Victron Energy GX grid meter Modbus register map

Energy meters configured as grid meter (ET340, EM24, EM540...), read through a GX device

  • Official
  • 33 registers
  • Modbus TCP
  • Revision 1 · 2026-10-14
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1default
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
33 holding registers
Revision
1 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-grid.mbmap.json · 7 KB · history
SHA-256
437c4dc4463df12a724fbf4d35aa626d64573f1cd6d14bce08da92eaa99b3af6
Manufacturer
victronenergy.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial holding 2609 string[7]

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.grid service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 2600 int16 R W D-Bus /Ac/L1/Power
HR 2601 int16 R W D-Bus /Ac/L2/Power
HR 2602 int16 R W D-Bus /Ac/L3/Power
HR 2603 uint16 R kWh ×0.01 D-Bus /Ac/L1/Energy/Forward
HR 2604 uint16 R kWh ×0.01 D-Bus /Ac/L2/Energy/Forward
HR 2605 uint16 R kWh ×0.01 D-Bus /Ac/L3/Energy/Forward
HR 2606 uint16 R kWh ×0.01 D-Bus /Ac/L1/Energy/Reverse
HR 2607 uint16 R kWh ×0.01 D-Bus /Ac/L2/Energy/Reverse
HR 2608 uint16 R kWh ×0.01 D-Bus /Ac/L3/Energy/Reverse
HR 2609 string[7] R D-Bus /Serial; The grid meter serial as string (MSB of first register: first character, LSB of last register: last character)
HR 2616 uint16 R V ×0.1 D-Bus /Ac/L1/Voltage
HR 2617 int16 R A ×0.1 D-Bus /Ac/L1/Current
HR 2618 uint16 R V ×0.1 D-Bus /Ac/L2/Voltage
HR 2619 int16 R A ×0.1 D-Bus /Ac/L2/Current
HR 2620 uint16 R V ×0.1 D-Bus /Ac/L3/Voltage
HR 2621 int16 R A ×0.1 D-Bus /Ac/L3/Current
HR 2622 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L1/Energy/Forward
HR 2624 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L2/Energy/Forward
HR 2626 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L3/Energy/Forward
HR 2628 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L1/Energy/Reverse
HR 2630 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L2/Energy/Reverse
HR 2632 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L3/Energy/Reverse
HR 2634 uint32 ABCD R kWh ×0.01 D-Bus /Ac/Energy/Forward; Depending on the energy summation method used by the meter, this may be different to the sum of the individual counters
HR 2636 uint32 ABCD R kWh ×0.01 D-Bus /Ac/Energy/Reverse
HR 2638 int32 ABCD R W D-Bus /Ac/L1/Power
HR 2640 int32 ABCD R W D-Bus /Ac/L2/Power
HR 2642 int32 ABCD R W D-Bus /Ac/L3/Power
HR 2644 uint16 R Hz ×0.01 D-Bus /Ac/Frequency
HR 2645 int16 R ×0.001 D-Bus /Ac/L1/PowerFactor
HR 2646 int16 R ×0.001 D-Bus /Ac/L2/PowerFactor
HR 2647 int16 R ×0.001 D-Bus /Ac/L3/PowerFactor
HR 2648 int16 R ×0.001 D-Bus /Ac/PowerFactor
HR 2650 string[8] RW D-Bus /CustomName