MBMap Registry
  1. Devices
  2. Moxa
  3. ioLogik R1241

Moxa ioLogik R1241 Modbus register map

Also covers ioLogik R1241-T

RS-485 remote I/O with 4 analog outputs (voltage or current)

  • Official
  • 40 registers
  • Modbus RTU
  • Revision 2 · 2026-10-17
  • Identity: serial number

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus RTU
Unit ID
1
Serial
9600 8N1 · 9600 baud, 8 data bits, none parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
32 holding registers, 8 input registers
Groups
2
Revision
2 · 2026-10-17
Added
()
File
maps/moxa/iologik-r1241.mbmap.json · 7 KB · history
SHA-256
a186beb881367830a36acc519eae8e21657dcdb3f4ddffc30b4e72c3ac16ae9f
Manufacturer
moxa.com

Device identity

What a tool can read to check that this map fits the connected device (SPEC.md section 4.7). Registers with a role are read like any other register.

Registers
RoleRegisterAddressTypeValues
Serial number Serial number input 30027 string[6]

Sources and notes

Source: Moxa, "ioLogik R1200 Series User's Manual", edition 3.3 (February 2018), Appendix A

  • The unit ID is set with the two rotary switches (1-99). With the mode switch in Initial position the port runs at 9600 baud, 8N1; the settings in Run mode are configured by software.
  • 32-bit values are high word first.
AreaAddressNameTypeAccessUnitScaleDescription
HR 1184 uint16 RW
HR 1185 uint16 RW
HR 1186 uint16 RW
HR 1187 uint16 RW
HR 1216 uint16 RW
HR 1217 uint16 RW
HR 1218 uint16 RW
HR 1219 uint16 RW
HR 1248 uint16 RW
HR 1249 uint16 RW
HR 1250 uint16 RW
HR 1251 uint16 RW
HR 1280 uint16 RW
HR 1281 uint16 RW
HR 1282 uint16 RW
HR 1283 uint16 RW
IR 30000 uint16 R
IR 30021 uint32 ABCD R
IR 30023 uint32 ABCD R
IR 30025 uint16 R
IR 30026 uint16 R Set with the two rotary switches, 1-99
IR 30027 string[6] R
IR 30037 string[10] R
IR 30058 uint16 R
HR 30001 string[10] RW
HR 30011 string[10] RW
HR 30047 string[5] RW
HR 30052 uint16 RW
HR 30053 uint16 RW s
HR 30054 uint16 RW
HR 30055 uint16 RW
HR 30056 uint16 RW
HR 30057 uint16 RW
HR 30060 uint16 RW
HR 30064 uint16 RW
HR 30066 uint16 RW
HR 30061 uint16 RW
HR 30065 uint16 RW
HR 30067 uint16 RW
HR 30100 string[20] RW

Help improve this map