Victron Energy GX solar charger Modbus register map

SmartSolar / BlueSolar MPPT solar chargers, read through a GX device

  • Official
  • 54 registers
  • Modbus TCP
  • Revision 1 · 2026-10-14

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1default
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
54 holding registers
Revision
1 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-solarcharger.mbmap.json · 11 KB · history
SHA-256
ffbfe747b35e4b941218f5d86e26ad842b3f873651bf176375501ca578208ae1
Manufacturer
victronenergy.com

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.solarcharger service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 771 uint16 R V ×0.01 D-Bus /Dc/0/Voltage
HR 772 int16 R A ×0.1 D-Bus /Dc/0/Current
HR 773 int16 R °C ×0.1 D-Bus /Dc/0/Temperature; VE.Can MPPTs only
HR 774 uint16 RW D-Bus /Mode; VE.Can MPPTs only
HR 775 uint16 R D-Bus /State
HR 776 uint16 R V ×0.01 D-Bus /Pv/V; Not available if multiple VE.Can chargers are combined
HR 777 int16 R A ×0.1 Calculated from /Yield/Power and /Pv/V
HR 778 uint16 R D-Bus /Equalization/Pending
HR 779 uint16 R s ×0.1 D-Bus /Equalization/TimeRemaining
HR 780 uint16 R D-Bus /Relay/0/State
HR 784 uint16 R kWh ×0.1 D-Bus /History/Daily/0/Yield; Today's yield
HR 785 uint16 R W D-Bus /History/Daily/0/MaxPower; Today's maximum power
HR 786 uint16 R kWh ×0.1 D-Bus /History/Daily/1/Yield; Yesterday's yield
HR 787 uint16 R W D-Bus /History/Daily/1/MaxPower; Yesterday's maximum power
HR 788 uint16 R D-Bus /ErrorCode
HR 789 uint16 R W ×0.1 D-Bus /Yield/Power; Older 16-bit variant of 789
HR 790 uint16 R kWh ×0.1 D-Bus /Yield/User; Energy generated by the solarcharger since last user reset
HR 791 uint16 R D-Bus /MppOperationMode
HR 792 uint32 ABCD R W D-Bus /Yield/Power
HR 3700 uint16 R V ×0.01 D-Bus /Pv/0/V
HR 3701 uint16 R V ×0.01 D-Bus /Pv/1/V
HR 3702 uint16 R V ×0.01 D-Bus /Pv/2/V
HR 3703 uint16 R V ×0.01 D-Bus /Pv/3/V
HR 3708 uint16 R kWh ×0.1 D-Bus /History/Daily/0/Pv/0/Yield
HR 3709 uint16 R kWh ×0.1 D-Bus /History/Daily/0/Pv/1/Yield
HR 3710 uint16 R kWh ×0.1 D-Bus /History/Daily/0/Pv/2/Yield
HR 3711 uint16 R kWh ×0.1 D-Bus /History/Daily/0/Pv/3/Yield
HR 3712 uint16 R kWh ×0.1 D-Bus /History/Daily/1/Pv/0/Yield
HR 3713 uint16 R kWh ×0.1 D-Bus /History/Daily/1/Pv/1/Yield
HR 3714 uint16 R kWh ×0.1 D-Bus /History/Daily/1/Pv/2/Yield
HR 3715 uint16 R kWh ×0.1 D-Bus /History/Daily/1/Pv/3/Yield
HR 3716 uint16 R W D-Bus /History/Daily/0/Pv/0/MaxPower
HR 3717 uint16 R W D-Bus /History/Daily/0/Pv/1/MaxPower
HR 3718 uint16 R W D-Bus /History/Daily/0/Pv/2/MaxPower
HR 3719 uint16 R W D-Bus /History/Daily/0/Pv/3/MaxPower
HR 3720 uint16 R W D-Bus /History/Daily/1/Pv/0/MaxPower
HR 3721 uint16 R W D-Bus /History/Daily/1/Pv/1/MaxPower
HR 3722 uint16 R W D-Bus /History/Daily/1/Pv/2/MaxPower
HR 3723 uint16 R W D-Bus /History/Daily/1/Pv/3/MaxPower
HR 3724 uint16 R W D-Bus /Pv/0/P
HR 3725 uint16 R W D-Bus /Pv/1/P
HR 3726 uint16 R W D-Bus /Pv/2/P
HR 3727 uint16 R W D-Bus /Pv/3/P
HR 3728 uint32 ABCD R kWh D-Bus /Yield/User; Energy generated by the solarcharger since last user reset
HR 3730 uint16 R W D-Bus /Yield/Power
HR 3731 uint16 R D-Bus /Pv/0/MppOperationMode
HR 3732 uint16 R D-Bus /Pv/1/MppOperationMode
HR 3733 uint16 R D-Bus /Pv/2/MppOperationMode
HR 3734 uint16 R D-Bus /Pv/3/MppOperationMode
HR 3735 uint16 R D-Bus /Pv/0/Enabled; Only available on MPPT RS
HR 3736 uint16 R D-Bus /Pv/1/Enabled
HR 3737 uint16 R D-Bus /Pv/2/Enabled
HR 3738 uint16 R D-Bus /Pv/3/Enabled
HR 3740 string[8] RW D-Bus /CustomName