Victron Energy GX system Modbus register map

System overview of a Victron GX device (Cerbo GX, Venus GX, Color Control GX, Ekrano GX)

  • Official
  • 72 registers
  • Modbus TCP
  • Revision 2 · 2026-11-10
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
100
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
72 holding registers
Revision
2 · 2026-11-10
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-system.mbmap.json · 14 KB · history
SHA-256
b7a609f4f0c1d8305d5e4f497b5dabee620f301996bd01510559263f144727dd
Manufacturer
victronenergy.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial (System) holding 800 string[6]

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.system service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • The unit ID of this service is 100.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 800 string[6] R D-Bus /Serial; System value -> MAC address of CCGX (represented as string)
HR 806 uint16 RW D-Bus /Relay/0/State
HR 807 uint16 RW D-Bus /Relay/1/State; Relay 1 is available on Venus GX only
HR 808 uint16 R W D-Bus /Ac/PvOnOutput/L1/Power; Summation of all AC-Coupled PV Inverters on the output
HR 809 uint16 R W D-Bus /Ac/PvOnOutput/L2/Power
HR 810 uint16 R W D-Bus /Ac/PvOnOutput/L3/Power
HR 811 uint16 R W D-Bus /Ac/PvOnGrid/L1/Power; Summation of all AC-Coupled PV Inverters on the input
HR 812 uint16 R W D-Bus /Ac/PvOnGrid/L2/Power
HR 813 uint16 R W D-Bus /Ac/PvOnGrid/L3/Power
HR 814 uint16 R W D-Bus /Ac/PvOnGenset/L1/Power; Summation of all AC-Coupled PV Inverters on a generator. Bit theoretic; this will never be used
HR 815 uint16 R W D-Bus /Ac/PvOnGenset/L2/Power
HR 816 uint16 R W D-Bus /Ac/PvOnGenset/L3/Power
HR 817 uint16 R W D-Bus /Ac/Consumption/L1/Power; Power supplied by system to loads
HR 818 uint16 R W D-Bus /Ac/Consumption/L2/Power
HR 819 uint16 R W D-Bus /Ac/Consumption/L3/Power
HR 820 int16 R W D-Bus /Ac/Grid/L1/Power; Power supplied by Grid to system
HR 821 int16 R W D-Bus /Ac/Grid/L2/Power
HR 822 int16 R W D-Bus /Ac/Grid/L3/Power
HR 823 int16 R W D-Bus /Ac/Genset/L1/Power; Power supplied by Genset tot system
HR 824 int16 R W D-Bus /Ac/Genset/L2/Power
HR 825 int16 R W D-Bus /Ac/Genset/L3/Power
HR 826 int16 R D-Bus /Ac/ActiveIn/Source; 0 indicates that there is an active input, but it is not configured under Settings → System setup
HR 830 uint64 ABCD R s
HR 834 uint16 R Render in hexadecimal to get the text version
HR 835 uint16 R This is zero for official releases
HR 840 uint16 R V ×0.1 D-Bus /Dc/Battery/Voltage; Battery Voltage determined from different measurements. In order of preference: BMV-voltage (V), Multi-DC-Voltage (CV), MPPT-DC-Voltage (ScV), Charger voltage
HR 841 int16 R A ×0.1 D-Bus /Dc/Battery/Current; Postive: battery begin charged. Negative: battery being discharged
HR 842 int16 R W D-Bus /Dc/Battery/Power; Postive: battery begin charged. Negative: battery being discharged
HR 843 uint16 R % D-Bus /Dc/Battery/Soc; Best battery state of charge, determined from different measurements
HR 844 uint16 R D-Bus /Dc/Battery/State
HR 845 uint16 R Ah ×-0.1 D-Bus /Dc/Battery/ConsumedAmphours
HR 846 uint16 R s ×100 D-Bus /Dc/Battery/TimeToGo; Special value: 0 = charging
HR 850 uint16 R W D-Bus /Dc/Pv/Power; Summation of output power of all connected Solar Chargers
HR 851 int16 R A ×0.1 D-Bus /Dc/Pv/Current; Summation of output current of all connected Solar Chargers
HR 855 uint16 R W D-Bus /Dc/Charger/Power
HR 860 int16 R W D-Bus /Dc/System/Power; Power supplied by Battery to system
HR 865 int16 R A ×0.1 D-Bus /Dc/Vebus/Current; Current flowing from the Multi to the dc system. Negative: the other way around
HR 866 int16 R W D-Bus /Dc/Vebus/Power; System value etc. AND: Positive: power flowing from the Multi to the dc system. Negative: the other way around
HR 868 int32 ABCD R ×0.1 D-Bus /Dc/InverterCharger/Current
HR 870 int32 ABCD R D-Bus /Dc/InverterCharger/Power
HR 872 int32 ABCD R W D-Bus /Ac/ConsumptionOnInput/L1/Power; This is the power shown on the overview in the Loads box
HR 874 int32 ABCD R W D-Bus /Ac/ConsumptionOnInput/L2/Power
HR 876 int32 ABCD R W D-Bus /Ac/ConsumptionOnInput/L3/Power
HR 878 int32 ABCD R W D-Bus /Ac/ConsumptionOnOutput/L1/Power
HR 880 int32 ABCD R W D-Bus /Ac/ConsumptionOnOutput/L2/Power
HR 882 int32 ABCD R W D-Bus /Ac/ConsumptionOnOutput/L3/Power
HR 884 uint32 ABCD R W D-Bus /Ac/PvOnOutput/L1/Power; Summation of all AC-Coupled PV Inverters on the output
HR 886 uint32 ABCD R W D-Bus /Ac/PvOnOutput/L2/Power
HR 888 uint32 ABCD R W D-Bus /Ac/PvOnOutput/L3/Power
HR 890 uint32 ABCD R W D-Bus /Ac/PvOnGrid/L1/Power; Summation of all AC-Coupled PV Inverters on the input
HR 892 uint32 ABCD R W D-Bus /Ac/PvOnGrid/L2/Power
HR 894 uint32 ABCD R W D-Bus /Ac/PvOnGrid/L3/Power
HR 896 uint32 ABCD R W D-Bus /Ac/PvOnGenset/L1/Power; Summation of all AC-Coupled PV Inverters on a generator. Bit theoretic; this will never be used
HR 898 uint32 ABCD R W D-Bus /Ac/PvOnGenset/L2/Power
HR 900 uint32 ABCD R W D-Bus /Ac/PvOnGenset/L3/Power
HR 902 uint32 ABCD R W D-Bus /Ac/Consumption/L1/Power; Power supplied by system to loads
HR 904 uint32 ABCD R W D-Bus /Ac/Consumption/L2/Power
HR 906 uint32 ABCD R W D-Bus /Ac/Consumption/L3/Power
HR 908 int32 ABCD R W D-Bus /Ac/Grid/L1/Power; Power supplied by Grid to system
HR 910 int32 ABCD R W D-Bus /Ac/Grid/L2/Power
HR 912 int32 ABCD R W D-Bus /Ac/Grid/L3/Power
HR 914 int32 ABCD R W D-Bus /Ac/Genset/L1/Power; Power supplied by Genset tot system
HR 916 int32 ABCD R W D-Bus /Ac/Genset/L2/Power
HR 918 int32 ABCD R W D-Bus /Ac/Genset/L3/Power
HR 5400 uint16 R D-Bus /DynamicEss/Active
HR 5401 uint16 R D-Bus /DynamicEss/AllowGridFeedIn
HR 5402 uint16 R D-Bus /DynamicEss/Available
HR 5403 uint16 R ×10 D-Bus /DynamicEss/ChargeRate
HR 5404 uint16 R D-Bus /DynamicEss/ErrorCode
HR 5405 uint16 R D-Bus /DynamicEss/Restrictions
HR 5406 uint16 R D-Bus /DynamicEss/Strategy
HR 5407 uint16 R % D-Bus /DynamicEss/TargetSoc