Victron Energy GX VE.Bus inverter/charger Modbus register map

MultiPlus, Quattro and other VE.Bus inverter/chargers, read through a GX device

  • Official
  • 144 registers
  • Modbus TCP
  • Revision 2 · 2026-10-14

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
227
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
144 holding registers
Revision
2 · 2026-10-14
Firmware
Venus OS; register list 3.81
Added
()
File
maps/victron-energy/gx-vebus.mbmap.json · 32 KB · history
SHA-256
81fc2a44955b67e5e0908de3cce91814029c7934d0add1ded420f849edd3edd4
Manufacturer
victronenergy.com

Sources and notes

Source: Victron Energy, CCGX Modbus TCP register list 3.81

  • Registers of the com.victronenergy.vebus service of the GX Modbus TCP server (Settings > Integrations > Modbus TCP server).
  • Each device on the GX has its own unit ID. Since Venus OS 2.60 they are assigned dynamically: see the list of available services on the GX device.
  • All registers are holding registers (FC03; FC06/FC16 for the writable ones).
AreaAddressNameTypeAccessUnitScaleDescription
HR 3 uint16 R V ×0.1 D-Bus /Ac/ActiveIn/L1/V
HR 4 uint16 R V ×0.1 D-Bus /Ac/ActiveIn/L2/V
HR 5 uint16 R V ×0.1 D-Bus /Ac/ActiveIn/L3/V
HR 6 int16 R A ×0.1 D-Bus /Ac/ActiveIn/L1/I; Positive: current flowing from mains to Multi. Negative: current flowing from Multi to mains
HR 7 int16 R A ×0.1 D-Bus /Ac/ActiveIn/L2/I; Positive: current flowing from mains to Multi. Negative: current flowing from Multi to mains
HR 8 int16 R A ×0.1 D-Bus /Ac/ActiveIn/L3/I; Positive: current flowing from mains to Multi. Negative: current flowing from Multi to mains
HR 9 int16 R Hz ×0.01 D-Bus /Ac/ActiveIn/L1/F
HR 10 int16 R Hz ×0.01 D-Bus /Ac/ActiveIn/L2/F
HR 11 int16 R Hz ×0.01 D-Bus /Ac/ActiveIn/L3/F
HR 12 int16 R W ×10 D-Bus /Ac/ActiveIn/L1/P; Sign meaning equal to Input current
HR 13 int16 R W ×10 D-Bus /Ac/ActiveIn/L2/P; Sign meaning equal to Input current
HR 14 int16 R W ×10 D-Bus /Ac/ActiveIn/L3/P; Sign meaning eaqual to Input current
HR 15 uint16 R V ×0.1 D-Bus /Ac/Out/L1/V
HR 16 uint16 R V ×0.1 D-Bus /Ac/Out/L2/V
HR 17 uint16 R V ×0.1 D-Bus /Ac/Out/L3/V
HR 18 int16 R A ×0.1 D-Bus /Ac/Out/L1/I; Postive: current flowing from Multi to the load. Negative: current flowing from load to the Multi
HR 19 int16 R A ×0.1 D-Bus /Ac/Out/L2/I; Postive: current flowing from Multi to the load. Negative: current flowing from load to the Multi
HR 20 int16 R A ×0.1 D-Bus /Ac/Out/L3/I; Postive: current flowing from Multi to the load. Negative: current flowing from load to the Multi
HR 21 int16 R Hz ×0.01 D-Bus /Ac/Out/L1/F
HR 22 int16 RW A ×0.1 D-Bus /Ac/ActiveIn/CurrentLimit; See Venus-OS manual for limitations, for example when VE.Bus BMS or DMC is installed
HR 23 int16 R W ×10 D-Bus /Ac/Out/L1/P; Sign meaning equal to Output current
HR 24 int16 R W ×10 D-Bus /Ac/Out/L2/P; Sign meaning equal to Output current
HR 25 int16 R W ×10 D-Bus /Ac/Out/L3/P; Sign meaning equal to Output current
HR 26 uint16 R V ×0.01 D-Bus /Dc/0/Voltage
HR 27 int16 R A ×0.1 D-Bus /Dc/0/Current; Positive: current flowing from the Multi to the dc system. Negative: the other way around
HR 28 uint16 R D-Bus /Ac/NumberOfPhases
HR 29 uint16 R D-Bus /Ac/ActiveIn/ActiveInput
HR 30 uint16 RW % ×0.1 D-Bus /Soc
HR 31 uint16 R D-Bus /State
HR 32 uint16 R D-Bus /VebusError
HR 33 uint16 RW D-Bus /Mode; See Venus-OS manual for limitations, for example when VE.Bus BMS or DMC is installed
HR 34 uint16 R D-Bus /Alarms/HighTemperature
HR 35 uint16 R D-Bus /Alarms/LowBattery
HR 36 uint16 R D-Bus /Alarms/Overload
HR 37 int16 RW W D-Bus /Hub4/L1/AcPowerSetpoint; ESS Mode 3 - Instructs the multi to charge/discharge with giving power. Negative = discharge. Used by the control loop in grid-parallel systems
HR 38 uint16 RW D-Bus /Hub4/DisableCharge; ESS Mode 3 - Enables/Disables charge (0=enabled, 1=disabled). Note that power setpoint will yield to this setting
HR 39 uint16 RW D-Bus /Hub4/DisableFeedIn; ESS Mode 3 - Enables/Disables feedback (0=enabled, 1=disabled). Note that power setpoint will yield to this setting
HR 40 int16 RW W D-Bus /Hub4/L2/AcPowerSetpoint; ESS Mode 3 - Instructs the multi to charge/discharge with giving power. Negative = discharge. Used by the control loop in grid-parallel systems
HR 41 int16 RW W D-Bus /Hub4/L3/AcPowerSetpoint; ESS Mode 3 - Instructs the multi to charge/discharge with giving power. Negative = discharge. Used by the control loop in grid-parallel systems
HR 42 uint16 R D-Bus /Alarms/TemperatureSensor
HR 43 uint16 R D-Bus /Alarms/VoltageSensor
HR 44 uint16 R D-Bus /Alarms/L1/HighTemperature
HR 45 uint16 R D-Bus /Alarms/L1/LowBattery
HR 46 uint16 R D-Bus /Alarms/L1/Overload
HR 47 uint16 R D-Bus /Alarms/L1/Ripple
HR 48 uint16 R D-Bus /Alarms/L2/HighTemperature
HR 49 uint16 R D-Bus /Alarms/L2/LowBattery
HR 50 uint16 R D-Bus /Alarms/L2/Overload
HR 51 uint16 R D-Bus /Alarms/L2/Ripple
HR 52 uint16 R D-Bus /Alarms/L3/HighTemperature
HR 53 uint16 R D-Bus /Alarms/L3/LowBattery
HR 54 uint16 R D-Bus /Alarms/L3/Overload
HR 55 uint16 R D-Bus /Alarms/L3/Ripple
HR 56 uint16 RW D-Bus /PvInverter/Disable; Disable PV inverter on AC out (using frequency shifting). Only works when vebus device is in inverter mode. Needs ESS or PV inverter assistant
HR 57 uint16 R D-Bus /Bms/AllowToCharge; VE.Bus BMS allows the battery to be charged
HR 58 uint16 R D-Bus /Bms/AllowToDischarge; VE.Bus BMS allows the battery to be discharged
HR 59 uint16 R D-Bus /Bms/BmsExpected; Presence of VE.Bus BMS is expected based on vebus settings (presence of ESS or BMS assistant)
HR 60 uint16 R D-Bus /Bms/Error
HR 61 int16 R °C ×0.1 D-Bus /Dc/0/Temperature
HR 62 uint16 RW D-Bus /SystemReset; Any write action will cause a reset
HR 63 uint16 R D-Bus /Alarms/PhaseRotation
HR 64 uint16 R D-Bus /Alarms/GridLost
HR 65 uint16 RW D-Bus /Hub4/DoNotFeedInOvervoltage
HR 66 uint16 RW W ×100 D-Bus /Hub4/L1/MaxFeedInPower
HR 67 uint16 RW W ×100 D-Bus /Hub4/L2/MaxFeedInPower
HR 68 uint16 RW W ×100 D-Bus /Hub4/L3/MaxFeedInPower
HR 69 uint16 R D-Bus /Ac/State/IgnoreAcIn1
HR 70 uint16 R D-Bus /Ac/State/IgnoreAcIn2
HR 71 uint16 RW D-Bus /Hub4/TargetPowerIsMaxFeedIn; When set to 1, the Multi behaves as if DoNotFeedInOvervoltage is disabled and AcPowerSetpoint is the maximum allowed feed-in
HR 72 uint16 RW D-Bus /Hub4/FixSolarOffsetTo100mV; When feeding overvoltage into the grid, the solar chargers are set to a higher voltage. This flag determines the size of the offset (per 12V increment)
HR 73 uint16 R D-Bus /Hub4/Sustain
HR 74 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcIn1ToAcOut; PLEASE NOTE:
HR 76 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcIn1ToInverter; Energy counters from the Multi(s) are volatile
HR 78 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcIn2ToAcOut; These energy counters reset to zero when the Multi is switched off
HR 80 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcIn2ToInverter; These energy counters ALSO reset to zero when the GX-device reboots
HR 82 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcOutToAcIn1
HR 84 uint32 ABCD R kWh ×0.01 D-Bus /Energy/AcOutToAcIn2
HR 86 uint32 ABCD R kWh ×0.01 D-Bus /Energy/InverterToAcIn1
HR 88 uint32 ABCD R kWh ×0.01 D-Bus /Energy/InverterToAcIn2
HR 90 uint32 ABCD R kWh ×0.01 D-Bus /Energy/InverterToAcOut
HR 92 uint32 ABCD R kWh ×0.01 D-Bus /Energy/OutToInverter
HR 94 uint16 R D-Bus /Alarms/BmsPreAlarm
HR 95 uint16 R D-Bus /VebusChargeState
HR 96 int32 ABCD RW W D-Bus /Hub4/L1/AcPowerSetpoint; 32-bit compliment to 37, 40 and 41
HR 98 int32 ABCD RW W D-Bus /Hub4/L2/AcPowerSetpoint
HR 100 int32 ABCD RW W D-Bus /Hub4/L3/AcPowerSetpoint
HR 102 uint16 RW D-Bus /Dc/0/PreferRenewableEnergy; Must be enabled in VE.Configure. This causes the system to charge from the grid at a lower sustain voltage. See manual
HR 103 uint16 RW D-Bus /Ac/Control/RemoteGeneratorSelected; Informs Multi that a generator is active on AC-in
HR 104 uint16 R D-Bus /Ac/State/RemoteGeneratorSelected
HR 105 uint16 RW D-Bus /RedetectSystem
HR 106 uint16 RW ×0.01 D-Bus /Settings/AssistCurrentBoostFactor; These 4 settings were first introduced I Venus 3.30, but immediately redefined as they did not work properly
HR 107 uint16 RW V ×0.01 D-Bus /Settings/InverterOutputVoltage
HR 108 uint16 RW D-Bus /Settings/PowerAssistEnabled
HR 109 uint16 RW D-Bus /Settings/UpsFunction
HR 110 uint16 R D-Bus /Devices/0/ExtendStatus/RelayTestOk
HR 111 uint16 R D-Bus /Devices/1/ExtendStatus/RelayTestOk
HR 112 uint16 R D-Bus /Devices/2/ExtendStatus/RelayTestOk
HR 113 uint16 R D-Bus /Devices/3/ExtendStatus/RelayTestOk
HR 114 uint16 R D-Bus /Devices/4/ExtendStatus/RelayTestOk
HR 115 uint16 R D-Bus /Devices/5/ExtendStatus/RelayTestOk