Eastron SDM630-Modbus Modbus register map

Three-phase multifunction DIN rail energy meter, direct connection (SDM630-Modbus and SDM630-Modbus V2). Values a wiring system does not use read 0

  • Official
  • 97 registers
  • Modbus RTU
  • Revision 3 · 2026-11-10
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based
Max read
80 registers per request

Connection values are defaults: the device may be configured differently.

Map

Registers
12 holding registers, 85 input registers
Groups
12
Revision
3 · 2026-11-10
Added
()
File
maps/eastron/sdm630-modbus.mbmap.json · 19 KB · history
SHA-256
71b8491656e1c7fbae33d55c06acae0337e03e36f789cc05195ee829f287def1
Manufacturer
eastroneurope.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number holding 64512 uint32 ABCD

Sources and notes

Source: Eastron Europe, "Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8"; https://www.eastroneurope.com/images/uploads/products/protocol/SDM630_MODBUS_Protocol.pdf

  • Eastron SDM630-Modbus three-phase energy meter (RS485).
  • Every value is a float32 in two registers. The meter answers FC03, FC04 and FC16 only (no FC06)
  • and rejects reads or writes of an odd number of registers.
AreaAddressNameTypeAccessUnitScaleDescription
IR 0 float32 ABCD R V Valid on 3P4W, 1P2W; reads 0 otherwise
IR 2 float32 ABCD R V Valid on 3P4W; reads 0 otherwise
IR 4 float32 ABCD R V Valid on 3P4W; reads 0 otherwise
IR 6 float32 ABCD R A
IR 8 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 10 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 12 float32 ABCD R W Valid on 3P4W, 1P2W; reads 0 otherwise
IR 14 float32 ABCD R W Valid on 3P4W, 1P2W; reads 0 otherwise
IR 16 float32 ABCD R W Valid on 3P4W; reads 0 otherwise
IR 18 float32 ABCD R VA Valid on 3P4W, 1P2W; reads 0 otherwise
IR 20 float32 ABCD R VA Valid on 3P4W; reads 0 otherwise
IR 22 float32 ABCD R VA Valid on 3P4W; reads 0 otherwise
IR 24 float32 ABCD R var Valid on 3P4W, 1P2W; reads 0 otherwise
IR 26 float32 ABCD R var Valid on 3P4W; reads 0 otherwise
IR 28 float32 ABCD R var Valid on 3P4W; reads 0 otherwise
IR 30 float32 ABCD R Sign follows the direction of the current: positive = forward, negative = reverse; Valid on 3P4W, 1P2W; reads 0 otherwise
IR 32 float32 ABCD R Sign follows the direction of the current: positive = forward, negative = reverse; Valid on 3P4W; reads 0 otherwise
IR 34 float32 ABCD R Sign follows the direction of the current: positive = forward, negative = reverse; Valid on 3P4W; reads 0 otherwise
IR 36 float32 ABCD R ° Valid on 3P4W, 1P2W; reads 0 otherwise
IR 38 float32 ABCD R ° Valid on 3P4W; reads 0 otherwise
IR 40 float32 ABCD R ° Valid on 3P4W; reads 0 otherwise
IR 42 float32 ABCD R V Valid on 3P4W; reads 0 otherwise
IR 46 float32 ABCD R A
IR 48 float32 ABCD R A
IR 52 float32 ABCD R W
IR 56 float32 ABCD R VA
IR 60 float32 ABCD R var
IR 62 float32 ABCD R Sign follows the direction of the current: positive = forward, negative = reverse
IR 66 float32 ABCD R °
IR 70 float32 ABCD R Hz
IR 72 float32 ABCD R kWh
IR 74 float32 ABCD R kWh
IR 76 float32 ABCD R kvarh
IR 78 float32 ABCD R kvarh
IR 80 float32 ABCD R kVAh
IR 82 float32 ABCD R Ah
IR 84 float32 ABCD R W Import minus export
IR 86 float32 ABCD R W Import minus export. The protocol table gives the unit as VA
IR 100 float32 ABCD R VA
IR 102 float32 ABCD R VA
IR 104 float32 ABCD R A Valid on 3P4W; reads 0 otherwise
IR 106 float32 ABCD R A Valid on 3P4W; reads 0 otherwise
IR 200 float32 ABCD R V Valid on 3P4W, 3P3W; reads 0 otherwise
IR 202 float32 ABCD R V Valid on 3P4W, 3P3W; reads 0 otherwise
IR 204 float32 ABCD R V Valid on 3P4W, 3P3W; reads 0 otherwise
IR 206 float32 ABCD R V Valid on 3P4W, 3P3W; reads 0 otherwise
IR 224 float32 ABCD R A Valid on 3P4W; reads 0 otherwise
IR 234 float32 ABCD R % Valid on 3P4W, 1P2W; reads 0 otherwise
IR 236 float32 ABCD R % Valid on 3P4W; reads 0 otherwise
IR 238 float32 ABCD R % Valid on 3P4W; reads 0 otherwise
IR 240 float32 ABCD R %
IR 242 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 244 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 248 float32 ABCD R % Valid on 3P4W, 1P2W; reads 0 otherwise
IR 250 float32 ABCD R %
IR 258 float32 ABCD R A
IR 260 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 262 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 264 float32 ABCD R A
IR 266 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 268 float32 ABCD R A Valid on 3P4W, 3P3W; reads 0 otherwise
IR 334 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 336 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 338 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 340 float32 ABCD R % Valid on 3P4W, 3P3W; reads 0 otherwise
IR 342 float32 ABCD R kWh Import plus export
IR 344 float32 ABCD R kvarh Import plus export
IR 346 float32 ABCD R kWh
IR 348 float32 ABCD R kWh
IR 350 float32 ABCD R kWh
IR 352 float32 ABCD R kWh
IR 354 float32 ABCD R kWh
IR 356 float32 ABCD R kWh
IR 358 float32 ABCD R kWh Import plus export
IR 360 float32 ABCD R kWh Import plus export
IR 362 float32 ABCD R kWh Import plus export
IR 364 float32 ABCD R kvarh
IR 366 float32 ABCD R kvarh
IR 368 float32 ABCD R kvarh
IR 370 float32 ABCD R kvarh
IR 372 float32 ABCD R kvarh
IR 374 float32 ABCD R kvarh
IR 376 float32 ABCD R kvarh Import plus export
IR 378 float32 ABCD R kvarh Import plus export
IR 380 float32 ABCD R kvarh Import plus export
HR 2 float32 ABCD RW min 0, 5, 8, 10, 15, 20, 30 or 60 minutes, default 60. 0 makes demand show the present value and max demand the maximum since the last reset
HR 10 float32 ABCD RW 3 = 3P4W, 2 = 3P3W, 1 = 1P2W. Needs the password
HR 12 float32 ABCD RW ms 60, 100 or 200 ms, default 100
HR 14 float32 ABCD RW Reads 0 = locked, 1 = unlocked; writing any value locks. Reading also restarts the one-minute password timeout
HR 18 float32 ABCD RW 0 = no parity, 1 stop bit (default); 1 = even, 1 stop; 2 = odd, 1 stop; 3 = no parity, 2 stop. Takes effect after a restart
HR 20 float32 ABCD RW Modbus address 1 to 247, default 1. Takes effect after a restart
HR 22 float32 ABCD RW 0 = 0.0025, 1 = 0.01, 2 = 0.1, 3 = 1, 4 = 10, 5 = 100 kWh (kvarh) per pulse
HR 24 float32 ABCD RW Write the password (default 0000) to unlock protected registers for one minute
HR 28 float32 ABCD RW 0 = 2400, 1 = 4800, 2 = 9600 (default), 3 = 19200, 4 = 38400. Takes effect after a restart
HR 86 float32 ABCD RW 1 = import active, 2 = total active, 4 = export active (default), 5 = import reactive, 6 = total reactive, 8 = export reactive
HR 61456 uint32 ABCD W The protocol writes 00 00 here; every Eastron write must cover an even number of registers, so this sends two zero registers with FC16
HR 64512 uint32 ABCD R