR 308 uint16 R A ×0.1 D-Bus /Info/MaxDischargeCurrent; Not supported by all Victron products. Supported by third-party CAN.Bus batteries and Lynx NG
HR 309 uint16 R Ah ×0.1 D-Bus /Capacity
HR 310 int32 ABCD R D-Bus /Diagnostics/LastErrors/1/Time
HR 312 int32 ABCD R D-Bus /Diagnostics/LastErrors/2/Time
HR 314 int32 ABCD R D-Bus /Diagnostics/LastErrors/3/Time
HR 316 int32 ABCD R D-Bus /Diagnostics/LastErrors/4/Time
HR 318 int16 R °C ×0.1 D-Bus /System/MinCellTemperature
HR 319 int16 R °C ×0.1 D-Bus /System/MaxCellTemperature
HR 320 uint16 R D-Bus /Alarms/HighChargeCurrent
HR 321 uint16 R D-Bus /Alarms/HighDischargeCurrent
HR 322 uint16 R D-Bus /Alarms/CellImbalance
HR 323 uint16 R D-Bus /Alarms/InternalFailure
HR 324 uint16 R D-Bus /Alarms/HighChargeTemperature
HR 325 uint16 R D-Bus /Alarms/LowChargeTemperature
HR 326 uint16 R D-Bus /Alarms/LowCellVoltage
HR 327 uint16 R D-Bus /Alarms/BmsCable; Supported only by Lynx BMS
HR 328 uint16 R D-Bus /Alarms/Contactor; Supported only by Lynx BMS
HR 329 uint16 R D-Bus /Alarms/HighCurrent; Supported only by Lynx BMS
HR 330 uint32 ABCD R Ah ×-1 D-Bus /ConsumedAmphours; 32-bit compliment to register 265
HR 1282 uint16 R D-Bus /State
HR 1283 uint16 R D-Bus /ErrorCode
HR 1284 uint16 R D-Bus /SystemSwitch
HR 1285 uint16 R D-Bus /Balancing
HR 1286 uint16 R D-Bus /System/NrOfBatteries
HR 1287 uint16 R D-Bus /System/BatteriesParallel
HR 1288 uint16 R D-Bus /System/BatteriesSeries
HR 1289 uint16 R D-Bus /System/NrOfCellsPerBattery
HR 1290 uint16 R V ×0.01 D-Bus /System/MinCellVoltage
HR 1291 uint16 R V ×0.01 D-Bus /System/MaxCellVoltage
HR 1292 uint16 R D-Bus /Diagnostics/ShutDownsDueError
HR 1293 uint16 R D-Bus /Diagnostics/LastErrors/1/Error
HR 1294 uint16 R D-Bus /Diagnostics/LastErrors/2/Error
HR 1295 uint16 R D-Bus /Diagnostics/LastErrors/3/Error
HR 1296 uint16 R D-Bus /Diagnostics/LastErrors/4/Error
HR 1297 uint16 R D-Bus /Io/AllowToCharge
HR 1298 uint16 R D-Bus /Io/AllowToDischarge
HR 1299 uint16 R D-Bus /Io/ExternalRelay
HR 1300 uint16 R V ×0.01 D-Bus /History/MinimumCellVoltage
HR 1301 uint16 R V ×0.01 D-Bus /History/MaximumCellVoltage
HR 1302 uint16 R D-Bus /System/NrOfModulesOffline
HR 1303 uint16 R D-Bus /System/NrOfModulesOnline
HR 1304 uint16 R D-Bus /System/NrOfModulesBlockingCharge
HR 1305 uint16 R D-Bus /System/NrOfModulesBlockingDischarge
HR 1306 string[4] R D-Bus /System/MinVoltageCellId
HR 1310 string[4] R D-Bus /System/MaxVoltageCellId
HR 1314 string[4] R D-Bus /System/MinTemperatureCellId
HR 1318 string[4] R D-Bus /System/MaxTemperatureCellId
HR 1322 uint16 RW D-Bus /Mode
HR 1323 uint16 R D-Bus /Balancer/Status