Entes MPR1 Series Modbus register map

MPR14S, MPR15S-22, MPR16S-21 and MPR17S-23 network analysers: measurement block (addresses 0-160): voltages, currents, power, power factor, angles, analog and temperature inputs and counters.

  • Official
  • 81 registers
  • Revision 3 · 2026-11-10

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTUdefault
Unit ID
1default
TCP port
502default
Serial
9600 8E1 · 9600 baud, 8 data bits, even parity, 1 stop bit defaults
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
81 holding registers
Groups
1
Revision
3 · 2026-11-10
Added
()
File
maps/entes/mpr1-series.mbmap.json · 13 KB · history
SHA-256
fa6582ebcc8772dfd3ed82916718c471731c35c4c4f1381eebafb12ec82d981b
Manufacturer
entes.com.tr

Sources and notes

  • Only the measurement block (0-161) is mapped; energy, min/max, THD, setup and record sections of the table are not included.
  • Addresses are 0-based. The table does not state word order; high word first assumed. Not tested on a device.
AreaAddressNameTypeAccessUnitScaleDescription
HR 0 uint32 ABCD R V ×0.1
HR 2 uint32 ABCD R V ×0.1
HR 4 uint32 ABCD R V ×0.1
HR 6 uint32 ABCD R V ×0.1
HR 8 uint32 ABCD R V ×0.1
HR 10 uint32 ABCD R V ×0.1
HR 12 uint32 ABCD R V ×0.1
HR 14 uint32 ABCD R A ×0.001
HR 16 uint32 ABCD R A ×0.001
HR 18 uint32 ABCD R A ×0.001
HR 20 uint32 ABCD R A ×0.001
HR 22 uint32 ABCD R A ×0.001
HR 24 uint32 ABCD R Hz ×0.01
HR 26 float32 ABCD R W
HR 28 float32 ABCD R W
HR 30 float32 ABCD R W
HR 32 float32 ABCD R W
HR 34 float32 ABCD R W
HR 36 float32 ABCD R W
HR 38 float32 ABCD R W
HR 40 float32 ABCD R var
HR 42 float32 ABCD R var
HR 44 float32 ABCD R var
HR 46 float32 ABCD R var
HR 48 float32 ABCD R var
HR 50 float32 ABCD R var
HR 52 float32 ABCD R var
HR 54 float32 ABCD R var
HR 56 float32 ABCD R var
HR 58 float32 ABCD R VA
HR 60 float32 ABCD R VA
HR 62 float32 ABCD R VA
HR 64 float32 ABCD R VA
HR 66 float32 ABCD R VA
HR 68 float32 ABCD R VA
HR 70 float32 ABCD R VA
HR 72 int32 ABCD R ×0.001
HR 74 int32 ABCD R ×0.001
HR 76 int32 ABCD R ×0.001
HR 78 int32 ABCD R ×0.001
HR 80 int32 ABCD R ×0.001
HR 82 int32 ABCD R ×0.001
HR 84 int32 ABCD R ×0.001
HR 86 int32 ABCD R ×0.001
HR 88 int32 ABCD R ×0.001
HR 90 int32 ABCD R ×0.001
HR 92 int32 ABCD R 1 = clockwise, 0 = none, -1 = counter-clockwise
HR 94 uint32 ABCD R % ×0.1
HR 96 uint32 ABCD R % ×0.1
HR 98 uint32 ABCD R ° ×0.1
HR 100 uint32 ABCD R ° ×0.1
HR 102 uint32 ABCD R ° ×0.1
HR 104 uint32 ABCD R ° ×0.1
HR 106 uint32 ABCD R ° ×0.1
HR 108 uint32 ABCD R ° ×0.1
HR 110 uint32 ABCD R ° ×0.1
HR 112 uint32 ABCD R ° ×0.1
HR 114 float32 ABCD R
HR 116 float32 ABCD R
HR 118 float32 ABCD R
HR 120 float32 ABCD R
HR 122 float32 ABCD R
HR 124 float32 ABCD R
HR 126 float32 ABCD R
HR 128 float32 ABCD R
HR 130 float32 ABCD R
HR 132 float32 ABCD R
HR 134 float32 ABCD R
HR 136 float32 ABCD R
HR 138 float32 ABCD R °C
HR 140 float32 ABCD R °C
HR 142 float32 ABCD R °C
HR 144 float32 ABCD R °C
HR 146 float32 ABCD R °C
HR 148 float32 ABCD R °C
HR 150 float32 ABCD R °C
HR 152 float32 ABCD R °C
HR 154 uint32 ABCD R h ×0.001
HR 156 uint32 ABCD R h ×0.001
HR 158 uint32 ABCD R Bit field of the digital inputs
HR 160 uint32 ABCD R Bit field of the digital outputs