Entes EPR-04S Modbus register map

3-phase power meter with RS-485 Modbus RTU: power and cos phi values, two energy counter sets, min/max/demand power values and setup. Values are 32-bit (two registers), energies 64-bit.

  • Official
  • 91 registers
  • Revision 3 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
91 holding registers
Translation tables
3
Revision
3 · 2026-11-10
Added
()
File
maps/entes/epr-04s.mbmap.json · 14 KB · history
SHA-256
fcd94e18acb30ea8b6b124609ad6e4b8cfaa943c2b6556ddeb8a3221b3cc5f07
Manufacturer
entes.com.tr

Sources and notes

  • The previous map had the addresses shifted by 2 and 16-bit types; the table shows 32-bit values, with unused rows for voltage and current.
  • Energy counters and min/max/demand values can be written to set or clear them.
  • The table does not state word order. Big-endian, high word first, is taken from the MPR-53S manual. Not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 20 int32 ABCD R W ×0.1
HR 22 int32 ABCD R W ×0.1
HR 24 int32 ABCD R W ×0.1
HR 26 int32 ABCD R var ×0.1
HR 28 int32 ABCD R var ×0.1
HR 30 int32 ABCD R var ×0.1
HR 32 uint32 ABCD R VA ×0.1
HR 34 uint32 ABCD R VA ×0.1
HR 36 uint32 ABCD R VA ×0.1
HR 38 int32 ABCD R ×0.001
HR 40 int32 ABCD R ×0.001
HR 42 int32 ABCD R ×0.001
HR 44 int32 ABCD R W ×0.1
HR 46 int32 ABCD R W ×0.1
HR 48 int32 ABCD R var ×0.1
HR 50 int32 ABCD R var ×0.1
HR 52 uint32 ABCD R VA ×0.1
HR 54 int32 ABCD R ×0.001
HR 56 int32 ABCD R ×0.001
HR 58 uint32 ABCD R Hz ×0.01
HR 84 uint32 ABCD R Bit 0 = input 1 active, bit 1 = input 2 active (12-48 V AC/DC applied)
HR 86 uint64 ABCD RW Wh
HR 90 uint64 ABCD RW Wh
HR 94 uint64 ABCD RW Wh
HR 98 uint64 ABCD RW Wh
HR 102 uint64 ABCD RW Wh
HR 106 uint64 ABCD RW Wh
HR 110 uint64 ABCD RW Wh
HR 114 uint64 ABCD RW Wh
HR 136 int32 ABCD RW W ×0.1
HR 138 int32 ABCD RW W ×0.1
HR 140 int32 ABCD RW W ×0.1
HR 142 int32 ABCD RW var ×0.1
HR 144 int32 ABCD RW var ×0.1
HR 146 int32 ABCD RW var ×0.1
HR 148 uint32 ABCD RW VA ×0.1
HR 150 uint32 ABCD RW VA ×0.1
HR 152 uint32 ABCD RW VA ×0.1
HR 154 int32 ABCD RW W ×0.1
HR 156 int32 ABCD RW W ×0.1
HR 158 int32 ABCD RW var ×0.1
HR 160 int32 ABCD RW var ×0.1
HR 162 uint32 ABCD RW VA ×0.1
HR 182 int32 ABCD RW W ×0.1
HR 184 int32 ABCD RW W ×0.1
HR 186 int32 ABCD RW W ×0.1
HR 188 int32 ABCD RW var ×0.1
HR 190 int32 ABCD RW var ×0.1
HR 192 int32 ABCD RW var ×0.1
HR 194 uint32 ABCD RW VA ×0.1
HR 196 uint32 ABCD RW VA ×0.1
HR 198 uint32 ABCD RW VA ×0.1
HR 200 int32 ABCD RW W ×0.1
HR 202 int32 ABCD RW W ×0.1
HR 204 int32 ABCD RW var ×0.1
HR 206 int32 ABCD RW var ×0.1
HR 208 uint32 ABCD RW VA ×0.1
HR 216 int32 ABCD RW W ×0.1
HR 218 int32 ABCD RW W ×0.1
HR 220 int32 ABCD RW W ×0.1
HR 222 int32 ABCD RW W ×0.1
HR 224 int32 ABCD RW W ×0.1
HR 226 int32 ABCD RW W ×0.1
HR 228 int32 ABCD RW var ×0.1
HR 230 int32 ABCD RW var ×0.1
HR 232 int32 ABCD RW var ×0.1
HR 234 int32 ABCD RW var ×0.1
HR 236 int32 ABCD RW var ×0.1
HR 238 int32 ABCD RW var ×0.1
HR 240 uint32 ABCD RW VA ×0.1
HR 242 uint32 ABCD RW VA ×0.1
HR 244 uint32 ABCD RW VA ×0.1
HR 246 int32 ABCD RW W ×0.1
HR 248 int32 ABCD RW W ×0.1
HR 250 int32 ABCD RW var ×0.1
HR 252 int32 ABCD RW var ×0.1
HR 254 uint32 ABCD RW VA ×0.1
HR 32768 int16 RW ×0.1 0 to 40000 raw
HR 32769 int16 RW
HR 32770 int16 RW 0-5, see the table for reactive energy calculation
HR 32771 int16 RW min
HR 32772 int16 RW 0-6: 1 W, 10 W, 100 W, 1 kW, 10 kW, 100 kW, 1 MW per pulse
HR 32773 int16 RW 0-5: active, active import, active export, reactive, reactive import, reactive export
HR 32774 int16 RW 0-5: same codes as pulse output 1
HR 32775 int16 RW 0 always counts, 1 digital input 1, 2 digital input 2, 3 counts when counter 2 does not
HR 32776 int16 RW 0 always counts, 1 digital input 1, 2 digital input 2, 3 counts when counter 1 does not
HR 32777 int16 RW 0-247
HR 32778 int16 RW
HR 32779 int16 RW
HR 32780 int16 RW
HR 32781 int16 RW 0-9999