MBMap Registry
  1. Devices
  2. Victron Energy
  3. GX PV inverter

Victron Energy GX PV inverter Modbus register map

AC-coupled PV inverters (Fronius, SMA, ...), read through a GX device

  • Official
  • 25 registers
  • Modbus TCP
  • Revision 1 · 2026-10-14
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1default
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
25 holding registers
Revision
1 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-pvinverter.mbmap.json · 5 KB · history
SHA-256
1b80392d977131def1b0ead72914febbecf5f2fda019ebca24dab3fcbc87480e
Manufacturer
victronenergy.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial holding 1039 string[7]

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.pvinverter service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 1026 uint16 R D-Bus /Position
HR 1027 uint16 R V ×0.1 D-Bus /Ac/L1/Voltage
HR 1028 int16 R A ×0.1 D-Bus /Ac/L1/Current
HR 1029 uint16 R W D-Bus /Ac/L1/Power
HR 1030 uint16 R kWh ×0.01 D-Bus /Ac/L1/Energy/Forward; Deprecated. Use 1046 instead
HR 1031 uint16 R V ×0.1 D-Bus /Ac/L2/Voltage
HR 1032 int16 R A ×0.1 D-Bus /Ac/L2/Current
HR 1033 uint16 R W D-Bus /Ac/L2/Power
HR 1034 uint16 R kWh ×0.01 D-Bus /Ac/L2/Energy/Forward; Deprecated. Use 1048 instead
HR 1035 uint16 R V ×0.1 D-Bus /Ac/L3/Voltage
HR 1036 int16 R A ×0.1 D-Bus /Ac/L3/Current
HR 1037 uint16 R W D-Bus /Ac/L3/Power
HR 1038 uint16 R kWh ×0.01 D-Bus /Ac/L3/Energy/Forward; Deprecated. Use 1050 instead
HR 1039 string[7] R D-Bus /Serial; The system serial as string (MSB of first register: first character, LSB of last register: last character)
HR 1046 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L1/Energy/Forward
HR 1048 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L2/Energy/Forward
HR 1050 uint32 ABCD R kWh ×0.01 D-Bus /Ac/L3/Energy/Forward
HR 1052 int32 ABCD R W D-Bus /Ac/Power
HR 1054 uint32 ABCD R W D-Bus /Ac/MaxPower
HR 1056 uint32 ABCD RW W D-Bus /Ac/PowerLimit; For use in ESS mode 3
HR 1058 uint32 ABCD R W D-Bus /Ac/L1/Power
HR 1060 uint32 ABCD R W D-Bus /Ac/L2/Power
HR 1062 uint32 ABCD R W D-Bus /Ac/L3/Power
HR 1064 uint16 R Hz ×0.01 D-Bus /Ac/Frequency
HR 1070 string[8] RW D-Bus /CustomName

Help improve this map