Schneider Electric Altivar 340 Modbus register map

Altivar 340 variable speed drive: every parameter, by its Modbus (logic) address

  • Official
  • 1,741 registers
  • Modbus TCP and RTU
  • Revision 2 · 2026-10-18

Official: Written from the manufacturer's documentation, but not tested on a device yet. Check the map against the manufacturer's documentation before you write to a live device. Tested it? Report a test.

Communication

Protocol
Modbus TCP and RTU
Unit ID
1
TCP port
502default
Serial
19200 8E1 · 19200 baud, 8 data bits, even parity, 1 stop bit
Byte / word order
ABCD · bytes big-endian, words high first
Addresses
0-based

Connection values are defaults: the device may be configured differently.

Map

Registers
1741 holding registers
Groups
17
Revision
2 · 2026-10-18
Added
()
File
maps/schneider-electric/altivar-340.mbmap.json · 402 KB · history
SHA-256
5bd9c0354b04d7c17a059e7a8297259f02b436c0e873ee87dc07e2e141c992cf
Manufacturer
se.com

Sources and notes

Source: Schneider Electric, Altivar 340 communication parameters (NVE61728 V4.6)

  • The address of each parameter is its logic address, which is also its Modbus register address.
  • Each name ends with the parameter code used in the drive menus and manuals.
  • Parameters marked 'writable only when the motor is stopped' are refused while the drive runs.
  • Many enumerations are shared lists in the source file; only the parameter-specific ones are included here.
AreaAddressNameTypeAccessUnitScaleDescription
HR 3006 uint16 RW Factory setting [Standard access] STD
HR 3010 uint16 RW Writable only when the motor is stopped; Factory setting [High duty] HIGH
HR 3011 uint16 R Factory setting [Unknown rating] NO
HR 3012 uint16 R Factory setting [Unkown voltage] NO
HR 3015 uint16 RW Writable only when the motor is stopped; Factory setting Refer to programming manual
HR 3017 uint16 R Unit: Refer to programming manual; Range 0 ... 65535; Factory setting Refer to programming manual
HR 3022 uint16 RW Writable only when the motor is stopped; Factory setting BIT1
HR 3101 uint16 RW Writable only when the motor is stopped; Factory setting [Switch.frequency type 1] HF1
HR 3102 uint16 RW kHz ×0.1 Range 2.0 kHz ... 16.0 kHz; Factory setting Refer to programming manual
HR 3103 uint16 RW Hz ×0.1 Writable only when the motor is stopped; Range 10.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3104 uint16 RW Hz ×0.1 Range 0.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3105 uint16 RW Hz ×0.1 Range 0.0 Hz ... 599.0 Hz; Factory setting Refer to programming manual
HR 3106 uint16 RW Factory setting [Standard ref template with 0% at init] BSD0
HR 3107 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3108 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3109 uint16 RW Writable only when the motor is stopped; Factory setting [No] NO
HR 3110 uint16 RW Writable only when the motor is stopped; Factory setting Refer to programming manual
HR 3111 uint16 RW V ×0.01 Writable only when the motor is stopped; Range 0.10 V ... 100.00 V; Factory setting 0.20 V
HR 3112 uint16 RW Writable only when the motor is stopped; Factory setting Refer to programming manual
HR 3113 uint16 RW Writable only when the motor is stopped; Factory setting [Measured] HWCOF
HR 3120 uint16 RW Factory setting [No] NO
HR 3130 uint16 RW Factory setting [Standard] STD
HR 3201 uint16 R
HR 3202 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3203 int16 R Hz ×0.1 Range -599.0 Hz ... 599.0 Hz
HR 3204 uint16 R Unit: Refer to programming manual; Range 0 ... 65535
HR 3205 int16 R % ×0.1 Range -3276.7 % ... 3276.7 %
HR 3206 uint16 R
HR 3207 uint16 R V ×0.1 Range 0.0 V ... 6553.5 V
HR 3208 uint16 R V Range 0 V ... 65535 V
HR 3209 uint16 R % Range 0 % ... 200 %
HR 3211 int16 R % Range -32767 % ... 32767 %
HR 3218 int16 R % Range 0 % ... 65535 %
HR 3219 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3222 int16 R Range -32767 ... 32767
HR 3224 uint16 R Unit: Refer to programming manual; Range 0 ... 65535
HR 3225 int16 R Hz ×0.1 Range -3276.7 Hz ... 3276.7 Hz
HR 3226 int16 R Range -32767 ... 32767
HR 3229 uint16 R V ×0.1 Range 0.0 V ... 6553.5 V
HR 3240 uint16 R
HR 3243 uint16 R V ×0.1 Range 0.0 V ... 6553.5 V
HR 3244 uint32 ABCD RW s 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0 s ... 4294967295 s
HR 3246 uint32 ABCD RW s 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0 s ... 4294967295 s
HR 3260 uint32 ABCD RW 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0 ... 4294967295
HR 3263 uint16 R rpm Range 0 rpm ... 65535 rpm
HR 3264 uint32 ABCD RW h 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0 h ... 500000 h
HR 3266 int16 R Hz ×0.1 Range -3276.8 Hz ... 3276.7 Hz
HR 3267 int16 R Hz ×0.1 Range -3276.8 Hz ... 3276.7 Hz
HR 3268 int16 R Unit: Refer to programming manual; Range -32767 ... 32767
HR 3269 uint16 RW ms Range 0 ms ... 10000 ms; Factory setting 0 ms
HR 3274 uint32 ABCD RW h ×0.1 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0.0 h ... 119304.6 h
HR 3276 uint32 ABCD RW h ×0.1 32-bit: the source does not state the word order (high word first assumed); Writable only when the motor is stopped; Range 0.0 h ... 119304.6 h
HR 3278 int16 R % ×0.1 Range -3276.7 % ... 3276.7 %
HR 3279 int16 R Range -32767 ... 32767
HR 3290 int16 R % Range -32767 % ... 32767 %
HR 3292 int16 R Unit: Refer to programming manual; Range -32767 ... 32767
HR 3293 int16 R Unit: Refer to programming manual; Range -32767 ... 32767
HR 3294 int16 R Unit: Refer to programming manual; Range -32767 ... 32767
HR 3297 int16 R % Range -300 % ... 300 %
HR 3298 int16 R Unit: Refer to programming manual; Range -32767 ... 32767
HR 3302 uint16 R Range 0 ... 65535
HR 3340 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3341 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3342 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3343 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3344 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3345 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3346 uint16 RW Range 0 ... 65535; Factory setting 0
HR 3347 uint16 RW Range 0 ... 65535; Factory setting 0
HR 4001 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4002 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4003 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4004 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4005 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4006 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4007 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4008 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4011 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4012 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4013 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4014 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4015 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4016 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 200 ms; Factory setting 2 ms
HR 4201 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4202 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4203 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4204 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4205 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4206 uint16 RW Writable only when the motor is stopped; Factory setting [High level] POS
HR 4221 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4222 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4223 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4224 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4225 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4226 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4241 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4242 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4243 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4244 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms
HR 4245 uint16 RW ms Writable only when the motor is stopped; Range 0 ms ... 60000 ms; Factory setting 0 ms