Eastron SDM530-MT Modbus register map

Three-phase four-wire multi-tariff DIN rail energy meter for current transformers, with four tariffs and twelve months of history

  • Official
  • 77 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
80 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
13 holding registers, 64 input registers
Groups
5
Revision
3 · 2026-10-18
Added
()
File
maps/eastron/sdm530-mt.mbmap.json · 14 KB · history
SHA-256
d139e6371060823b3247a5387a87c22bab6d3665069c06bc7ddc8dea5c8cc1f2
Manufacturer
eastroneurope.com

Sources and notes

Source: Eastron, "Eastron SDM530-MT User Manual" with the SDM530-MT Modbus protocol

  • Measurements are float32 input registers (FC04); settings are float32 holding registers (FC03 read, FC16 write, one parameter per write).
  • Requests must cover an even number of registers; at most 40 values per read.
  • Protected settings need the password written to the password register; it times out after one minute unless the password lock register is read.
  • Not in this map: the monthly history blocks (input registers 0x0201-0x0321 and 0xF101-0xFB01, five values per block: total and tariffs 1-4), the clock (0xF000), the demand/display setup (0xF500) and the tariff schedule (0xF700).
AreaAddressNameTypeAccessUnitScaleDescription
IR 0 float32 ABCD R V
IR 2 float32 ABCD R V
IR 4 float32 ABCD R V
IR 6 float32 ABCD R A
IR 8 float32 ABCD R A
IR 10 float32 ABCD R A
IR 12 float32 ABCD R W
IR 14 float32 ABCD R W
IR 16 float32 ABCD R W
IR 18 float32 ABCD R VA
IR 20 float32 ABCD R VA
IR 22 float32 ABCD R VA
IR 24 float32 ABCD R var
IR 26 float32 ABCD R var
IR 28 float32 ABCD R var
IR 30 float32 ABCD R
IR 32 float32 ABCD R
IR 34 float32 ABCD R
IR 36 float32 ABCD R °
IR 38 float32 ABCD R °
IR 40 float32 ABCD R °
IR 42 float32 ABCD R V
IR 46 float32 ABCD R A
IR 48 float32 ABCD R A
IR 52 float32 ABCD R W
IR 56 float32 ABCD R VA
IR 60 float32 ABCD R var
IR 62 float32 ABCD R
IR 66 float32 ABCD R °
IR 70 float32 ABCD R Hz
IR 72 float32 ABCD R kWh
IR 74 float32 ABCD R kWh
IR 76 float32 ABCD R kvarh
IR 78 float32 ABCD R kvarh
IR 80 float32 ABCD R kVAh
IR 82 float32 ABCD R Ah
IR 84 float32 ABCD R W
IR 86 float32 ABCD R W
IR 100 float32 ABCD R VA
IR 102 float32 ABCD R VA
IR 104 float32 ABCD R A
IR 106 float32 ABCD R A
IR 200 float32 ABCD R V
IR 202 float32 ABCD R V
IR 204 float32 ABCD R V
IR 206 float32 ABCD R V
IR 224 float32 ABCD R A
IR 254 float32 ABCD R °
IR 258 float32 ABCD R A
IR 260 float32 ABCD R A
IR 262 float32 ABCD R A
IR 264 float32 ABCD R A
IR 266 float32 ABCD R A
IR 268 float32 ABCD R A
IR 342 float32 ABCD R kWh
IR 344 float32 ABCD R kvarh
IR 2000 float32 ABCD R kWh
IR 2002 float32 ABCD R kWh
IR 2004 float32 ABCD R kWh
IR 2006 float32 ABCD R kWh
IR 2256 float32 ABCD R kWh
IR 2258 float32 ABCD R kWh
IR 2260 float32 ABCD R kWh
IR 2262 float32 ABCD R kWh
HR 0 float32 ABCD R min Minutes into the first demand period; demand values are valid once it reaches the demand period
HR 2 float32 ABCD RW min 0, 5, 8, 10, 15, 20, 30 or 60 minutes, default 60. 0 makes demand show the present value and max demand the maximum since the last reset
HR 6 float32 ABCD R V
HR 8 float32 ABCD R A
HR 12 float32 ABCD RW ms 60, 100 or 200 ms, default 100
HR 14 float32 ABCD RW Writing any value locks; reading also restarts the one-minute password timeout
HR 18 float32 ABCD RW Default 0
HR 20 float32 ABCD RW Modbus address, default 1. Takes effect after a restart
HR 22 float32 ABCD RW Default 0 (400 imp/kWh)
HR 24 float32 ABCD RW Write the password to unlock the protected registers
HR 28 float32 ABCD RW Default 2 (9600)
HR 36 float32 ABCD R W Rated system power, e.g. system volts x system amps x 3 on 3P4W
HR 86 float32 ABCD RW