Three-phase DIN rail energy meter with a reduced Modbus register set: total power and import/export energy

  • Official
  • 16 registers
  • Modbus RTU
  • Revision 3 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
7 holding registers, 9 input registers
Groups
4
Revision
3 · 2026-10-18
Added
()
File
maps/eastron/sdm72d-m.mbmap.json · 4 KB · history
SHA-256
2fe0ce72f5e02aef96f8575e364b7edc916dada5d569c0ba0b3b2072bfdd3274
Manufacturer
eastroneurope.com

Sources and notes

Source: Zhejiang Eastron Electronic, "SDM72D-M Modbus Protocol", V1.1

  • Measurements are float32 input registers (FC04); settings are float32 holding registers (FC03 read, FC10 write).
  • Settings marked as protected need the password (default 1000) written to the password register first.
AreaAddressNameTypeAccessUnitScaleDescription
IR 52 float32 ABCD R W
IR 72 float32 ABCD R kWh
IR 74 float32 ABCD R kWh
IR 342 float32 ABCD R kWh Import + export
IR 384 float32 ABCD R kWh Import + export
IR 388 float32 ABCD R kWh
IR 390 float32 ABCD R kWh
IR 1280 float32 ABCD R W
IR 1282 float32 ABCD R W
HR 18 float32 ABCD RW Default 0
HR 20 float32 ABCD RW Default 1
HR 24 float32 ABCD RW Write the password (default 1000) to unlock the protected registers
HR 28 float32 ABCD RW Default 2 (9600)
HR 58 float32 ABCD RW s 0 = no automatic scrolling (default)
HR 60 float32 ABCD RW min 0 = backlight always on (default)
HR 61456 uint16 W