MBMap Registry
  1. Devices
  2. Moxa
  3. ioLogik E2260

Moxa ioLogik E2260 Modbus register map

Also covers ioLogik E2260-T

Ethernet micro controller with 6 RTD inputs and 4 digital outputs (Click&Go logic)

  • Official
  • 208 registers
  • Modbus TCP
  • Revision 2 · 2026-10-17

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP
Unit ID
1
TCP port
502
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
118 holding registers, 36 input registers, 54 coils
Groups
4
Revision
2 · 2026-10-17
Added
()
File
maps/moxa/iologik-e2260.mbmap.json · 31 KB · history
SHA-256
300593578d5bde0c36368bd5024617162be674d46b1aaa8ae98097a4122576d0
Manufacturer
moxa.com

Sources and notes

Source: Moxa, "ioLogik E2200 Series User Manual", version 7.2 (July 2022), Appendix I

  • Modbus/TCP address map from Appendix I of the manual. Many values appear twice, as a coil or discrete input and again as a holding register (names ending in "(register)").
  • 32-bit values are two registers; the manual lists the high word first unless the register says otherwise.
  • Not in this map: the DI counter mode values at holding 0x0D00, which the manual lists as two-word values at consecutive addresses.
  • Virtual channels are the average or difference of two RTD channels.
AreaAddressNameTypeAccessUnitScaleDescription
CO 0 bool RW Read: Always 0 Write: 1=Reset to current value, 0=return illegal data value
CO 1 bool RW
CO 2 bool RW
CO 3 bool RW
CO 4 bool RW
CO 5 bool RW
CO 6 bool RW
CO 7 bool RW
CO 8 bool RW
CO 9 bool RW
CO 10 bool RW
CO 11 bool RW
CO 12 bool RW
CO 13 bool RW
CO 14 bool RW
CO 15 bool RW
CO 16 bool RW
CO 17 bool RW
CO 18 bool RW
CO 19 bool RW
CO 20 bool RW
CO 21 bool RW
CO 22 bool RW
CO 23 bool RW
CO 24 bool RW
CO 25 bool RW
CO 26 bool RW
CO 27 bool RW
CO 28 bool RW
CO 29 bool RW
CO 30 bool RW
CO 31 bool RW
CO 32 bool RW
CO 33 bool RW
CO 34 bool RW
CO 35 bool RW
CO 36 bool RW
CO 37 bool RW
CO 38 bool RW
CO 39 bool RW
CO 40 bool RW
CO 41 bool RW
CO 42 bool RW
CO 43 bool RW
CO 44 bool RW
CO 45 bool RW
CO 46 bool RW
CO 47 bool RW
CO 48 bool RW
CO 49 bool RW
CO 50 bool RW
CO 51 bool RW
CO 52 bool RW
CO 53 bool RW
IR 0 uint16 R ×0.1 Read: 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
IR 1 uint16 R
IR 2 uint16 R
IR 3 uint16 R
IR 4 uint16 R
IR 5 uint16 R
IR 6 uint16 R ×0.1 Read: 0~65535, Unit:0.1 (Celsius, Fahrenheit)
IR 7 uint16 R
IR 8 uint16 R
IR 9 uint16 R
IR 10 uint16 R
IR 11 uint16 R
IR 12 uint16 R ×0.1 Read: 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
IR 13 uint16 R
IR 14 uint16 R
IR 15 uint16 R
IR 16 uint16 R
IR 17 uint16 R
IR 18 uint16 R
IR 19 uint16 R
IR 20 uint16 R
IR 21 uint16 R
IR 22 uint16 R
IR 23 uint16 R
IR 24 uint16 R ×0.1 Read: 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
IR 25 uint16 R
IR 26 uint16 R
IR 27 uint16 R
IR 28 uint16 R
IR 29 uint16 R
IR 30 uint16 R
IR 31 uint16 R
IR 32 uint16 R
IR 33 uint16 R
IR 34 uint16 R
IR 35 uint16 R
HR 0 uint32 ABCD RW 0~4294967295
HR 2 uint32 ABCD RW
HR 4 uint32 ABCD RW
HR 6 uint32 ABCD RW
HR 8 uint32 ABCD RW 0~4294967295
HR 10 uint32 ABCD RW
HR 12 uint32 ABCD RW
HR 14 uint32 ABCD RW
HR 16 uint32 ABCD RW 0~4294967295
HR 18 uint32 ABCD RW

Help improve this map